Installation Instructions R-410A Split System Air Conditioner
Installation Instructions R-410A Split System Air Conditioner
These instructions must be read and understood completely before attempting installation.
TABLE OF CONTENTS
Inspect New Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 2                   !          WARNING
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2   DEATH, PERSONAL INJURY, AND/OR PROPERTY
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3         DAMAGE HAZARD
Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4       Failure to carefully read and follow this warning
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . 5 - 8                 could result in equipment malfunction, property
                                                                                           damage, personal injury and/or death.
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 - 10
                                                                                           Installation or repairs made by unqualified per‐
Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11              sons could result in equipment malfunction, prop‐
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11              erty damage, personal injury and/or death.
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . 11                 The information contained in this manual is in‐
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12           tended for use by a qualified service technician fa‐
                                                                                           miliar with safety procedures and equipped with
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12         the proper tools and test instruments.
Comfort Alertt Diagnostics Codes . . . . . . . . . . . . . . 13                            Installation must conform with local building
R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . 14                          codes and with the National Electrical Code
                                                                                           NFPA70 current edition or Canadian Electrical
                                                                                           Code Part 1 CSA C.22.1.
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the
dealer/distributor for information and assistance. The                !           WARNING
qualified installer must use factory authorized kits and
accessories when modifying this product. Refer to the           ELECTRICAL SHOCK HAZARD
individual instructions packaged with the kit or accessory      Failure to turn off the main (remote) electrical dis‐
when installing.                                                connect device could result in personal injury or
The weight of the product requires careful and proper           death.
handling procedures when lifting or moving to avoid             Before installing, modifying or servicing system,
personal injury. Use care to avoid contact with sharp or        turn OFF the main (remote) electrical disconnect
pointed edges.                                                  device. There may be more than one disconnect
Follow all safety codes. Wear safety glasses, protective        device.
clothing, and work gloves. Use a heat sinking material -
such as a wet rag - during brazing operations. Keep a fire
extinguisher available. Consult local codes and the
National Electric Code (NEC) for special requirements.
                                                                      !            CAUTION
Improper installation, adjustment, alteration, service or       PROPERTY DAMAGE HAZARD
maintenance can void the warranty.                              Failure to follow this caution may result in proper‐
                                                                ty damage
                                                                R-410A systems operate at higher pressures than
                                                                R-22 systems. When working with R-410A sys‐
                                                                tems, use only service equipment and replace‐
                                                                ment components specifically rated or approved
                                                                for R-410A service.
LOCATION
Check local codes for regulations concerning zoning,           Locate unit away from recessed or confined areas where
noise, platforms, and other issues.                            recirculation of discharge air may occur (refer to
Locate unit away from fresh air intakes, vents, or             CLEARANCES section of this document).
bedroom windows. Noise may carry into the openings             Roof-top installation is acceptable providing the roof will
and disturb people inside.                                     support the unit and provisions are made for water
Locate unit in a well drained area, or support unit high       drainage and noise/vibration dampening.
enough so that water runoff will not enter the unit.           NOTE: Roof mounted units exposed to wind may require
Locate unit away from areas where heat, lint, or exhaust       wind baffles. Consult the manufacturer for additional
fumes will be discharged onto unit (as from dryer vents).      information.
CLEARANCES
Nominal minimum clearances are 48 inches above unit            Inside corner locations on single story structures require
for discharge air and 18 inches on each side of the coil for   evaluation. Large overhanging soffits may cause air
intake air. Clearance on any one side of the coil (normally    recirculation in a corner area even though recommended
between unit and structure) may be reduced to 6 inches.        minimum clearances are maintained. As a guide, locate
Nominal minimum clearances are based on a solid                the unit far enough out so that half of the discharge grille is
parallel object such as a wall or roof overhang.               out from under the soffit.
The clearance may be reduced for a single object with          When placing two or more units side-by-side, provide a
small surface area, such as the end of a wall, outside         minimum of 18 inches between units.
corner of a wall, fence section, post, etc. As a general       Provide minimum service clearance of 24 inches from
rule, the minimum clearance from the unit should equal         control box corner and side service panel.
the width of the object. For example, a 6 inch fence post
should be a minimum of 6 inches from the unit.                 Refer to Figure 1.
Do not install unit under roof overhangs unless gutters are
present. A minimum vertical clearance of 48 inches is
required to the overhang.
2                                                                                                          421 01 5101 00
INSTALLATION INSTRUCTIONS                                         R-410A Split System Air Conditioner
Wall Wall
                           6”
                                                                              24”
                                                                            Service
     24”                              18”
   Service
                                                                                                Wall
                                                                   18”                    6”
18”
18”
Wall Wall
6” 6”
                                                                24”
                                      18”                     Service                          18”
     24”
   Service
                                                    4”                              6”
                                4”
                                                    wide fence
                                                                              6”
                                                                              Post
Wall
421 01 5101 00                                                                                         3
INSTALLATION INSTRUCTIONS                                                         R-410A Split System Air Conditioner
UNIT SUPPORT
NOTE: Unit must be level  2 degrees ( inch rise or fall            Figure 2                  Tie Down Knockouts
per foot of run) or compressor may not function properly.
A. GROUND LEVEL INSTALLATION                                      ” dia. Tie Down Knockouts                View From Top
                                                                  In Base Pan (2 places)                Product Family: N series
The unit must be level and supported above grade by
beams, platform, or a pad. Platform or pad can be of open
or solid construction but should be of permanent
materials such as concrete, bricks, blocks, steel, or
pressure- treated timbers approved for ground contact.
Soil conditions must be considered so that the platform or
pad does not shift or settle and leave the unit partially
supported. Minimum pad dimensions are shown in Figure                                                                        Base
                                                                                                                              Pan
2.                                                                                                                           Depth
If beams or an open platform are used for support, it is                                                                 C
recommended that the soil be treated or area be graveled
to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is
recommended that supports not be in contact with the
building structure. However, slabs on grade constructions                                                            B
with an extended pad are normally acceptable.
B. ROOF TOP INSTALLATION                                                   A
                                                                                       Base Pan Width
This type of installation is not recommended on wood
frame structures where low noise levels are required.               Base Pan                Tie Down                Minimum
Supporting structure or platform for the unit must be level.        (Square)                Knockouts             Mounting Pad
If installation is on a flat roof, locate unit minimum 6 inches   Width x Depth
                                                                                        A       B         C        Dimensions
above roof level.                                                    (inches)
Place the unit over one or more load bearing walls. If there                    	      
       
           
are several units, mount them on platforms that are                             	             
          
self-supporting and span several load bearing walls.              
  
            	                        
These suggestions are to minimize noise and vibration
transmission through the structure. If the structure is a               ” dia. Tie Down Knockouts         View From Top
home or apartment, avoid locating the unit over                         In Base Pan (2 places)       Product Family: C,H,T series
bedrooms or study.
NOTE: When unit is to be installed on a bonded
guaranteed roof, a release must be obtained from the
building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in
place, remove the knockouts in the base pan and install                                                                        Base
tie down bolts through the holes (refer to Figure 2).                                                                           Pan
                                                                                                                               Depth
Contact local distributor for hurricane hold-down details
and the P.E. (Professional Engineer) certification, when                                                                 C
required.
! CAUTION B
4                                                                                                              421 01 5101 00
INSTALLATION INSTRUCTIONS                                                     R-410A Split System Air Conditioner
REFRIGERATION SYSTEM
A. COMPONENT MATCHES                                           B. REFRIGERANT LINE SETS
Check to see that the proper system components are in          The refrigerant line set must be properly sized to assure
place, especially the indoor coil.                             maximum efficiency and proper oil circulation.
R-410A outdoor units can only be used with R-410A              Refer to Product Specifications and Long Line
specific indoor coils. If there is a refrigerant mis-match,    Applications Guideline for line set sizing.
consult the indoor coil manufacturer to determine if a         NOTE: Total line set length must not exceed 200 feet.
refrigerant conversion kit is available for the indoor coil.
                                                               A crankcase heater must be used when the refrigerant
This outdoor unit is designed for use only with indoor coils   line length exceeds 80 feet.
that utilize a TXV refrigerant metering device. If any other
type of metering device is installed on the indoor coil,       If outdoor unit is more than 10 feet higher than the indoor
consult the indoor coil manufacturer to determine if a TXV     coil, refer to the Extended Length Refrigeration Piping
conversion kit is available.                                   Manual for instructions.
                                                               When the outdoor unit is higher than the indoor coil, the
                                                               vertical separation must not exceed 100 feet.
      !            CAUTION                                     When the outdoor unit is lower than the indoor coil, the
                                                               vertical separation must not exceed 50 feet.
 PRODUCT DAMAGE HAZARD
                                                               If it is necessary to add refrigerant line in the field, use
 Failure to follow this caution may result in product          dehydrated or dry, sealed, deoxidized, copper
 damage.                                                       refrigeration tubing. Do not use copper water pipe.
 Indoor coil and outdoor unit must be listed as a              Do not remove rubber plugs or caps from copper tubing
 certified combination (match) in the ARI Unitary              until connections are ready to be made.
 Directory of Certified Products.                              Be extra careful when bending refrigeration tubing.
 Indoor coil must have R-410A specific, hard shut-             Tubing can “kink” easily, and if this occurs, the entire
 off TXV refrigerant metering device.                          length of tubing must be replaced.
When installing a TXV on an indoor coil, follow the
instructions provided with the new TXV.
A typical TXV installation is shown in Figure 3.
                                INDOOR
                                  COIL
 EQUALIZER
 TUBE
   SENSING                                    SUCTION
   BULB                                       TUBE
                                              LIQUID
                                              TUBE
TXV
     SENSING BULB
     (EITHER SIDE)                            STRAP
                 ÉÉ                 ÉÉ
                         SUCTION
     8 O'CLOCK
                 ÉÉ        TUBE
                                    ÉÉ     4 O'CLOCK
421 01 5101 00                                                                                                          5
INSTALLATION INSTRUCTIONS                                                     R-410A Split System Air Conditioner
                                                             Fill all gaps with RTV caulk. This will prevent noise
      !           WARNING                                    transmission between the tubing and the foundation or
                                                             wall.
 PERSONAL INJURY HAZARD                                      Along floor or ceiling joists, suspend refrigerant lines so
 Failure to relieve system pressure could result in          that they do not contact the building structure, water
 personal injury and/or death.                               pipes, or ductwork. Use insulated or suspension type
                                                             hangers. Metal straps must be at least 1” wide to avoid
 Relieve pressure and recover all refrigerant before         cutting into the tube insulation. Keep the liquid and
 servicing existing equipment, and before final unit         suction lines separate. Refer to Figure 4.
 disposal. Use all service ports and open all flow-
 control devices, including solenoid valves.
                                                                                                         JOIST
     OUTDOOR WALL          INDOOR WALL
                                                                 HANGER STRAP
               CAULK                                          (AROUND SUCTION
                                                                    TUBE ONLY)                         INSULATION
                                          LIQUID TUBE
                                                                                                          SUCTION TUBE
                                          SUCTION TUBE
            INSULATION
                                                                          1” MIN
                                                                                                        LIQUID TUBE
                       THROUGH THE WALL                                            SUSPENSION
 Do not bury more than 36” of line set underground.          E. LIQUID LINE FILTER-DRIER
 Refrigerant may migrate to cooler buried section            Outdoor units are shipped with an appropriate filter-drier
 during extended periods of unit shut-down, caus‐            for installation in the liquid line. Leave the plugs in the tube
 ing refrigerant slugging and possible compressor            ends until the filter-drier is installed. The optimal location
 damage at start-up.                                         for the filter-drier is close to the indoor coil. Install the
 If ANY section of the line set is buried under‐             filter-drier with the arrow pointing towards the indoor coil.
 ground, provide a minimum 6” vertical rise at the           Refer to Figure 5.
 service valve.
6                                                                                                         421 01 5101 00
INSTALLATION INSTRUCTIONS                                                  R-410A Split System Air Conditioner
                                                                  !            CAUTION
                                                            PRODUCT DAMAGE HAZARD
                                                            Failure to follow this caution may result in product
                                                            damage.
     Filter-Drier                            38-11-84       Braze with Sil-Fos or Phos-copper alloy on cop‐
     (arrow points towards indoor coil)                     per-to-copper joints and wrap a wet cloth around
                                                            rear of fitting to prevent damage to TXV.
F. SERVICE VALVES
                                                           H. EVACUATING LINE SET AND INDOOR COIL
Service valves are closed and tube stubs are plugged
from the factory. Outdoor units are shipped with a         The unit is shipped with a factory refrigerant charge. The
refrigerant charge sealed in the unit. Leave the service   liquid line and suction line service valves have been
valves closed until all other refrigerant system work is   closed after final testing at the factory. Do not disturb
complete or the charge will be lost. Leave the plugs in    these valves until the line set and indoor coil have been
place until line set tubing is ready to be inserted.       evacuated and leak checked, or the charge in the unit
                                                           may be lost.
Service valve bodies are brass and tube stubs are
copper.                                                    NOTE: Do not use any portion of the factory charge for
                                                           purging or leak testing. The factory charge is for filling the
                                                           system only after a complete evacuation and leak check
                                                           has been performed.
                                                                  !            CAUTION
                                                            PRODUCT DAMAGE HAZARD
                                                            Failure to follow this caution may result in product
                                                            damage.
                                                            Never use the outdoor unit compressor as a vacu‐
                                                            um pump. Doing so may damage the compressor.
                                                           Line set and indoor coil should be evacuated using the
                                                           recommended deep vacuum method of 500 microns. If
                                                           deep vacuum equipment is not available, the alternate
                                                           triple evacuation method may be used by following the
                                                           specified procedure.
                                                           If vacuum must be interrupted during the evacuation
                                                           procedure, always break vacuum with dry nitrogen.
421 01 5101 00                                                                                                        7
INSTALLATION INSTRUCTIONS                                                      R-410A Split System Air Conditioner
           3000
           2500
                                                                                  CHARGE SYSTEM
           2000
           1500                                 VACUUM TIGHT
                                                TOO WET
           1000                                                 I. OPENING SERVICE VALVES
                                                TIGHT           Outdoor units are shipped with a refrigerant charge
            500                                 DRY SYSTEM      sealed in the unit. Opening the service valves releases
                                                                this charge into the system.
                      0   1   2    3   4    5   6   7
                                  MINUTES                       NOTE: Open the Suction service valve first. If the Liquid
                                                                service valve is opened first, oil from the compressor may
                                                                be drawn into the indoor coil TXV, restricting refrigerant
Triple Evacuation Method
                                                                flow and affecting operation of the system.
The triple evacuation method should only be used when
                                                                Remove Suction service valve cap and insert a hex
system does not contain any water in liquid form and
vacuum pump is only capable of pulling down to 28 inches        wrench into the valve stem. Hold the valve body steady
                                                                with an end-wrench and back out the stem by turning the
of mercury. Refer to Fig. 7 and proceed is as follows:
                                                                hex wrench counterclockwise. Turn the stem until it just
    1. Pull system down to 28 inches of mercury and             contacts the rolled lip of the valve body.
       allow pump to continue operating for an additional       After the refrigerant charge has bled into the system,
       15 minutes.
                                                                open the Liquid service valve.
    2. Close manifold valves or valve at vacuum pump
                                                                NOTE: These are not back-seating valves. It is not
       and shut off vacuum pump.
                                                                necessary to force the stem tightly against the rolled lip.
    3. Connect a nitrogen cylinder and regulator to
       system and fill with nitrogen until system pressure      The service valve cap is a primary seal for the valve and
       is 2 psig.                                               must be properly tightened to prevent leaks. Make sure
                                                                cap is clean and apply refrigerant oil to threads and
    4. Close nitrogen valve and allow system to stand for       sealing surface on inside of cap.
       1 hour. During this time, dry nitrogen will diffuse
       throughout the system absorbing moisture.                Tighten cap finger tight and then tighten additional  of a
                                                                turn (1 wrench flat) to properly seat the sealing surfaces.
    5. Repeat this procedure as indicated in Figure 7.
    6. After the final evacuate sequence, confirm there         J. GAUGE PORTS
       are no leaks in the system. If a leak is found, repeat   Check for leaks at the schrader ports and tighten valve
       the entire process after repair is made.                 cores if necessary. Install plastic caps finger tight.
8                                                                                                        421 01 5101 00
INSTALLATION INSTRUCTIONS                                                    R-410A Split System Air Conditioner
ELECTRICAL WIRING
                                                              Wiring Connections
      !           WARNING                                     Make all outdoor electrical supply (Line Voltage)
                                                              connections with raintight conduit and fittings. Most
 ELECTRICAL SHOCK HAZARD                                      codes require a disconnect switch outdoors within sight of
 Failure to turn off the main (remote) electrical dis‐        the unit. Consult local codes for special requirements.
 connect device could result in personal injury or            Route electrical supply (Line Voltage) wiring through
 death.                                                       knockout hole in bottom of Control Box. Connect wires to
                                                              Contactor and Ground Lug according to Wiring Diagram
 Before installing, modifying or servicing system,
                                                              on unit. Refer to Figure 8.
 turn OFF the main (remote) electrical disconnect
 device. There may be more than one disconnect                Route thermostat wiring through rubber grommet in
 device.                                                      bottom of Control Box. Low voltage lead wires are
                                                              provided in the control box for connection to thermostat
The supply voltage must be 208/230 volts (197 volt            wires (use wire nuts). Refer to Wiring Diagram on unit and
minimum to 253 volts maximum) 60 Hz single phase.             Figure 9 for low voltage wiring examples.
Outdoor units are approved for use with copper                NOTE: Use No. 18 AWG (American Wire Gage)
conductors only. Do not use aluminum wire.                    color-coded, insulated (35 °C minimum) wire. If
Refer to unit rating plate for minimum circuit ampacity and   thermostat is located more than 100 feet (30.5 m) from
circuit protection requirements.                              unit as measured along the control voltage wires, use No.
                                                              16 AWG color-coded wires to avoid excessive voltage
Grounding
                                                              drop.
Permanently ground unit in accordance with the National
Electrical Code and local codes or ordinances. Use a          NOTE: Some models are factory equipped with Comfort
copper conductor of the correct size from the grounding       Alertt Diagnostics device. If Comfort Alert is used as a
lug in control box to a grounded connection in the service    field installed option, then a hot bundle must be run for
panel or a properly driven and electrically grounded          proper connection.
ground rod.
   Figure 8                       Electrical Supply (Line Voltage) Connections
                              DISCONNECT
                             PER NEC AND/OR
                              LOCAL CODES
                                                                CONTACTOR
                                                                 11
                                                  L1
                             FIELD POWER
                                WIRING            L2
                                                                 23 or 13
                             FIELD GROUND
                                 WIRING
                                                          GROUND
                                                            LUG
421 01 5101 00                                                                                                       9
INSTALLATION INSTRUCTIONS                                             R-410A Split System Air Conditioner
24 VAC HOT R R
24 VAC COM C C
INDOOR FAN G G
24 VAC HOT R R
24 VAC COM C C
INDOOR FAN G G
24 VAC HOT R R R
24 VAC COM C C C
INDOOR FAN G G
10                                                                                         421 01 5101 00
INSTALLATION INSTRUCTIONS                                                       R-410A Split System Air Conditioner
START-UP PROCEDURE
  1. Set indoor thermostat selector switch to OFF.                 4. Set indoor thermostat at desired temperature. Be
  2. Turn ON all electrical disconnect devices.                       sure setpoint is below indoor ambient temperature
                                                                      or thermostat will not call for cooling.
  3. If unit has a crankcase heater, energize the heater
     and wait 24 hours before proceeding.                          5. Set indoor thermostat selector switch to COOL.
                                                                      Operate unit for minimum 15 minutes, then check
                                                                      the system refrigerant charge.
REFRIGERANT CHARGE
Outdoor units are shipped with a refrigerant charge to             2. Measure liquid service valve pressure by attaching
match a specific indoor coil and 15 feet of refrigerant line.         an accurate gauge to service port.
If shorter or longer refrigerant lines or a different indoor       3. Measure liquid line temperature by attaching an
coil are used, the charge will have to be adjusted.                   accurate thermistor type sensor or electronic
For different line lengths, add or remove charge based on             thermometer to liquid line near outdoor coil.
0.6 ounces charge per foot of difference. For example, a           4. Refer to unit rating plate for required subcooling
25 foot line set is 10 feet longer than the specified 15 feet.        temperature.
Add 0.6 ounces charge for each of the extra 10 feet:               5. Refer to Figure 10. Find the required liquid line
10 x 0.6 = 6.0 ounces additional charge                               temperature where the rating plate subcooling
This outdoor unit is designed for use only with indoor coils          temperature intersects measured liquid service
that utilize a TXV refrigerant metering device. With an               valve pressure.
indoor TXV, use the subcooling method to make final                6. If the measured liquid line temperature is higher
charge adjustments:                                                   than the chart number, add refrigerant to lower the
                                                                      measured temperature.
NOTE: Only use subcooling charging method when
S outdoor ambient temperature is between 70_F and 100_F          NOTE: When adding refrigerant, charge in liquid form,
S indoor temperature is between 70_ and 80_F                     using a flow restricting device, into the suction port.
S line set is less that 80 feet.                                 If the measured liquid line temperature is lower than the
  1. Operate unit a minimum of 15 minutes before                 chart number, reclaim refrigerant to raise the measured
     checking charge.                                            temperature.
     NOTE: If outdoor unit has a 2-speed fan motor,              Tolerance is  3 °F.
     motor will operate in low speed when outdoor
     ambient temperature is below 82 °F. Pull one of the
     yellow low voltage wires off the fan control and the
     unit will default to high speed fan for servicing.
     Reconnect wire after servicing.
SEQUENCE OF OPERATION
With power supplied to indoor and outdoor units,                 When thermostat is satisfied, its contacts open,
transformer is energized.                                        de-energizing contactor and blower relay. Compressor
On a call for cooling, the thermostat makes circuits R-Y         and motors stop.
and R-G. Circuit R-Y energizes contactor, starting               NOTE: If indoor unit is equipped with a time-delay relay
outdoor fan motor and compressor. Circuit R-G                    circuit, the blower runs an additional length of time to
energizes indoor unit blower relay, starting indoor blower       increase system efficiency.
motor.
421 01 5101 00                                                                                                        11
INSTALLATION INSTRUCTIONS                                                   R-410A Split System Air Conditioner
TROUBLESHOOTING
Some models are factory equipped with the Comfort                                Comfort Alertt Diagnostics
Alertt Diagnostics device in the control box (refer to          Figure 11
                                                                                      (some models)
Figure 11). Comfort Alert provides around-the-clock
monitoring for common electrical problems, compressor                               Compressor Wires
defects, and broad system faults. If trouble is detected, an                        Pass Through Holes (3)
alert code is displayed with a flashing LED indicator. Alert
codes are listed in Figure 12.
The device is factory wired and requires no
modification. Low voltage lead wires are provided in the                                         “Power” LED
control box for connection to thermostat wires (use wire               R
nuts).
NOTE: The RED (R) low voltage lead wire is provided                                          Thermostat Demand
only for powering the Comfort Alert device. To utilize the             C        Y
Comfort Alert device, connect the RED (R) low voltage
lead wire directly to 24 VAC hot at the indoor unit or                          C
                                                                                             24 VAC Common
thermostat. Use one of the spare wires in the thermostat                S       R
cable to bring 24 VAC hot out to the outdoor unit. If there
are no spare wires in the thermostat cable, leave the                                           “Alert” LED
insulation on the end of the RED low voltage lead wire to
avoid an electrical short. The air conditioner will                                             “Trip” LED
function normally without the RED (R) low voltage              24 VAC Hot
lead wire connected.
The Comfort Alert device operates by monitoring the
compressor power leads and the thermostat demand
signal (Y terminal). It draws constant 24 VAC power at the
R and C terminals.
MAINTENANCE
Condensate Drain
During the cooling season, check monthly for free flow of
drainage and clean if necessary.
Cleanliness
These tips will help keep the air conditioner looking better
and working more efficiently:
  1. Free flow of air is essential. Keep fences, shrubs,
     trash cans, and other obstructions at least 18
     inches from all coil inlets.
  2. Keep the coil free of grass clippings, leaves,
     weeds, and other debris.
     NOTE: Coil may occasionally require cleaning with
     a liquid solution. The coil must be cold when
     cleaning. Use an alkaline based cleaner only.
     Cleaning a hot coil or using an acid based cleaner
     will remove the paint from the fins and may clog the
     coil.
  3. Never use a weather cover over the outdoor unit
     unless it is a ventilated type or made of breathable
     fabric that will allow moisture to evaporate rapidly.
     A cover that holds moisture in the unit will cause
     more rust build-up and damage than normal
     exposure to weather.
12                                                                                               421 01 5101 00
INSTALLATION INSTRUCTIONS                                                    R-410A Split System Air Conditioner
421 01 5101 00                                                                                                      13
INSTALLATION INSTRUCTIONS                                                    R-410A Split System Air Conditioner
• R-410A refrigerant operates at 50% - 70% higher pressures than R-22. Be sure that servicing equipment and
  replacement components are designed to operate with R-410A.
• Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
• R-410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
  manifold hose.
• Manifold sets should be 750 psig high-side and 200 psig low-side with 520 psig low-side retard.
• R-410A, as with other HFC refrigerants, is only compatible with POE oils.
• Do not use liquid line filter-driers with rated working pressures less than 600 psig.
• POE oils may cause damage to certain plastics and roofing materials.
• Wrap all filter-driers and service valves with wet cloth when brazing.
• If indoor unit is equipped with an R-22 TXV, it must be changed to an R-410A TXV.
• When system must be opened for service, break vacuum with dry nitrogen and replace all filter-driers.