AUTO START MODULE WITH CAN BUS J1939 PROTOCOL – SMART-CAN
FEATURES
Microcontroller based design                                         ACTUAL SIZE
CAN bus J1939 enabled
Operation by 3 push buttons
Easy to fit DIN standard 72x72 panel mount housing
Connection is via locking plug and socket connectors
Solid-state short circuit protected outputs
LCD display for engine status and to access the menu
Oil change notification alert
Front panel leds for status and alarm indication
Automatic engine starting and stopping
Automatic shutdown on fault condition
Low oil pressure alarm and shut down
High engine temperature alarm and shut down
Dynamo failure alarm and shut down
Over/Under speed alarm and shut down
Coolant level alarm and shut down
General alarm output
DESCRIPTION
Smart-CAN is a new addition to the Smart series. It is an intelligent auto start
and protection module with CAN bus J1939 communication protocol, engine
status display, run hour counter and run hours since the last oil change.
Automatic assembly and microcontroller based high integration design resulted
in this low-cost yet high performance controller.
OPERATION
Stop Mode: In this mode, the engine is shut down along with the module. All alarms are reset.
Auto Mode: In this mode, the genset is ready to start. Starting is controlled by the remote control input. Following is a description of the
operation in this mode:
    1. The Remote Control input receives a start signal (activated by connection to –Vbat).
    2. No action is taken until the delay set by RSP is elapsed.
    3. A starting sequence of a preset number of attempts ATT will initiate.
    4. The Electric Valve engages 0.5sec before the Starter.
    5. If the start signal is removed before the engine starts, all timers are reset and the module is ready for a new sequence.
    6. Cranking is disconnected when the RPM (divided by 60 to convert it to Hz) received through the CAN bus exceeds CRF or a voltage
          exceeding dCd (if not set to bYP) appears on the Dynamo input or the oil pressure switch opens given that boP is not set to bYP
          and its preset delay has elapsed or for Volvo engines, when a running indication is received through the CAN bus.
    7. If the engine fails to start after the preset number of attempts, a scan of the six red leds is initiated to indicate a start fail. The Alarm
          output is activated. The Smart-CAN would reattempt starting by selecting the Stop Mode then selecting Auto Mode or by recycling
          the remote control signal.
    8. After elapse of the warm-up delay, set by WUP, the load contactor is engaged via terminal Contactor and yellow led activated.
    9. All protections are enabled when the engine is running and after the elapse of the fault bypass time set by bYP.
    10. Any fault will shut the load down and then shut the engine down and the corresponding led is lit. Alarm output is activated as well.
    11. When the start signal is removed, the Smart-CAN will shut the load down after the elapse of the delay set by oFF. The engine is shut
          down after the elapse of the cooling time set by COL.
Manual Mode: This mode is similar to the Auto Mode except that the start signal is internally activated.
DISPLAY FUNCTIONS
Genset status: while standing-by for a start signal in Auto Mode, the display shows READY if the genset is ready to start. In case the genset is
not ready, NOTRdY is displayed. This could be the result of three causes: oil pressure switch not connected (or damaged), dynamo input sees a
voltage exceeding dcd or running status was received through the CAN bus. If there is no oil pressure switch, set boP to bYP. If there is no
dynamo (or dynamo not connected), set dCd to bYP and dSd to diS. The display will show CRANKG during cranking and it will also show the
count down of the response, warm-up, load shutdown (off delay) and cooling delays. Following a shutdown due to a fault, the display will show
the DTC (J1939 protocol error code) description of the fault received from the CAN bus. The LCD will show RUNING when the engine is
running, LOADOK when engine is running on load.
Measurements: The LCD also displays measurements received by the module from the engine through the CAN bus. Displayed measurements
                                                      o
are: oil pressure (PSI), engine coolant temperature ( C), fuel consumption (Liters/hour), battery voltage (Vdc), engine speed (RPM), engine total
hours of operation (Hr) and the engine total fuel consumption (L). The display also shows the run hours since the last oil change (recorded by
the Smart-CAN). When the oil run hour reaches RHR, the low oil pressure indicating led will start blinking. Following an oil change, the oil hour
counter can be reset to zero by pressing simultaneously AUTO and HAND push buttons for 2 seconds. Autoscrolling between these
measurements can be done by pressing the AUTO or HAND push button (user should press the one that is already active so as not to change
the operating mode).
ACCESSING THE MENU
The menu is accessed by pressing either AUTO or HAND push buttons for 3 seconds. Once in menu mode (i.e. scrolling the menu and editing
parameters), the AUTO and HAND push buttons will no longer affect the operating mode of the Smart-CAN controller. The AUTO push button
scrolls down the menu and decrements values. The HAND push button selects the menu item for editing and increments values. The new value
will be automatically memorized after 2 seconds if no push buttons are pressed. If no buttons are pressed for 25 seconds, the Smart-CAN will
automatically exit the menu mode.
                                                                                                            ST
                                                            BEIRUT OFFICE: BOUTROS BLDG. CHEIKH-EL-GHABY ST. 1 BSMT   FACTORY: S.& A.S. BLDG.
                                                                           GHABY BEIRUT 2068 7808                              OLD SAIDA ROAD – JIEH - CHOUF
                                                                           LEBANON                                             LEBANON
          S. & A.S. LTD                                                    TEL. 01 216994 FAX 01 339600
                                                                           WWW.SASCONTROLLERS.COM
                                                                                                                               TEL. 07 996333 FAX 07996116
                                                                                                                               SUPPORT@SASCONTROLLERS.COM
MENU DESCRPTION
 Display    Description                                                                     Range                                                    Factory Setting
   rSP      Response delay                                                                  0 to 255sec                                                   5sec
   StA      Starter time                                                                    0 to 255sec                                                   5sec
   bEt      Time between trials                                                             0 to 255sec                                                  12sec
   Att      Number of starting attempts                                                     0 to 255                                                        3
  bYP       Fault bypass delay                                                              0 to 255sec                                                  15sec
  WUP       Warm-up delay                                                                   0 to 255sec                                                  10sec
  OFF       Load shutdown delay (Off delay)                                                 0 to 255sec                                                  10sec
  COL       Engine cooling time                                                             0 to 255sec                                                   5sec
  CRF       Crank disconnect frequency set point                                            0 to 255Hz                                                    15Hz
  OFS       Over frequency set point                                                        0 to 255Hz                                                    55Hz
  UFS       Under frequency set point                                                       0 to 255Hz                                                    45Hz
  OFd       Over frequency delay or disables over frequency                                 DiS, 1 to 255sec                                              2sec
  UFd       Under frequency delay or disables under frequency                               DiS, 1 to 255sec                                              5sec
  CHT       Selects whether to enable cool down after high temperature shutdown             diS, EnA                                                       diS
  bOP       Selects whether to permanently bypass the Oil pressure switch for crank         bYP: bypass OPS for crank disconnect                          3sec
            disconnect or whether to bypass it for a preset delay                           1 to 5sec
  dCd       Selects whether to permanently bypass the dynamo for crank disconnect or        bYP: bypass dynamo for crank disconnect                       10Volts
            sets the voltage above which cranking stops                                     10 to 26Volts
  dSd       Selects whether to disable the dynamo shutdown or sets the voltage below        diS: disables bypass dynamo shutdown                           5Volts
            which there will be a dynamo shutdown                                           5 to 10Volts
  LCL       Low coolant input polarity logic                                                no, nc                                                           nc
   SF       Spare function                                                                  HET: High engine temperature                                    HET
                                                                                            HOT: High oil temperature
                                                                                            LFL: low fuel level
  RHR       Sets the number of hours before alerting for an oil change                      diS, 1 to 255hours                                              150
  ECU       Type of engine electronic control unit used                                     SE: Standard engine (generic J1939)                             SE
                                                                                            VE: Volvo engine
                                                                                            PE: Perkins engine
  LFS       Load factory settings
  EXI       Exit the menu
SPECIFICATION
Operating voltage                           8 to 28vdc
Signal voltage range                      50 to 250vac
Outputs                                         1A 50V
Dimensions (WidthxHghtxDepth)            72x72x32 mm
ABSOLUTE MAXIMUM RATINGS
Supply voltage                                 8-30Vdc
Signal voltage                                  280vac
Outputs                                            1.4A
Operating temperature                       -30 to 70°C
INSTALLATION
                                                                                                                  ST
                                                                  BEIRUT OFFICE: BOUTROS BLDG. CHEIKH-EL-GHABY ST. 1 BSMT   FACTORY: S.& A.S. BLDG.
                                                                                 GHABY BEIRUT 2068 7808                              OLD SAIDA ROAD – JIEH - CHOUF
                                                                                 LEBANON                                             LEBANON
           S. & A.S. LTD                                                         TEL. 01 216994 FAX 01 339600
                                                                                 WWW.SASCONTROLLERS.COM
                                                                                                                                     TEL. 07 996333 FAX 07996116
                                                                                                                                     SUPPORT@SASCONTROLLERS.COM