PVD Series Parts Verification Sensor

Datasheet
Diffuse or Retroreflective Sensor for Error Proofing of Bin-Picking Operations

• One-component system, easy to mount and even easier to use. Automatically operates in either diffuse or
retroreflective mode, depending on the application
• Automatic setup and adjustment; wide beam pattern provides easy alignment
• Range up to 2 m (6.5 ft) when used with retroreflective target; 400 mm (15.7 in) when used in diffuse mode
• Large job lights on either side of the metal housing can be remotely controlled to initiate user action with a
solid or a blinking green light; job lights turn red to indicate bin-picking errors
• Compact package size; only 30 mm wide × 15 mm deep (1.2 in × 0.6 in)
• Available in 2 lengths to fit existing parts bin sizes and configurations
• Easy DIP-switch adjustments: PNP/NPN output, normally open/normally closed operation, solid/flashing job
light, and gate polarity for job light activation
• Two LEDs indicate power ON and output ON
• Choose 2 m (6.5 ft) unterminated cable or 2 m (6.5 ft) cable with 5-pin Euro-style quick-disconnect
connector
• Heavy-duty protective brackets available
• 12 V dc to 30 V dc operation

WARNING: Not To Be Used for Personnel Protection


Never use this device as a sensing device for personnel protection. Doing so could lead to serious injury or
death. This device does not include the self-checking redundant circuitry necessary to allow its use in personnel safety
applications. A sensor failure or malfunction can cause either an energized or de-energized sensor output condition.

Models
Models 1 Range Array Sensing Beam Supply Voltage Output

PVD100
Retroreflective Mode: up to 2 m (6.5 ft) 100 mm (4 in) long, 4
beams
PVD100Q
Diffuse Mode: up to 400 mm (15.7 in) User-selectable
Visible red, 630 nm 12 V to 30 V dc
NPN/PNP
PVD225 All models may be used in either sensing 225 mm (9 in) long, 8
mode. beams
PVD225Q

Overview
The PVD Series Parts Verification Sensor is a one-component, easy-to-use light screen suited to many part assembly, bin picking (pick-to-
light), and error-proofing applications. The PVD increases task efficiency due to simplified job training, increased quality control (no skipped
components), and reduced rework and inspections. It speeds the resumption of work after breaks and other distractions, and is ideal for
multilingual workplaces where communication is an issue.
The PVD self-contained, solid-state emitter/receiver array is capable of functioning in either diffuse or retroreflective sensing mode. No
configuration is required for this selection. If a retroreflective target is installed opposite the sensor, it will function in retroreflective mode. If
not, it will function in diffuse mode. The sensor’s ongoing self-adjustment feature requires no user adjustment; the sensor adapts to the
sensing conditions after 15 seconds when blocked. Sensor range decreases when no retroreflector is installed.
The DIP-switch-selectable PNP/NPN output interfaces to a system controller, which is pre-programmed for a specific sequence of tasks.
Mounted with its visible red beams stretching across each parts bin, the sensor job light signals the assembler which bins contain items to
be picked in a given operation and in what order they should be picked.
As the assembler takes a part in sequence and breaks the beam, the sensor senses that the part was removed and it sends an output signal
to the controller. The controller then verifies if the correct part was taken and may respond by turning that job light OFF, activating the job
light of the next bin in the sequence. If the assembler reaches into a bin out of sequence, the PVD turns on its output to signal the system
controller and turns on its red job light to signal the assembler that an incorrect pick has occurred.
Standard configuration options are selected by means of a bank of four DIP switches behind a press-on black rubber cover. DIP switch
options include: PNP or NPN output, Normally Open or Normally Closed operation, steady or flashing job light, and job light control input.

1 • To order the 9 m (30 ft) cable model, add the suffix "W/30" to the cabled model number. For example, PVD100 W/30.
• To order the 150 mm (6 in) cable model with a quick disconnect, add the suffix "W/6IN" to the cabled model number. For example,
PVD100Q W/6IN.
• Models with a quick disconnect require a mating cordset.

Original Document 4 August 2016


113230 Rev. G

113230
PVD Series Parts Verification Sensor

110 mm
100 mm
90 mm

to Always Block a Beam


Minimum Object Size
80 mm
70 mm
60 mm
50 mm
40 mm
30 mm
20 mm
MODE 10 mm
Job Lights 0
(Error Lights) Status Configuration 0 0.5 m 1m 1.5 m 2m 2.5 m
Indicators Switch Cover Range

Figure 1. Sensor features Figure 2. Minimum object detection size (retroreflective operation)

Installation
Multiple sensors located farther than the sensor's maximum range from one another are unlikely to cause crosstalk problems. However,
when multiple sensors are mounted in a confined area, take care to avoid crosstalk between them. Alternate the relative position of adjacent
sensors and/or reflectors. Sensors positioned above or below one another should not create crosstalk difficulties. Mount the sensor and
reflector parallel.

Sensor

Reflector

Reflector

Sensor

Sensor
MODE

Reflector

Sensor

Reflector
MODE

MODE

Figure 3. Examples of Appropriate Positions Figure 4. Example of Incorrect Position

2 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 113230 Rev. G


PVD Series Parts Verification Sensor

Mounting
The wide beam pattern of PVD sensors simplifies their alignment. M4 stainless steel fasteners and
two stainless steel brackets are included with each sensor.
Mount the sensor and its reflector, if used, parallel to one another in the same plane, and their tops
and bottoms aligned.
1. From a common point of reference, make measurements to locate the sensor and its
reflector, if used, in the same plane with their midpoints directly opposite each other.
2. Mount the included brackets to the top and bottom of each sensor, as shown.
3. Mount the sensor in its brackets and the reflector, if used, being careful to position the
sensor's red lenses directly facing the reflector.
4. Measure from one or more reference planes (for example, the building or bin floor) to the
same point(s) on the emitter and receiver to verify their mechanical alignment. (If the
sensors/reflectors are mounted exactly vertical or horizontal, a carpenter’s level may be
helpful. A straightedge or a string extended between the sensor and the bin wall may also
be helpful.)

MODE
5. Also check “by eye” for line-of-sight alignment.
6. Make any necessary final mechanical adjustments, and hand-tighten the bracket hardware.
7. After the electrical hookup is complete, check for beam alignment. If necessary, re-align the
emitter and receiver at that time.

Figure 5. PVD Mounting


Hardware

Wiring
All models feature integral 2 m (6.5 ft) long, 3.3 mm (0.13 inch) diameter PVC-jacketed cables. Models whose model numbers end in “Q”
are terminated with quick-disconnect (QD) Euro-style 5-pin connectors; other models have unterminated ends. Optional mating QD cables
are available. Either 4-pin or 5-pin QD cables may be used; the center pin of a 5-pin cable (gray wire, pin 5) is unused in normal operation.
Wiring is functionally identical for cabled and quick-disconnect models.

NPN (Sinking) Output PNP (Sourcing) Output Key

1 = Brown
1 1 2 = White
+ +
3
12-30V dc
3
12-30V dc 3 = Blue
– – 4 = Black
4 4 5 = Gray
Load Load
2 2
Job Light Control Job Light Control
5 5
Not Used Not Used

See Configuration on page 3 for job light control input requirements.

Configuration
To configure the PVD, set the DIP switches as shown, using the supplied plastic screwdriver to avoid damaging the switches or causing a
short circuit.

Cover Removal Cover Replacement

P/N 113230 Rev. G www.bannerengineering.com - Tel: +1-763-544-3164 3


PVD Series Parts Verification Sensor

Cover Removal Cover Replacement

Insert a fingernail or small screwdriver into To replace the switch cover, align one edge of the cover with the edge of the sensor
the slot; apply gentle pressure, angling housing opening. Then press the front corners into place.
away from the sensor lens. The cover will
remain tethered to the sensor housing.

The switches determine four status operating modes:

PVD Configuration DIP Switch Settings

The factory default setting is ON for all switches Switch Condition

1 ON = PNP output
OFF = NPN output

2 ON = Normally Open
OFF = Normally Closed

3 ON = Job light steady


OFF = Job light flashes
O
N
O
4 Job light control input: Connect the white wire as follows:
F
F 1 2 3 4

PNP Output
ON Example Shown: ON = Job light ON for +10 to 30V dc (29kΩ input impedance)
Switch #1 OFF OFF = Job light ON for 0 to 1.5V dc/open circuit
Switch #2 ON
Switch #3 OFF NPN Output
Switch #4 ON ON = Job light ON for +10 to 30V dc/open circuit
OFF OFF = Job light ON for 0 to 1.5V dc (10kΩ input impedance)

Figure 6. Configuration DIP switch setting positions

Status Indicators/Troubleshooting
Indicator Condition Description Status Indicators

Steady Output is active (Changing Switch #2 to N.C. turns the yellow


Yellow indicator ON when the system is clear)
#1
OFF Output is inactive (Changing Switch #2 to N.O. turns the
yellow indicator ON when the system is blocked)

Steady Power is ON and system is OK


Green

Flashing Blanking is enabled MODE


#2 Green

OFF Power is OFF


Status Indicator #1
Status Indicator #2

4 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 113230 Rev. G


PVD Series Parts Verification Sensor

Specifications
Supply Voltage and Current Output Protection
Input Voltage: 12 V dc to 30 V dc (10% maximum ripple at 10% duty cycle) Protected against false pulse on power-up and short circuit of outputs
Input Current: less than 88 mA at 12 V dc, less than 75 mA at 24 V dc and less Output Response Time
than 72 mA at 30 V dc (exclusive of load)
400 ms (includes standard 100 ms ON-delay and 100 ms OFF-delay)
Supply Protection Circuitry Delay at Power-Up
Protected against reverse polarity and transient overvoltages Less than 1.0 second
Sensing Beam
Sensing Resolution
Visible red, 630 nm
See Dimensions on page 6 for Minimum Object Detection Zone
Sensing Range Retroreflective: 51 mm at 406 mm range, 100 mm at 2 m (2.0 in dia. at 16 in
Retroreflective applications: 2 m (6.5 ft) using 25 mm (1 in) wide range, 3.9 in at 6.5 ft); see Figure 2 on page 2
retroreflective tape Diffuse: 55 mm dia. at 400 mm range (2.16 in at 15.7 in range)
Diffuse applications: 400 mm (15.7 in) with 18% reflectivity gray card target
Indicators
Sensing Height Green LED: Power ON/OFF
4-channel models: 111 mm (4.4 in) Yellow LED: Output ON/OFF
8-channel models: 240 mm (9.4 in) Job Light (Diffused Green LED): Turned ON and OFF by applying an external
Beam Spacing signal to the Job input (white wire). The job lights will be active high or active
low, depending on DIP switch 4 selection.
28.6 mm (1.125 in)
Error Light (Diffused Red LED): Turned ON and OFF by detection of an output
Output Configuration event when job light is not ON.
User-selectable via DIP switch:
Indicator Light Lumens
1 open-collector PNP (current sourcing) or 1 open-collector NPN (current sinking)
Output Rating Light Function Color Typical Wavelength Typical Intensity (lm)
150 mA maximum
OFF-state leakage current: less than 10 microamps Job Light Green 525 nm 12
ON-state saturation voltage: NPN — less than 1 V dc at 150 mA; PNP — less than
Error Light Red 625 nm 2.5
2 V dc at 150 mA
Required Overcurrent Protection

WARNING: Electrical connections must be made Adjustments


by qualified personnel in accordance with local and 4 DIP switches, located behind access panel (default setting is ON position)
national electrical codes and regulations.
Construction
Overcurrent protection is required to be provided by end product application per Black painted aluminum housing; acrylic lenses; thermoplastic polyester end
the supplied table. caps; thermoplastic elastomer programming switch cover; stainless steel
mounting brackets and hardware
Overcurrent protection may be provided with external fusing or via Current
Limiting, Class 2 Power Supply. Connections
Supply wiring leads < 24 AWG shall not be spliced. 5-conductor PVC-jacketed 2 m (6.5 ft) cable which is either unterminated or
For additional product support, go to http://www.bannerengineering.com. terminated with a 5-pin Euro-style quick-disconnect connector, depending on
model. Cable diameter is 3.3 mm (0.13 in).
Supply Wiring (AWG) Required Overcurrent Protection (Amps) Environmental Rating
NEMA 2; IEC IEC IP62
20 5.0
Operating Conditions
22 3.0 Temperature: 0 °C to +50 °C (+32 °F to +122 °F)
Humidity: 90% at +50 °C maximum relative humidity (non-condensing)
24 2.0
Certifications
26 1.0

28 0.8

30 0.5

P/N 113230 Rev. G www.bannerengineering.com - Tel: +1-763-544-3164 5


PVD Series Parts Verification Sensor

Dimensions
3.9 mm 21.1 mm 22.1 mm
(0.15") (0.83") (0.83")

Minimum Object Detection Zone

18.0 mm
(0.71")

MODE

130.0 mm
4 x ø4.45 mm
(5.12")
(0.175")
137.8 mm
(5.43")

3.9 mm 29.2 mm 29.2 mm


(0.15") (1.15") (1.15")

Minimum Object Detection Zone

18.0 mm
(0.71")

MODE

258.6 mm
(10.19") 4 x ø4.45 mm
(0.175")
266.4 mm
(10.49")

1.4 mm
43.2 mm 71.8 mm (0.06")
Cable
(1.70") (2.83")

15.0 mm
(0.59")
30.0 mm
(1.18")

SMBPVA1 Standard Bracket (2 Included with PVD) Hardware Included with Each Sensor (kit part
number 50532)

5.0 mm
4 x ø4.6 mm Qty Description
(0.20")
(0.18") 5.0 mm
2 x 4.8 mm
(0.20") 4 Stainless steel Phillips panhead machine screws
(0.19")
(M4 x 0.7 x 12)
10.2 mm
(0.40") 2 Stainless steel Phillips panhead machine screws
20.1 mm (M4 x 0.7 x 6)
(0.79")
10.2 mm
(0.40") 2 Stainless steel Phillips panhead machine screws
(M4 x 0.7 x 18)
4 x R2.54
(0.10") 6.0 mm 4 Stainless steel hex nuts (M4 x 0.7)
18.0 mm (0.24")
6.1 mm
(0.71") 4 Stainless steel lock washers (M4 x 0.7)
(0.24") 6.0 mm
40.6 mm (0.24")
(1.60") 1 Plastic screwdriver (3.6 cm/1.4 in long)

2.0 mm
22.9 mm (0.08")
(0.90")

6 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 113230 Rev. G


PVD Series Parts Verification Sensor

Accessories
Cordsets
4-Pin Threaded M12/Euro-Style Cordsets

Model Length Style Dimensions Pinout (Female)

MQDC-406 1.83 m (6 ft)

MQDC-415 4.57 m (15 ft)


44 Typ. 2
1
MQDC-430 9.14 m (30 ft)
3
Straight 4
M12 x 1
MQDC-450 15.2 m (50 ft) 1 = Brown
ø 14.5
2 = White
3 = Blue
4 = Black

5-Pin Threaded M12/Euro-Style Cordsets—Single Ended

Model Length Style Dimensions Pinout (Female)

MQDC1-501.5 0.50 m (1.5 ft)


2
MQDC1-506 1.83 m (6 ft) 44 Typ. 1

MQDC1-515 4.57 m (15 ft) 3


Straight
4 5
1 = Brown
M12 x 1
MQDC1-530 9.14 m (30 ft) 2 = White
ø 14.5 3 = Blue
4 = Black
5 = Gray

Brackets
All measurements are listed in millimeters, unless noted otherwise.

Bracket Selection Table

Bracket Model Requires Use of May Be Used with Bracket Model Requires Use of May Be Used with
Bracket Model(s) Bracket Model(s) Bracket Model(s) Bracket Model(s)

SMBPVD1 SMBPVD100A(B) SMBPVA9 SMBPVD100A(B)


N.A.
(included with N.A. SMBPVD225A(B) SMBPVD225A(B)
PVD System) SMBPVA2
SMBPVA2 SMBPVD100A(B)
N.A.
SMBPVD100A(B) SMBPVD1 SMBPVD225A(B)
SMBPVD225A(B) SMBPVA5(10)
N.A.
SMBPVA9 SMBPVA7 SMBPVA5C SMBPVD100A(B)
SMBPVA2 or SMBPVD225A(B)
SMBPVA10C
SMBPVA5C SMBPVD100A(B)
SMBPVA10C SMBPVD225A(B) SMBPVA8 SMBPVA5C SMBPVD100A(B)
N.A.
SMBPVA7 or SMBPVD225A(B)
SMBPVA8 SMBPVA10C

NOTE: Standard mounting brackets are included with each PVD System. The following brackets are in addition to the
standard brackets.

SMBPVA2 SMBPVA7
A 32
• Set of 4 molded brackets • One-piece bracket for mounting
• Snaps onto standard 28 mm to 28 mm (1.1 in) diameter
(1.1 in) diameter pipe pipe
• Black-painted steel B 51
• 2 required per sensor
• Requires SMBPVA..C for
mounting at an angle ±90°

C 41

A = M4 x 0.5, B = ø 5.2, C = ø 4.2

P/N 113230 Rev. G www.bannerengineering.com - Tel: +1-763-544-3164 7


PVD Series Parts Verification Sensor

SMBPVA8 SMBPVA9
• Heavy-duty 2-part bracket A • Pair of two-piece swivel
mounts to 28 mm (1.1 in) brackets
diameter pipe • Mount directly to sensor or to
• Cold-rolled steel with zinc PVD or PVA protective
finish 33 brackets
• Requires SMBPVA..C for • Designed for mounting
mounting sensor to "look down"
A=ø 30.5, B=ø 7.1
65 B

SMBPVD..A & SMBPVD..AB SMBPV..C


35.7 mm 35.7 mm
(1.40 in.) (1.40 in.)
• Heavy-duty protection brackets • Back-mounted bracket for 2 x Ø7.3
mounting to SMBPVA7 or L
• Some models include DIP-switch
access port SMBPVA8 brackets
• Cold-rolled steel with zinc finish • Cold-rolled steel with zinc
finish
• May be used with SMBPVA..C for 4 x Ø5.2
mounting to SMBPVA7 or SMBPVA8
41
brackets 6 x Ø4.8
L L
16

Model L

SMBPVA5C 170.0 mm

SMBPVA10C 298.5 mm
21.2 mm 21.2 mm
(0.83 in.) (0.83 in.)

Models with DIP Models with No DIP L


Switch Access Port Switch Access

SMBPVD100A SMBPVD100AB 140 mm (5.5 in)

SMBPVD225A SMBPVD225AB 269 mm (10.6 in)

Retroreflective Tape
Model Reflectivity Factor Maximum Temperature Size

BRT-THG-1-100 0.7 +60 °C (+140 °F) 25 mm (1 in) wide, 2.5 m (100 in) long

BRT-THG-2-100 0.7 +60 °C (+140 °F) 50 mm (2 in) wide, 2.5 m (100 in) long

BRT-THG-3-100 0.7 +60 °C (+140 °F) 75 mm (3 in) wide, 2.5 m (100 in) long

Banner Engineering Corp. Limited Warranty


Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free
of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability
for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR
ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM
ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY,
NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by
Banner Engineering Corp.

Copyright Notice
Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes
will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this
document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. For the most recent version of any documentation, refer to:
www.bannerengineering.com. © Banner Engineering Corp. All rights reserved.