OVERVOLTAGE RELAY FOR
SUPERVISION OF CTs’ CIRCUITS
                                                                  UB3/59-S
                                                                                               CAT. B7-98
                                                                                                               12-01-99
GENERAL CHARACTERISTICS
Three-phase three-elements sensitive overvoltage relay with adjustable definite time
trip delay complete with time start output relay.
The UB3/59-S is used for supervision of the Current Transformers Secondary circuits
in Busbar differential protection.
SETTINGS
Settings are made on front face by means of two 4-poles DIP-SWITCH that allow to
obtain a wide and accurate setting range for the trip level as well as for the trip time
delay.
SIGNALIZATIONS
!   1 Green led for signalization of auxiliary power supply presence and relay
     regular operation.
!   1 Red led for trip signalization.
!   1 Yellow led for start time monitoring.
COMMANDS
!   Test spring lever switch: when pressed it simulates a voltage beyond the trip
     level and allows the complete functional check of the relay. In one position the
     test function does not operate the output relays; in the other it also operates the
     output relays.
!   Reset after trip of the time delayed output relays R1, R2, R3 can be:
    - manual by reset push button on front face
    - manual by remote push button connected to the relevant terminals provided               ORDERING DATA
      on the relay
    - automatic with differential by connecting a bridge on remote reset terminals.
                                                                                           • Relay Type
OUTPUT RELAYS
!   3 Trip signal relays with one Change-over contacts rating 5A.                          • Rated Input Voltage
!   1 Time start signal relay with one Change-over contact rating 5A.                      • Auxiliary Power Supply
The output relays are normally deenergized (energized on trip).
                                                                                           • Setting Ranges
                                                                                           • Execution
                                                         40
OVERALL DIMENSIONS
See Overall Dimensions - 1 Module Relay.
ELECTRICAL CHARACTERISTICS                                                                             CAT.    B7-98
                                                                                                                   12-01-99
Rated input voltage       : 100 V                    Burden on Input voltage : 0,03VA @ Vn = 100/√3 V
Auxiliary power           :      Type 1   : 24-110V d.c./a.c. ±
supply                                      20%                                                            3W(d.c.);
                                                                      Burden on supply voltage :
                                 Type 2   : 90-220V d.c./a.c. ±                                            6VA(a.c.)
                                            20%
STANDARD SETTING RANGES (Different on request)
           VOLTAGE REGULATION                                               TRIP TIME DELAY
!     Vs = [a0 + (0 ÷ 15)] V                                      !   T = [1+(0 ÷ 15)] x Kt(s)
!     a0 = 2 : Vs = (2 ÷ 17) V      step 1 V                      !   Kt = 1 : T = (1 ÷ 16) s    step 1s
                                                 WIRING DIAGRAM
    Vn (phase-to-phase)
           100V