SPEC.No.
A58353 00304B
                                         DATE         N o v. 1 3 , 2 0 0 7
     SPECIFICATIONS
ENGINE-DRIVEN AC GENERATOR
        MODEL                DA-6000SS
          (60Hz-110/220V)
                       HEAD OFFICE
2-8-5 Nihonbashi-horidomecho, Chuo-ku, Tokyo, 103-8566 Japan
                    TEL +81 - 3 - 6861 - 1111
                    FAX +81 - 3 - 6861 - 1181
1.     APPLICATION
 1.1    This specification covers the water-cooled, diesel engine-driven AC generator model
       DA-6000SS (hereafter referred to as generating set).
 1.2     This generating set shall be designed, manufactured and tested in accordance with the
       latest standards of JIS, JEC and JEM.
     JIS     :   Japanese Industrial Standard
     JEC     :   Standard of The Japanese Electrotechnical Committee
     JEM     :   The Standard Of The Japan Electrical Manufacturer's Association
                  Other matters which are not specifically mentioned in the above standards
                 shall be subject to Denyo Co., Ltd.'s production regulations.
2.     GENERAL
 2.1     Materials and Workmanship
     The materials used in the manufacture of this equipment shall be of the high quality, and
      shall be free from defects and imperfections.
     All materials and apparatus not manufactured by Denyo Co., Ltd. shall be the products of
      well-known manufacturers. The workmanship shall be of the high grade and in
      accordance with the most efficient, up-to-date procedures.
 2.2     Change
          Minor changes after the final design may be made by Denyo Co., Ltd. without prior notice
       to the Purchaser. In case of major changes or additional equipment which may result in an
       increase or decrease of equipment's cost, such modifications shall be made in writing and
       agreed to by both parties prior to production and shall constitute an amendment to these
       specifications.
 2.3     Tests and Inspections
          Routine tests and inspections shall be final in our factory.
       If any tests and inspections beyond the scope of Denyo's standard commercial procedures
       are required by the Purchaser, charges for such inspections or tests shall be added to our
       estimate. Conditions of any such tests and inspections shall be mutually agreed upon
       between both parties.
                                                 -1-
3.     STRUCTURE
         The machine possesses a solid structure, and is comprised of a water - cooled diesel
       engine and a generator, which are directly coupled on a common base.
       A coupling housing is employed to connect the generator to the engine. Firm coupling of the
       engine and generator is ensured by tight connection of the housing exterior. The rotating
       section of the generator is directly coupled to the flywheel of the engine.
         The generator is of single bearing construction.
         The standard generator is of the brushless type.
         A heavy gauge steel bonnet and side door completely cover the engine, generator and
       accessories, protecting the unit from effects of weather or possible handling damages at the
       construction site.
         A lifting hook is attached to the common base, and it extends to the balance point through
       the bonnet top.
4.     SPECIFICATIONS AND PERFORMANCE
 4.1     Ambient Conditions
       This generating set should meet the following conditions:
       (1)   Ambient temperature      :   -5゚C or higher, 40゚C or lower
       (2)   Altitude                 :   up to 500m above sea level
       (3)   Relative humidity        :   85% or lower
       (4)   Place of installation    :   outdoor
 4.2     Dimensions and Weight
                          Length              :   1140mm
                          Width               :    650mm
                          Height              :    795mm
                          Dry weight          :    239kg
                          Total weight        :    264kg (all fluids including fuel)
 4.3     AC Generator
             Generator Model              :       DA-6000SS
             Type                         :       Brushless, revolving-field type
             Excitation                   :       Solid-state, statically excited system
             Continuous Duty Rating       :       6.0    kW
             Standby rating                       6.6    kW
             Voltage                      :       110 / 220 V
             Current                      :       27.3 A
             Frequency                    :       60 Hz
             Rated Speed                  :       3600 min-1
             Power Factor                 :       1.0
             No. of Phase                 :       Single phase (3 wires)
             Insulation system            :       class F
             Cooling System               :       Self - ventilation
             Protection type                      IP20
                                                         -2-
4.4     Diesel Engine
         Maker and model             :     KUBOTA Z482
         Type                        :     Water - Cooled Diesel Engine
         Rated output                :     7.7 kW / 3600 min-1
         Max.output                  :     8.9 kW / 3600 min-1
         No. of cylinders            :     2
         Bore × stroke               :     67 mm × 68 mm
         Piston displacement         :     0.479 L
         Lubricating Oil             :     API service class CD class or higher
         Cooling System              :     Water cooling by radiator with fan
         Starting Motor              :     12 V - 0.7 kW
         Battery                     :     38B20R ( 12 V - 35 Ah )
         Fuel                        :     Diesel fuel ( ASTM No.2 or equivalent )
           - NOTE -
           Continuous Duty Rating     :   The generating set is designed for continuous operation
                                          under normal load conditions [25℃ temperature,
                                          100kPa barometric pressure, 31% relative humidity].
           Standby Rating             :   The generating set is designed to operate continuously
                                          for the duration of a utility power failure. The standby
                                          rating is the maximum intermittent overload rating for
                                          the generating set.
4.5     Voltage Regulation
        The voltage regulation from no load to rated load under a rated power factor shall be
      within ±5 % of rated voltage.
4.6     Speed Regulation
       The speed regulation from no load to rated load under a rated power factor shall be within
      ±5 % of rated speed.
4.7     Limits of Temperature
         Limits of temperature rise of the generator shall be in accordance with relevant Japanese
      standards, based on ambient temperature not exceeding 40℃, and shall not exceed the
      following:
                Armature windings         85℃   (Insulation class F)
                Field windings            85℃   (Insulation class F)
                Bearing                   40℃
                                                 -3-
 4.8     Dielectric Strength Test
           The strength of the windings of the generator and control box shall meet the
       specifications of the high voltage test according to Japanese standards:
                 Armature windings        - Grounding       AC 1500V     (one minute)
                 Field windings           - Grounding       AC 1500V     (one minute)
                 Control box              - Grounding       AC 1500V     (one minute)
5.     INSTRUMENT PANEL AND SYSTEM
 5.1     Generator Control Panel
           The following meters and apparatus are mounted on the control panel:
           AC Voltmeter                                                             1 pc.
           Circuit Breaker                                                          1 pc.
 5.2     Engine Control Panel
           The following control equipment are mounted on the panel:
           Starter Switch                                                           1   pc.
           Operation Switch                                                         1   pc.
           Hour Meter                                                               1   pc.
           Warning Lamp Unit        ( Oil / Water / Charge / Preheat )              1   pc.
 5.3     Output Terminal
           Output Terminal (1-phase)      U,N,V                                     1 pc.
                                                    -4-
 5.4     Safety Controls
         The generating set shall be equipped with automatic safety controls which will shut down
       the engine in the event of any abnormal condition, such as :
                                                             Circuit breaker will
                                  Engine shut down                                     Warning lamp
                                                                     trip
        Low lubricating oil
            pressure                        ○                         -                    ○
         High jacket water
               temp.                        ○                         -                    ○
        Insufficient charge                 ○                         -                    ○
          Over current of
            generator                         -                      ○                      -
              Mark   ○       ;   Operate,
              Mark   -       ;   Not operate
 5.5     Capacity
            Cooling Water Capacity            :   approx.      1.95 L
            Lube oil capacity                 :   approx.      2.05 L
            Fuel tank capacity                :   approx.     25    L
6.     ATTACHMENT
           Instruction manual                                                   1   vol.
           Instruction manual       ( Engine )                                  1   vol.
           Parts List                                                           1   vol.
           Spare Fuse               ( 65A )                                     1   pc.
7.     OPTION PARTS
           AC Ammeter                                                           1 pc.
           Frequency meter                                                      1 pc.
           Idle Control Switch      ( switch & unit )                           1 set.
8.     COATING
         The color of the generator proper and the engine shall be the manufacturer's standard
       colors, and that of the bonnet shall be Munsell No. 7.5BG5/10 .
                                                       -5-
                                         SPEC.No.     A58343 00404A
                                         DATE         N o v. 0 6 , 2 0 0 7
     SPECIFICATIONS
ENGINE-DRIVEN AC GENERATOR
        MODEL                DA-6000SS
          (50Hz-110/220V)
                       HEAD OFFICE
2-8-5 Nihonbashi-horidomecho, Chuo-ku, Tokyo, 103-8566 Japan
                    TEL +81 - 3 - 6861 - 1111
                    FAX +81 - 3 - 6861 - 1181
1.     APPLICATION
 1.1    This specification covers the water-cooled, diesel engine-driven AC generator model
       DA-6000SS (hereafter referred to as generating set).
 1.2     This generating set shall be designed, manufactured and tested in accordance with the
       latest standards of JIS, JEC and JEM.
     JIS     :   Japanese Industrial Standard
     JEC     :   Standard of The Japanese Electrotechnical Committee
     JEM     :   The Standard Of The Japan Electrical Manufacturer's Association
                  Other matters which are not specifically mentioned in the above standards
                 shall be subject to Denyo Co., Ltd.'s production regulations.
2.     GENERAL
 2.1     Materials and Workmanship
     The materials used in the manufacture of this equipment shall be of the high quality, and
      shall be free from defects and imperfections.
     All materials and apparatus not manufactured by Denyo Co., Ltd. shall be the products of
      well-known manufacturers. The workmanship shall be of the high grade and in
      accordance with the most efficient, up-to-date procedures.
 2.2     Change
          Minor changes after the final design may be made by Denyo Co., Ltd. without prior notice
       to the Purchaser. In case of major changes or additional equipment which may result in an
       increase or decrease of equipment's cost, such modifications shall be made in writing and
       agreed to by both parties prior to production and shall constitute an amendment to these
       specifications.
 2.3     Tests and Inspections
          Routine tests and inspections shall be final in our factory.
       If any tests and inspections beyond the scope of Denyo's standard commercial procedures
       are required by the Purchaser, charges for such inspections or tests shall be added to our
       estimate. Conditions of any such tests and inspections shall be mutually agreed upon
       between both parties.
                                                 -1-
3.     STRUCTURE
         The machine possesses a solid structure, and is comprised of a water - cooled diesel
       engine and a generator, which are directly coupled on a common base.
       A coupling housing is employed to connect the generator to the engine. Firm coupling of the
       engine and generator is ensured by tight connection of the housing exterior. The rotating
       section of the generator is directly coupled to the flywheel of the engine.
         The generator is of single bearing construction.
         The standard generator is of the brushless type.
         A heavy gauge steel bonnet and side door completely cover the engine, generator and
       accessories, protecting the unit from effects of weather or possible handling damages at the
       construction site.
         A lifting hook is attached to the common base, and it extends to the balance point through
       the bonnet top.
4.     SPECIFICATIONS AND PERFORMANCE
 4.1     Ambient Conditions
       This generating set should meet the following conditions:
       (1)   Ambient temperature      :   -5゚C or higher, 40゚C or lower
       (2)   Altitude                 :   up to 500m above sea level
       (3)   Relative humidity        :   85% or lower
       (4)   Place of installation    :   outdoor
 4.2     Dimensions and Weight
                          Length              :   1140mm
                          Width               :    650mm
                          Height              :    795mm
                          Dry weight          :    239kg
                          Total weight        :    264kg (all fluids including fuel)
 4.3     AC Generator
             Generator Model              :       DA-6000SS
             Type                         :       Brushless, revolving-field type
             Excitation                   :       Solid-state, statically excited system
             Continuous Duty Rating       :       5.5    kW
             Standby rating                       6.1    kW
             Voltage                      :       110 / 220 V
             Current                      :       25 A
             Frequency                    :       50 Hz
             Rated Speed                  :       3000 min-1
             Power Factor                 :       1.0
             No. of Phase                 :       Single phase (3 wires)
             Insulation system            :       class F
             Cooling System               :       Self - ventilation
             Protection type                      IP20
                                                         -2-
4.4     Diesel Engine
         Maker and model             :     KUBOTA Z482
         Type                        :     Water - Cooled Diesel Engine
         Rated output                :     6.5 kW / 3000 min-1
         Max.output                  :     7.6 kW / 3000 min-1
         No. of cylinders            :     2
         Bore × stroke               :     67 mm × 68 mm
         Piston displacement         :     0.479 L
         Lubricating Oil             :     API service class CD class or higher
         Cooling System              :     Water cooling by radiator with fan
         Starting Motor              :     12 V - 0.7 kW
         Battery                     :     38B20R ( 12 V - 35 Ah )
         Fuel                        :     Diesel fuel ( ASTM No.2 or equivalent )
           - NOTE -
           Continuous Duty Rating     :   The generating set is designed for continuous operation
                                          under normal load conditions [25℃ temperature,
                                          100kPa barometric pressure, 31% relative humidity].
           Standby Rating             :   The generating set is designed to operate continuously
                                          for the duration of a utility power failure. The standby
                                          rating is the maximum intermittent overload rating for
                                          the generating set.
4.5     Voltage Regulation
        The voltage regulation from no load to rated load under a rated power factor shall be
      within ±6 % of rated voltage.
4.6     Speed Regulation
       The speed regulation from no load to rated load under a rated power factor shall be within
      ±7 % of rated speed.
4.7     Limits of Temperature
         Limits of temperature rise of the generator shall be in accordance with relevant Japanese
      standards, based on ambient temperature not exceeding 40℃, and shall not exceed the
      following:
                Armature windings         85℃   (Insulation class F)
                Field windings            85℃   (Insulation class F)
                Bearing                   40℃
                                                 -3-
 4.8     Dielectric Strength Test
           The strength of the windings of the generator and control box shall meet the
       specifications of the high voltage test according to Japanese standards:
                 Armature windings        - Grounding       AC 1500V     (one minute)
                 Field windings           - Grounding       AC 1500V     (one minute)
                 Control box              - Grounding       AC 1500V     (one minute)
5.     INSTRUMENT PANEL AND SYSTEM
 5.1     Generator Control Panel
           The following meters and apparatus are mounted on the control panel:
           Frequency Meter                                                          1   pc.
           AC Voltmeter                                                             1   pc.
           AC Ammeter                                                               1   pc.
           Earth Leakage AC Circuit Breaker (25A)                                   1   pc.
           AC Circuit Breaker (for 220V, 25A)                                       1   pc.
           AC Circuit Breaker (for 220V, 15A)                                       1   pc.
           AC Circuit Breaker (for 110V, 25A)                                       1   pc.
           AC Circuit Breaker (for 110V, 15A)                                       1   pc.
 5.2     Engine Control Panel
           The following control equipment are mounted on the panel:
           Starter Switch                                                           1   pc.
           Idle Control Switch                                                      1   pc.
           Hour Meter                                                               1   pc.
           Warning Lamp Unit        ( Oil / Water / Charge / Preheat )              1   pc.
 5.3     Output Terminal
           1-phase AC Output Terminal (built in)  U,N,V                             1   pc.
           1-phase AC Output Receptacle (220V, 32A)                                 1   pc.
           1-phase AC Output Receptacle (220V, 16A)                                 1   pc.
           1-phase AC Output Receptacle (110V, 32A)                                 1   pc.
           1-phase AC Output Receptacle (110V, 16A)                                 1   pc.
           Ground Terminal (for ELCB)                                               1   pc.
                                                    -4-
 5.4     Safety Controls
         The generating set shall be equipped with automatic safety controls which will shut down
       the engine in the event of any abnormal condition, such as :
                                                           Circuit breaker will
                                  Engine shut down                                   Warning lamp
                                                                   trip
        Low lubricating oil
            pressure                        ○                       -                    ○
         High jacket water
               temp.                        ○                       -                    ○
        Insufficient charge                 ○                       -                    ○
        Over current of    AC
               power                        -                      ○                      -
          Earth leakage of
             AC power                       -                      ○                 ○(Red mark)
           Side door open                   ○                       -                     -
              Mark   ○       ;   Operate,
              Mark   -       ;   Not operate
 5.5     Capacity
            Cooling Water Capacity          :   approx.      1.95 L
            Lube oil capacity               :   approx.      2.05 L
            Fuel tank capacity              :   approx.     25    L
6.     ATTACHMENT
           Parts list                                                         1   vol.
           Instruction manual                                                 1   vol.
           Instruction manual        (Engine)                                 1   vol.
           Earth bar                                                          1   pc.
           Cancellation connect                                               1   pc.
           Spare Fuse                ( 65A )                                  1   pc.
7.     COATING
         The color of the generator proper and the engine shall be the manufacturer's standard
       colors, and that of the bonnet shall be Munsell No. 2.5PB7/5, No. 2.5YR6/2 .
                                                     -5-