0% found this document useful (0 votes)
98 views2 pages

Cutler-Hammer: 1600 A NW Moulded Case Circuit Breaker

The document provides information on Cutler-Hammer 1600A NW Moulded Case Circuit Breakers. It lists key features such as meeting IEC 60947-2 standards, having a high 70kA interrupting capacity rating at 415V AC, and using Digitrip RMS 310 electronic trip units. It also provides specifications on adjustable long time pickup, compact design that takes up 46% less panel space, and a complete line of external accessories. Dimensions and catalog numbers are given for 3-pole and 4-pole options.

Uploaded by

baskaranjay5502
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views2 pages

Cutler-Hammer: 1600 A NW Moulded Case Circuit Breaker

The document provides information on Cutler-Hammer 1600A NW Moulded Case Circuit Breakers. It lists key features such as meeting IEC 60947-2 standards, having a high 70kA interrupting capacity rating at 415V AC, and using Digitrip RMS 310 electronic trip units. It also provides specifications on adjustable long time pickup, compact design that takes up 46% less panel space, and a complete line of external accessories. Dimensions and catalog numbers are given for 3-pole and 4-pole options.

Uploaded by

baskaranjay5502
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Cutler-Hammer

1600 A NW Moulded Case Circuit Breaker

Features IEC 60947-2 Breaking Capacity


V AC 50/60 Hz kA rms Icu/Ics
‰ Meets IEC 60947-2 Standards NW HNW
ƒ KEMA KEUR Third Party Certified 220-240 85/85 100/100
380-415 50/50 70/50
‰ High Performance 70 kA I.C. Rating @ 415 V Ac 660-690 20/10 25/13

‰ Digitrip RMS 310 Electronic Trip Unit Digitrip RMS 310


ƒ LS L - Adjustable Long Delay Pickup 50-100% In
ƒ LSI S – Adjustable Short Delay Pickup w/ Fixed Short Delay
2
ƒ LSG Time 2-8 x In (I t Response) or Adjustable Short Delay
ƒ LSIG Time (Flat Response)
I – Adjustable Instantaneous Pickup by Setting Short
‰ Adjustable Long Time Pickup Delay Time to Instantaneous 0-300 ms
ƒ 800, 1000, 1250, 1600 G – Adjustable Ground Fault Pickup 200-1200 A with
Adjustable Ground Fault Delay (Flat Response) 0-500 ms
‰ Compact Design Catalog Number
ƒ 46% Less Panel Space Than R-Frame MCCB Standard I.C. High I.C. Trip Unit
ƒ 210 mm Wide x 406 mm High x 345 mm Depth 3-Pole

‰ Field Installed Accessories NW316T33WP35 HNW316T33WP35 LS


ƒ Auxiliary Switch NW316T32WP35 HNW316T32WP35 LSI
ƒ Alarm Switch NW316T35WP35 HNW316T35WP35 LSG
ƒ Shunt Trip (Variety of Voltage Ratings) NW316T36WP35 HNW316T36WP35 LSIG
ƒ UVR (Variety of Voltage Ratings) 4-Pole

‰ Complete Line of External Accessories NW416T33WP35 HNW416T33WP35 LS


ƒ Handle Mech. Rotary, Flex-Shaft NW416T32WP35 HNW416T32WP35 LSI
ƒ Lock-off NW416T35WP35 HNW416T35WP35 LSG
ƒ Terminals (Busbar) NW416T36WP35 HNW416T36WP35 LSIG
ƒ Interphase Barriers
Dimensions
N-Frame, 1600 A MCCB

08/09/02
Cutler-Hammer

1600 A N-Frame
CIRCUIT BREAKERS

08/09/02

You might also like