3500/4500 CENCAL
Software Version V5.1
   Addr.       Size     Item                  Description             R/W   Min     Max     Dp     Def.   Meas.
    hex                                                                                                   Unit
   000A         1                Start / Stop - value 24 (18 Hex)     R/W    0       255
                                 Stop / Start - value 24 (18 Hex)
                                 Reset       - value 128 (80 Hex)
    000E        2          -     A/D reading of remote setpoint        R      0     65535     -     -      cp
    0016        2          -     A/D reading of 50mV reference         R      0     65535     -     -      cp
    0018        2          -     A/D reading of ambient temp.          R      0     65535     -     -      cp
    001A        2          -     A/D reading GND                       R      0     65535     -     -      cp
    001C        2          -     A/D reading of RTD third wire         R      0     65535     -     -      cp
    001E        2          -     A/D reading of main variable          R      0     65535     -     -      cp
    0027        1       PrOG     Selected program                     R/W     0       50      -     0
    0064        2          -     Heating power (*3)                   R/W    0.0    100.0     -     1      %
    0074        2          -     Cooling power (*3)                   R/W    0.0    100.0     -     1      %
    0082        2        P.V.    Process variable                      R    Lo_S    Hi_S    dP_S    -     S.p.
    008E        2        SPR     Remote setpoint value                 R    LoSP    HiSP    dPSP    -     S.p.
    0090        2         SP     Local setpoint                       R/W   _LO_    _HI_    dP_S          S.p.
    0092        2       LOSP     Minimum scale remote setpoint        R/W   Lo_S    Hi_S    dPSP    0     S.p.
    0094        2       HISP     Maximum scale remote setpoint        R/W   Lo_S    Hi_S    dPSP   1000   S.p.
    0096        1       tyPE     Type of probe or linear input        R/W     0       31      -     0      -
    0097        1        Prot    Level of protection                  R/W     0       19      -     0      -
    0098        1       rEG.t    Type of controller                   R/W     0        7      -     0      -
    0099        1       SP.Pr    Type of programmer                   R/W     0        6      -     0      -
    009A        2       _no_     Serial comm. instrument code         R/W     0      9999     -     1      -
    009C        2       LO_S     Minimum scale                        R/W   -1999    9999   dP_S    0     S.p.
    009E        2       HI_S     Maximum scale                        R/W   -1999    9999   dP_S   1000   S.p.
    00A0        1       dP_S     Decimal point position               R/W     0        3      -     0      -
    00A1        1       bArG     Allocation to bargraph “ D “         R/W     0        1      -     0      -
    00A2        1          -     Status of the controller:            R/W     -        -      -      -     -
                                     0H: auto, local
                                     40H: manual, local
                                     80H: auto, remote
                                     C0H: manual, remote
   00A3         1        FLt_    Filter time                          R/W     0      20.0    1      0     sec
   00A4         2        rSt_    Manual reset                         R/W    -99      99     0      0     S.p.
   00A6         2        OFSt    Main input offset                    R/W   -999     999     0      0     S.p.
   00A8         2        HPb-    Heating proportional band            R/W    0.0    999.9    1     2.5     %
   00AA         2        HIt-    Heating integral time                R/W   0.00    99.99    2     4.00   min
   00AC         2        Hdt-    Heating derivative time              R/W   0.00    99.99    2     1.50   min
   00AE         2        CPb-    Cooling proportional band            R/W    0.0    999.9    1     2.5     %
   00B0         2        CIt-    Cooling integral time                R/W   0.00    99.99    2     4.00   min
   00B2         2        Cdt-    Cooling derivative time              R/W   0.00    99.99    2     1.50   min
   00B4         2        P.rSt   Reset power                          R/W     0     100.0    1     0.0     %
   00B6         1       An.O.1   Ref. signal for analog output (*1)   R/W     0       31     -      0      -
                        LOO1     Ref. signal for logic output (*1)            0       5      -
                        rL.O.1   Ref. signal for relay output (*1)            0       9      -
                         E8_1    Ref. signal for MD8-1 output (*1)            0       4      -
    00B7        2       L.OU1    Trimming min. if Out1 = analog       R/W   -200    1000     -              -
                                 (*1)
Addr.   Size   Item                   Description                     R/W   Min     Max     Dp     Def.    Meas.
 hex                                                                                                       Unit
00B8     1      Ct_1    Cycle time if Out1 = logic or relay           R/W    0      200      -      20      sec
                        (*1)
00B9     2     H.OU1    Trimming max. if Out1 = analog                R/W   -1000   200      -               -
                        (*1)
00BB     1     An.O.2   Ref. signal for analog output (*1)            R/W     0      31      -      1
               LOO2     Ref. signal for logic output (*1)                     0       5
               rL.O.2   Ref. signal for relay output (*1)                     0       9
                E8_2    Ref. signal for MD8-1 output (*1)                     0       4
00BC     2     L.OU2    Trimming min. if Out2 = analog                R/W   -200    1000     -               -
                        (*1)
00BD     1      Ct_2    Cycle time if Out2 = logic or relay           R/W    0      200      -      20      sec
                        (*1)
00BE     2     H.OU2    Trimming max. if Out2 = analog                R/W   -1000   200      -               -
                        (*1)
00C0     1     An.O.3   Ref. signal for analog output (*1)            R/W     0      31      -      2        -
               LOO3     Ref. signal for logic output (*1)                     0       5
               rL.O.3   Ref. signal for relay output (*1)                     0       9
                E8_3    Ref. signal for MD8-1 output (*1)                     0       4
00C1     2     L.OU3    Trimming min. if Out3 = analog                R/W   -200    1000     -               -
                        (*1)
00C2     1      Ct_3    Cycle time if Out3 = logic or relay           R/W    0      200      -      0       sec
                        (*1)
00C3     2     H.OU3    Trimming max. if Out3 = analog                R/W   -1000   200      -               -
                        (*1)
00C5     1     An.O.4   Ref. signal for analog output (*1)            R/W     0      31      -      3        -
               LOO4     Ref. signal for logic output (*1)                     0       5
               rL.O.4   Ref. signal for relay output (*1)                     0       9
                E8_4    Ref. signal for MD8-1 output (*1)                     0       4
00C6     2     L.OU4    Trimming min. if Out4 = analog                R/W   -200    1000     -               -
                        (*1)
00C7     1      Ct_4    Cycle time if Out4 = logic or relay           R/W    0      200      -      0       sec
                        (*1)
00C8     2     H.OU4    Trimming max. if Out4 = analog                R/W   -1000   200      -               -
                        (*1)
00CA     1     rL.O.5   Ref. signal for control output 5              R/W    0       9       -      3        -
                        ( relay )
00CB     1      -At-    Valve travel time                             R/W    0.0    20.0     1      0.0    min
00CC     1      Ct_5    Relay cycle time                              R/W     0     200      0       0     sec
                        ( control output 5 )
00CF     1     S.tun    Self-Tuning code                              R/W      0      15      -      0      -
00D0     2     _LO_     Setpoint low limit                            R/W   Lo_S    Hi_S    dP_S     0     S.p.
00D2     2     _HI_     Setpoint high limit                           R/W   Lo_S    Hi_S    dP_S   1000    S.p.
00D4     2     HPHI     Heating power limit                           R/W     0.0   100.0     1    100.0    %
00D6     2     CPHI     Cooling power limit                           R/W     0.0   100.0     1    100.0    %
00D8     2     CSPO     Cooling dead band                             R/W   -25.0    25.0     1     0.0     %
00DA     2      -db-    Valve dead zone                               R/W      0    1000      -      0     S.p.
00DC     2     t_LO     Minimum valve pulse                           R/W     0.0   100.0     1     2.0     %
00DE     2     OFSP     Remote setpoint offset                        R/W    -999    999      -      0     S.p.
00E0     2        -     Alarm point 1                                 R/W   Lo_S    Hi_S    dP_S     0     S.p.
                                                    ( if relative )         -1999
00E2     2     HyS1     Hysteresis alarm 1                            R/W    -999   999      -      -1     S.p.
Addr.   Size   Item                  Description                     R/W   Min     Max    Dp     Def.   Meas.
 hex                                                                                                    Unit
00E4     1     AL1.t Alarm 1 type                                    R/W      0     57      -     0       -
00E5     2      -    Alarm point 2                                   R/W   Lo_S    Hi_S   dP_S    0      S.p.
                                                   ( if relative )         -1999
00E7     2     HyS2 Hysteresis alarm 2                               R/W    -999   999      -     -1    S.p.
00E9     1     AL2.t Alarm 2 type                                    R/W      0     57      -     0      -
00EA     2     AL3 Alarm point 3                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                   ( if relative )         -1999
00EC     2     HyS3 Hysteresis alarm 3                               R/W    -999   999      -     -1    S.p.
00EE     1     AL3.t Alarm 3 type                                    R/W      0     57      -     0      -
00EF     2     AL4 Alarm point 4                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                   ( if relative )         -1999
00F1     2     HyS4 Hysteresis alarm 4                               R/W    -999   999      -     -1    S.p.
00F3     1     AL4.t Alarm 4 type                                    R/W      0     57      -     0      -
00F4     2     AL5 Alarm point 5                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                   ( if relative )         -1999
00F6     2     HyS5 Hysteresis alarm 5                               R/W    -999   999      -     -1    S.p.
00F8     1     AL5.t Alarm 5 type                                    R/W      0     57      -     0      -
00F9     2     AL6 Alarm point 6                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                   ( if relative )         -1999
00FB     2     HyS6 Hysteresis alarm 6                               R/W    -999   999      -     -1    S.p.
00FD     1     AL6.t Alarm 6 type                                    R/W      0     57      -     0      -
00FE     2     AL7 Alarm point 7                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                   ( if relative )         -1999
0100     2     HyS7 Hysteresis alarm 7                               R/W    -999   999      -     -1    S.p.
0102     1     AL7.t Alarm 7 type                                    R/W      0     57      -     0      -
0103     2     AL8 Alarm point 8                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                   ( if relative )         -1999
0105     2     HyS8 Hysteresis alarm 8                               R/W    -999   999      -     -1    S.p.
0107     1     AL8.t Alarm 8 type                                    R/W      0     57      -     0      -
0108     2     AL9 Alarm point 9                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                   ( if relative )         -1999
010A     2     HyS9 Hysteresis alarm 9                               R/W    -999   999      -     -1    S.p.
010C     1     AL9.t Alarm 9 type                                    R/W      0     57      -     0      -
010D     2     AL0 Alarm point 0                                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
                                                 ( if relative )           -1999
010F     2     HyS0    Hysteresis alarm 0                            R/W    -999   999      -     -1    S.p.
0111     1     AL0.t   Alarm 0 type                                  R/W      0     57      -     0      -
0136     2     St.00   Custom scale point 0 (*2)                     R/W   Lo_S    Hi_S   dP_S    0     S.p.
0138     2     St.01   Custom scale point 1 (*2)                     R/W   Lo_S    Hi_S   dP_S    31    S.p.
013A     2     St.02   Custom scale point 2 (*2)                     R/W   Lo_S    Hi_S   dP_S    62    S.p.
013C     2     St.03   Custom scale point 3 (*2)                     R/W   Lo_S    Hi_S   dP_S    94    S.p.
013E     2     St.04   Custom scale point 4 (*2)                     R/W   Lo_S    Hi_S   dP_S   125    S.p.
0140     2     St.05   Custom scale point 5 (*2)                     R/W   Lo_S    Hi_S   dP_S   156    S.p.
0142     2     St.06   Custom scale point 6 (*2)                     R/W   Lo_S    Hi_S   dP_S   187    S.p.
0144     2     St.07   Custom scale point 7 (*2)                     R/W   Lo_S    Hi_S   dP_S   219    S.p.
0146     2     St.08   Custom scale point 8 (*2)                     R/W   Lo_S    Hi_S   dP_S   250    S.p.
0148     2     St.09   Custom scale point 9 (*2)                     R/W   Lo_S    Hi_S   dP_S   281    S.p.
014A     2     St.10   Custom scale point 10 (*2)                    R/W   Lo_S    Hi_S   dP_S   312    S.p.
014C     2     St.11   Custom scale point 11 (*2)                    R/W   Lo_S    Hi_S   dP_S   344    S.p.
014E     2     St.12   Custom scale point 12 (*2)                    R/W   Lo_S    Hi_S   dP_S   375    S.p.
    Addr.    Size Item                 Description          R/W   Min     Max     Dp     Def.    Meas.
     hex                                                                                         Unit
    0150      2   St.13 Custom scale point 13 (*2)          R/W Lo_S      Hi_S    dP_S    406     S.p.
    0152      2   St.14 Custom scale point 14 (*2)          R/W Lo_S      Hi_S    dP_S    437     S.p.
    0154      2   St.15 Custom scale point 15 (*2)          R/W Lo_S      Hi_S    dP_S    469     S.p.
    0156      2   St.16 Custom scale point 16 (*2)          R/W Lo_S      Hi_S    dP_S    500     S.p.
    0158      2   St.17 Custom scale point 17 (*2)          R/W Lo_S      Hi_S    dP_S    531     S.p.
    015A      2   St.18 Custom scale point 18 (*2)          R/W Lo_S      Hi_S    dP_S    562     S.p.
    015C      2   St.19 Custom scale point 19 (*2)          R/W Lo_S      Hi_S    dP_S    594     S.p.
    015E      2   St.20 Custom scale point 20 (*2)          R/W Lo_S      Hi_S    dP_S    625     S.p.
    0160      2   St.21 Custom scale point 21 (*2)          R/W Lo_S      Hi_S    dP_S    656     S.p.
    0162      2   St.22 Custom scale point 22 (*2)          R/W Lo_S      Hi_S    dP_S    687     S.p.
    0164      2   St.23 Custom scale point 23 (*2)          R/W Lo_S      Hi_S    dP_S    719     S.p.
    0166      2   St.24 Custom scale point 24 (*2)          R/W Lo_S      Hi_S    dP_S    750     S.p.
    0168      2   St.25 Custom scale point 25 (*2)          R/W Lo_S      Hi_S    dP_S    781     S.p.
    016A      2   St.26 Custom scale point 26 (*2)          R/W Lo_S      Hi_S    dP_S    812     S.p.
    016C      2   St.27 Custom scale point 27 (*2)          R/W Lo_S      Hi_S    dP_S    844     S.p.
    016E      2   St.28 Custom scale point 28 (*2)          R/W Lo_S      Hi_S    dP_S    875     S.p.
    0170      2   St.29 Custom scale point 29 (*2)          R/W Lo_S      Hi_S    dP_S    906     S.p.
    0172      2   St.30 Custom scale point 30 (*2)          R/W Lo_S      Hi_S    dP_S    937     S.p.
    0174      2   St.31 Custom scale point 31 (*2)          R/W Lo_S      Hi_S    dP_S    969     S.p.
    0176      2   St.32 Custom scale point 32 (*2)          R/W Lo_S      Hi_S    dP_S   1000     S.p.
    0178      2 L.b.A.P L.B.A. alarm power                  R/W   0.0     100.0     1    100.0     %
    017A      2   SOFt Soft-Start time                      R/W   0.0      100      1     0.0     min
    017C      1    SPr.t Type of remote setpoint            R/W    0        8       -      0       -
    017D      1   bAud Baud rate                            R/W    0        3       -      0       -
    017E      2    ArSt Antireset                           R/W    0      9999      -      0      S.p.
    0180      1    E8_ MD8-1 extension mounted              R/W    0        1       -      0       -
    0181      1   dPSP Decimal point for auxiliary input    R/W    0        3       -      0       -
    0182      2    FFd- Feedforward gain                    R/W -100.0    100.0     1      0       %
    0184      1 L.b.A.t. L.B.A. intervention time           R/W   0.0      20.0     1             min
    0185      1      -   Tipe of control cards (*1)          R     -         -      -              -
    8000      1      -   Program running                    R/W    1        50      -              -
    8001      1   CS.tP Current step                        R/W    0        99      -              -
    8002      1   LOOP Number of cycles to repeat           R/W    0       200      -              -
8004+4*(N-1) 1    F.St_ First step of program “ N “         R/W    0        99      -              -
  1 ≤N≤ 50
8005+4*(N-1) 1     L.St Final step of program “ N “         R/W     0       99     -              -
8006+4*(N-1) 1    PrG.t Type of reset                       R/W     0       3      -              -
8007+4*(N-1) 1    LOOP Number of cycles of program “ N “    R/W     0      200     -              -
8110+0CH*n    2   HPbn Group “ n “ heating prop. band       R/W    0.0    999.9    1      0      %
8112+0CH*n    2    HItn Group “ n “ heating integral time   R/W   0.00    99.99    2      0      min
8114+0CH*n    2    Hdtn Group “ n “ heating derivative      R/W   0.00    99.99    2      0      min
                         time
8116+0CH*n    2   CPbn Group “ n “ cooling prop. band       R/W    0.0    999.9    1      0      %
8118+0CH*n    2    CItn Group “ n “ cooling integral time   R/W   0.00    99.99    2      0      min
811A+0CH*n    2    Cdtn Group “ n “ cooling derivative      R/W   0.00    99.99    2      0      min
                         time; 1 ≤ n ≤ 9
    8188      2          Selected setpoint: local            R    _LO_    _HI_    dP_S     -     S.p.
                                             remote               LoSP    HiSP    dPSP
    818C      2    -tH- Elapsed step time                   R/W   00.00   99.23     2    00.00   gg.hh
    818E      2    -tL- Elapsed step time                   R/W   00.00   59.59     2    00.00   mm.ss
   Addr.   Size          Item                 Description                 R/W      Min      Max       Dp        Def.   Meas.
    hex                                                                                                                Unit
8192+12H*m  2           SPm     Setpoint step “ m “                        R/W    _LO_     _HI_      dP_S        0      S.p.
8194+12H*m  2           rHm     Ramp time                                  R/W    00.00    99.23       2         0     gg.hh
8196+12H*m  2           rLm     Ramp time                                  R/W    00.00    59.59       2         0     mm.ss
8198+12H*m  2           SHm     Soak time                                  R/W    00.00    99.23       2         0     gg.hh
819A+12H*m  2           SLm     Soak time                                  R/W    00.00    59.59       2         0     mm.ss
819C+12H*m  2           Hbm     Deviation band                             R/W      0      1000        -         0      S.p.
819E+12H*m  1           G.rm    Gradient                                   R/W      0       200        -         0     digit/
                                                                                                                        min
819F+12H*m        1      dSm    P.I.D. parameter block                     R/W       0       9         -         0       -
81A0+12H*m        1      oAm    8 logic outputs 1-8                        R/W       0      255        -         0       -
81A1+12H*m        1      obm    8 logic outputs 9-16                       R/W       0      255        -         0       -
81A2+12H*m        1      ISm    8 required to be active inputs             R/W       0      255        -         0       -
81A3+12H*m        1       Irm   8 required to be non-active inputs         R/W       0      255        -         0       -
                                0 ≤ m ≤ 99
Remarks:
(*1) Hardware configuration is defined in the control cards:
               bit 0, 1 Card type in position 1
               bit 2, 3 Card type in position 2
               bit 4, 5 Card type in position 3
               bit 6, 7 Card type in position 4
The type for each position is defined as:
                 00 = Analog card
                 01 = Logic card
                 10 = Relay card
                 11 = MD8 extension module/card not installed
(*2) The value of “ Def. “ column is expressed in “ S.p. “, the value read or written from the serial port is
      within a 0 – 65535 range.
            Conversion example from “ S.p. “ to 65535tdths:
            if LO_S = 0, HI_S = 1000, St.01 = 31
            St.01 value read from serial = St.01 * 65535/( HI_S - LO_S ) = 2031
(*3) The value read or written from serial is within a 0 – 65535 range
            Reading example = 50.0 %, Read value = 50.0 * 65535/100 = 32767