2x500MW BHUSAVAL TPS
BHARAT HEAVY ELECTRICALS LIMIT
                                                           LV2 NCT-CORE-1
SWITCH YARD PT   400                                       LV2 NCT-CORE-2
                                                              LV2 MVA
                                                           LV2 PT VOLTAGE
                                            STATION
                                        TRANSFORMER HV
SWICTH YARD CT   500                          MVA          80
                                                                            LV2
                                                                   HV
                                                                            LV1
                       115.4734411085
                       0.230946882217            HV TURRET CT        250
                                         HV NEUTRAL CT CORE-01       250
                                         HV NEUTRAL CT CORE-02       250
                                                           LV1 NCT-CORE-2
                                                           LV1 NCT-CORE-1
                                                      DATA SHEET OF STATION TRANSFORMER
                                                      SERIAL NO
                                                        MAKE
                                                    VECTOR GROUP
                                          TRANSFORMER RATING(HV/LV1/LV2)
                                              % IMPEDANCE(HV/LV1/LV2)
                                                  RATED HV CURRENT
                                                RATED SEC -1 CURRENT
                                                RATED SEC -2 CURRENT
                                                 HV TURRET CT RATIO
                                            HV NEUTRAL CT CORE-1CT RATIO
                                            HV NEUTRAL CT CORE-2 CT RATIO
                                           LV1 NEUTRAL CT CORE-1 CT RATIO
                                           LV1 NEUTRAL CT CORE-2 CT RATIO
                                           LV2 NEUTRAL CT CORE-1 CT RATIO
                                           LV2 NEUTRAL CT CORE-2 CT RATIO
NOTE:   Fill the data marker in RED get the value of current through CT's UNDER Normal conditi
W BHUSAVAL TPS
Y ELECTRICALS LIMITED
             300       IN        0
             3150      IN        0    SWGR OCA CT REF CORE-1 PRY    2928.674   3150
              35                      SWGR OCA CT DIFF CORE-2 PRY   2928.674   3150
              6.9
      LV2                                                                        OCA
      LV1                                                                       OBA
            0.461894
               0
               0                      SWGR OBA CT REF CORE-1 PRY    2259.263   3150
                                      SWGR OBA CT REF CORE-2 PRY    2259.263   3150
                 LV1 MVA        45
             LV1 PT VOLTAGE    11.5
              3150      IN       0
              300       IN       0
STATION TRANSFORMER
                       BHEL
                     YNyn0yn0
             400       11.5     6.9
             17.5      32.5      55
                115.473441108545
                2259.26297821066
                2928.67423101382
                   250            1
                   250            1
                   250            1
                   300            1
                  3150            1
                   300            1
                  3150            1
T's UNDER Normal condition.
      0.929738
      0.929738
OCA
OBA
      0.717226
      0.717226
NOTE:
                            FILL ONLY THE DATA IN THE BOXES WHICH ARE MARKED RED.
        PREPARED BY:
                               CT RATIO SWITCHTYARD SIDE
                                         500                       PRY CURRENT IN HV
                                                                         SIDE
            415         0                   0.00210644
                                                                   1.0532193        0
            415        120                  0.00210644
                                                                   1.0532193    120
            415        240                  0.00210644
                                                                   1.0532193    240
           VOLTAGE APPLIED ACROSS HV SIDE DURING STABILITY
                            DETAILS TO BE FURNISH
                SERIAL NO
                   MAKE                                      BHEL
              VECTOR GROUP                                 YNyn0yn0
     TRANSFORMER RATING(HV/LV1/LV2)                 400      11.5
    % IMPEDANCE(HV-LV1/HV-LV2/LV1-LV2)              17.5     32.5
    MVA RATING OF STATION TRANSFORMER                80       45
NORMAL RATED CURENT OF HV/LV1/LV2 SIDE ON 115.4734 2259.263
           THEIR RESP. BASES.
                                                115.4734 4016.468
 CURRENT ON HV/LV1/LV2 SIDE ON 80 MVA BASE
      DIFFERENTIAL CURRENT                           RESTRAINING CURRENT
R-PHASE       Y-PHASE    B-PHASE               R-PHASE     Y-PHASE
  0.0000        0.0000      0.0000              0.009121 0.009121
                  HV STANDBY EARTH FAULT CURRENT
                                 LV1 STANDBY EARTH FAULT CURRENT
                                 LV2 STANDBY EARTH FAULT CURRENT
        1.THE POLARITY OF CT'S CAN BE REVERSED BY CHANGING THE PHASE ANGLE EITHER AT HV/LV1/LV2
NOTE:
        2.CT RATIOS ,PT RATIO AND MVA RATING WILL CHANGE FROM SITE TO SITE.
                                 RATIO                          PRY CURRENT
         CORE-2                     3150                           0.0000000
              SEC CURRENT        0.000000000
         CORE-1                     300                            0.0000000
              SEC CURRENT         0.00000000
                                                                     MVA RATING
                                                                     45
 CT RATIO HV TURET               MVA RATING
        250                                         LV1
                                     80
         0.00421288
                                               HV
         0.00421288
                                                                                  MVA RATING
                                                          LV2
         0.00421288                                                               35
CORE-1      250        0.00000                  0.0000
           CORE-2     250       0.00000   0.0000
                                                            RATIO
                                                   CORE-1
                                                             300
                      415
                                                   CORE-2
                                                            3150
  BHEL
YNyn0yn0
             6.9
             55
             35
           2928.674
           6694.113
AINING CURRENT
           B-PHASE
           0.009121
                      0.00000
                       0.00000
                       0.00000
GLE EITHER AT HV/LV1/LV2 IN BOXES MARKED RED IN COLOR.
TE.
                                                CURRENT FLOWING IN CT SECOND
                                       CORE-1       3150
                                       0.007559      180
              CURRENT FLOWING IN PRY
             23.81122   180
                                       0.007559      300
             23.81122   300
                                       0.007559      420
             23.81122   420
             21.36904   180            0.006784      180
MVA RATING
             21.36904   300            0.006784      300
                      21.36904   420   0.006784      420
  PRY
CURRENT SEC CURRENT
                                       CORE-1       3150
  0.0000    0.00000
                                                CURRENT FLOWING IN CT SECOND
  0.0000     0.0000
URRENT FLOWING IN CT SECONDARY
                   CORE-2        3150
                    0.007559     180
                    0.007559     300
                    0.007559     420
                    0.006784     180
                    0.006784     300
                    0.006784     420
                   CORE-2        3150
URRENT FLOWING IN CT SECONDARY