SolarBrochure - v06 HEMK
SolarBrochure - v06 HEMK
REFERENCE FS3190M
OUTPUT AC Output Power (kVA/kW) @50°C [1] 3190
AC Output Power (kVA/kW) @40°C [1] 3300
Operating Grid Voltage (VAC) [2] 34.5kV ±10%
Operating Grid Frequency (Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 849V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2] Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 3970
Max. DC short circuit current (A) [4] 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98% including MV transformer (preliminary)
CEC (η) 98% including MV transformer (preliminary)
Max. Power Consumption (KVA) 20
CABINET Dimensions [WxDxH] (ft) 21.7 x 7 x 7
Dimensions [WxDxH] (m) 6.6 x 2.2 x 2.2
Weight (lb) 30865
Weight (kg) 14000
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) [5] 2000m
Noise level [6] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection MV Switchgear (configurable)
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL 1741, CSA 22.2 No.107.1-01, UL 62109-1, IEC 62109-1, IEC 62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547.1-2005 / UL 1741 SA-Sept. 2016
[1] Values at 1.00•Vac nom and cos Ф= 1. Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Consult Power Electronics for other altitudes.
[3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2). [6] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
29
HEMK
UTILITY SCALE CENTRAL STRING INVERTER
OUTDOOR DURABILITY
NEMA 3R / IP54
ICOOL 3
ACTIVE HEATING
3 LEVEL TOPOLOGY
NEW RATINGS
COMBINING
THE BENEFITS
OF CENTRAL AND
STRING INVERTERS
ROBUST DESIGN
NEMA 3R / IP54.
POWER ELECTRONICS
By providing full front access the HEMK series simplifies With the HEMK, Power Electronics offers its most compact
the maintenance tasks, reducing the MTTR (and achieving solution, achieving 3.8MW in just 12ft long, reducing installa-
a lower OPEX). The total access allows a fast swap of the tion costs and labor time.
FRUs without the need of qualified technical personnel.
Based on more than 3 years of experience with our MV degree of protection, without having to maintain cumber-
Variable Speed Drive, the iCOOL3 is the first air-cooling some dust filters or having to use liquid-cooling systems,
system allowing IP54 degree of protection in an outdoor solar avoiding the commonly known inconveniences of it (complex
inverter. iCOOL3 delivers a constant stream of clean air to the maintenance, risk of leaks, higher number of components…),
FRUs, being the most effective way of reaching up to IP54 therefore resulting in an OPEX cost reduction.
VAR AT NIGHT
At night, the HEMK inverter can shift to reactive power compensation mode. The inverter can respond to an external dynamic
signal, a Power Plant Controller command or pre-set reactive power level (kVAr).
ACTIVE HEATING
At night, when the unit is not actively exporting power, the the most efficient and homogeneous way to prevent conden-
inverter can import a small amount of power to keep the sation, increasing the inverters availability and reducing the
inverter internal ambient temperature above -20°C, without maintenance. PATENTED
using external resistors. This autonomous heating system is
POWER ELECTRONICS
MULTILEVEL TOPOLOGY
The multilevel IGBT topology is the most efficient approach design is the result of our experience with 3 level topologies.
to manage high DC link voltages and makes the difference in The 3 level IGBT topology reduces stage losses, increases
the 1,500 Vdc design. Power Electronics has many years of inverter efficiency and minimizes total harmonic distortion.
power design in both inverters and MV drives and the HEMK
VOLTAGE (V)
EASY TO MONITOR
HEMK firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding, active and reactive power
curtailment…), and can be configured to meet specific utility requirements.
1.2
0.8
50%
0.6
0.4
0.2
0
0%
-1 0 1 2 3 4
50Hz 52Hz
SECONDS FREQUENCY (Hz)
PO12.3 BDEW PREPA CEI-016 HECO
Low Voltage Ride Through (LVRT or ZVRT). Inverters can withstand any Frequency Regulation System (FRS). Frequency droop algorithm curtails the
voltage dip or profile required by the local utility. The inverter can immediately active power along a preset characteristic curve supporting grid stabilization.
feed the fault with full reactive current, as long as the protection limits are not
exceeded.
1 1.1
0.8 1.09
0.7 1.085
U 0.6 1.08
Voltage
0.5 1.075
0.4 1.07
0.3 1.065
Q(V) curve. It is a dynamic voltage control function which provides reactive power in order to maintain the voltage as close as possible to its nominal value.
FAST
ISLANDING CONDITION
FREQUENCY (Hz)
SLOW
Transformer Grid
POI Utility
PV array Freesun breaker
TIME (s) inverter
SLOW
R L C Loads
FAST
Frequency Ride Through (FRT). Freesun solar inverters have flexible frequency Anti-islanding. This protection combines passive and active methods that
protection settings and can be easily adjusted to comply with future requirements. eliminates nuisance tripping and reduces grid distortion according to IEC
FRAME 1 FRAME 2
REFERENCE FS2445K FS3670K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2445 3670
AC Output Power(kVA/kW) @40°C [1]
2530 3800
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 690V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 976V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2]
Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4]
4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.9% (preliminary)
Euroeta (η) 98.5% (preliminary) 98.7% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect EEE 1547.1-2005 / UL1741SA-Sept. 2016
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
HEMK 37
FRAME 1 FRAME 2
REFERENCE FS2340K FS3510K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2340 3510
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2285K FS3430K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2285 3430
AC Output Power(kVA/kW) @40°C [1]
2365 3550
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 645V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 913V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2]
Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4]
4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.8% (preliminary) 98.9% (preliminary)
Euroeta (η) 98.4% (preliminary) 98.6% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect EEE 1547.1-2005 / UL1741SA-Sept. 2016
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
HEMK 39
FRAME 1 FRAME 2
REFERENCE FS2235K FS3350K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2235 3350
AC Output Power(kVA/kW) @40°C [1]
2310 3465
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 630V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 891V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2]
Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4]
4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.8% (preliminary)
Euroeta (η) 98.4% (preliminary) 98.6% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect EEE 1547.1-2005 / UL1741SA-Sept. 2016
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2180K FS3270K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2180 3270
AC Output Power(kVA/kW) @40°C [1]
2255 3380
Max. AC Output Current (A) @40°C 2117 3175
Operating Grid Voltage(VAC) [2] 615V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 870V-1310V
Maximum DC voltage 1500V
Number of PV inputs [2]
Up to 36
Number of Freemaq DC/DC inputs [4] Up to 6
Max. DC continuous current (A) [4] 2645 3970
Max. DC short circuit current (A) [4]
4000 6000
EFFICIENCY & AUXILIARY SUPPLY Efficiency (Max) (η) 98.8% (preliminary)
Euroeta (η) 98.4% (preliminary) 98.6% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 12 x 7 x 7
Dimensions [WxDxH] (m) 3.7 x 2.2 x 2.2
Weight (lb) 12125 12677
Weight (kg) 5500 5750
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R - IP54
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect EEE 1547.1-2005 / UL1741SA-Sept. 2016
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for Freemaq DC/DC connection configurations.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.