Cutler-Hammer
1600 A NW Moulded Case Circuit Breaker
Features IEC 60947-2 Breaking Capacity
V AC 50/60 Hz kA rms Icu/Ics
Meets IEC 60947-2 Standards NW HNW
KEMA KEUR Third Party Certified 220-240 85/85 100/100
380-415 50/50 70/50
High Performance 70 kA I.C. Rating @ 415 V Ac 660-690 20/10 25/13
Digitrip RMS 310 Electronic Trip Unit Digitrip RMS 310
LS L - Adjustable Long Delay Pickup 50-100% In
LSI S – Adjustable Short Delay Pickup w/ Fixed Short Delay
2
LSG Time 2-8 x In (I t Response) or Adjustable Short Delay
LSIG Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short
Adjustable Long Time Pickup Delay Time to Instantaneous 0-300 ms
800, 1000, 1250, 1600 G – Adjustable Ground Fault Pickup 200-1200 A with
Adjustable Ground Fault Delay (Flat Response) 0-500 ms
Compact Design Catalog Number
46% Less Panel Space Than R-Frame MCCB Standard I.C. High I.C. Trip Unit
210 mm Wide x 406 mm High x 345 mm Depth 3-Pole
Field Installed Accessories NW316T33WP35 HNW316T33WP35 LS
Auxiliary Switch NW316T32WP35 HNW316T32WP35 LSI
Alarm Switch NW316T35WP35 HNW316T35WP35 LSG
Shunt Trip (Variety of Voltage Ratings) NW316T36WP35 HNW316T36WP35 LSIG
UVR (Variety of Voltage Ratings) 4-Pole
Complete Line of External Accessories NW416T33WP35 HNW416T33WP35 LS
Handle Mech. Rotary, Flex-Shaft NW416T32WP35 HNW416T32WP35 LSI
Lock-off NW416T35WP35 HNW416T35WP35 LSG
Terminals (Busbar) NW416T36WP35 HNW416T36WP35 LSIG
Interphase Barriers
Dimensions
N-Frame, 1600 A MCCB
08/09/02
Cutler-Hammer
1600 A N-Frame
CIRCUIT BREAKERS
08/09/02