Wet Bench
Wet Bench
$*XLGHOLQHWR:HW%HQFK6DIHW\
                                       
                                        
                                 FROOHFWHGE\
      ,QWHJUDWHG&LUFXLWV6DIHW\*URXS
                             3DW$QGHUVRQ
                             'DYH%DOGZLQ
                              $IVL*HUDPL
                            &KULV+DPLOWRQ
                            .HYLQ/DZOHVV
                             5RGQH\0RVV
                            6FRWW1RUPDQ
                              -DPLH5XELQ
                               -RH6LQJK
                           3HWH6SDPSLQDWR
                                       
0LVVLRQ6WDWHPHQW 
3URPRWHGHYHORSPHQWDQG VKDULQJRIHQYLURQPHQWDOKHDOWKDQGVDIHW\EHVW
SUDFWLFHVDQGSURFHGXUHVIRUHQWLWLHVZLWKLQWHJUDWHGFLUFXLWSURFHVVHV 
      $JLOHQW7HFKQRORJLHV+HZOHWW3DFNDUG
: H W  % H Q F K  * X L G H OL Q H V 
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group     January 2000                    Page 1 of 29
                                            
                                                
                                                
The information and recommendations contained in this publication were compiled from
sources believed to be reliable. However the authors make no guarantees as to the
sufficiency or accuracy of the information.
This guideline is intended to show what one company has done to address the issue of wet
bench safety. As such it may not include information which is important for a particular
user. The primary reference sources used for the guidelines are listed in sections 5 and 6.
The reader should consult these sources, other references applicable to their operations,
and the appropriate individuals in their organization in order to obtain a more complete
understanding of the subject.
Note: This document contains intranet links to internal Hewlett Packard / Agilent
      Technologies documents that will not be accessible to people outside the company.
                                    Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group     January 2000            Page 2 of 29
   1.0 Overview
   2.0 Applicability
   3.0 Definitions
   4.0 Design Criteria
              4.1    General
              4.2    Ventilation
              4.3    Electrical
              4.4    Materials of Construction
              4.5    Fire Prevention and Protection
              4.6    Heating Devices
              4.7    Ergonomic Design
              4.8    Layout Considerations
              4.9    Environmental Considerations
              4.10 Chemical Use
              4.11 Other Issues
                     4.11.1 Decontamination and decommissioning
                     4.11.2 Ozone usage
                     4.11.3 New equipment purchase
                     4.11.4 Installation procedures
                     4.11.5 Seismic Requirements
   5.0 References
   6.0 Guidance Documents
              6.1    Wet Bench diagram and terms
              6.2    Fire Suppression Systems
              6.3    Acceptable Heating Sources
              6.4    Capital Equipment Purchase Process
              6.5    Installation and Start-up Permit
              6.6    Equipment Decontamination/Decommissioning Procedures
              6.7    Wet Bench Code Reference Table
              6.8    Recommendations for existing wet benches
              6.9    Visual Exhaust Check Procedures
   Though this is a guideline, there are some statements that state “shall” or “must”. Those
   terms are used when there is an enforceable code or standard that states specific
   requirements. These are referenced in section 6.7.
   Exceptions to these guidelines may be considered only after review by the EHS and
   Facilities departments. Any exception should be documented with assumptions about
   operating and administrative controls.
                                   Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group        January 2000                     Page 3 of 29
   1.0 OVERVIEW
         The purpose of this guideline is to establish minimum design and performance
         criteria for wet benches used in semiconductor manufacturing and R&D operations
         in order to assure that:
         1) Employees are not exposed to unsafe levels of airborne contaminants.
         2) Employee exposure to ergonomic risk factors is controlled (See H&S Manual –
            Ergonomic Process Standard 535.033).
         3) Environmental impacts associated with wet bench use are minimized.
         4) Through proper design and construction of wet benches, fire and electrical
            hazards are reduced and/or eliminated.
         2.0    APPLICABILITY
         This document contains the minimum guidelines for new wet benches used in
         semiconductor manufacturing. Paragraph 6.8 also recommends the minimum safety
         requirements for existing wet benches. Each site should establish a time-table for
         bringing existing wet benches up to the criteria specified in Paragraph 6.8.
   3.0   DEFINITIONS
          3.1    Capture Velocity: The air velocity at any point in front of the hood opening
                 necessary to overcome opposing air currents and to capture the contaminated
                 air at that point by causing it to flow into the hood usually measured in feet
                 per minute (fpm) or linear feet per minute lfm.
          3.2 Chemical bath: Recessed cavity extending from the deck down into the
              plenum.
          3.3    Combustible Liquid: A liquid having a flash point at or above 100 degrees
                 Fahrenheit (37.8* C).and less than 200 degrees Fahrenheit (93.3 C)
          3.4    Combustible Material: A material that will ignite and act as fuel in a
                 self-sustaining reaction. Polypropylene is an example of a combustible
                 material.
          3.5    Ergonomic design: Designed to meet SEMI S8-95A (Safety Guidelines for
                 Ergonomics/Human Factors Engineering of Semiconductor Manufacturing
                 Equipment) and H&S Manual, Ergonomics Process Standard).
          3.6    Exhausted Vertical Laminar Flow Hood: The combination of a vertical
                 laminar flow hood and a wet bench; it is used when both hazard control and
                 particle control are required.
          3.7    Explosion-proof: Electrical devices meeting National Electric Code
                 requirements for use in potentially hazardous environments (Class I,
                 Division 1).
          3.8    Face: The cross sectional area through which air flow enters.
                                      Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group     January 2000                       Page 4 of 29
          3.9 Face Velocity: The average exhaust flow velocity at the face of an exhaust
                hood or enclosure; measured in linear feet per minute (lfm).
          3.10 Fire-safe material: A material that meets FM4910 protocol. (See FM4910
               definition.)
          3.11 Fire Suppression System: A system designed to automatically discharge
               fire suppression agent upon the detection of low levels of heat, smoke or
               flame.
          3.12 Flammable Liquid: A liquid having a flash point less than 100 degrees
               Fahrenheit (37.8o C).
          3.13 Flash Point: The minimum temperature at which a liquid gives off vapor in
               sufficient concentration to form an ignitable mixture with air.
          3.14 FM 4910 Protocol: Abbreviation for the specification test standard titled,
               Factory Mutual Research Corporation (FMRC), Clean Room Materials
               Flammability Test Protocol (Class 4910). This specification test standard
               establishes testing procedures and maximum levels for Fire Propagation,
               Smoke and Corrosive products of combustion. A “fire-safe” material meets
               the following criteria
                  3.14.1 Fire propagation Index <6.0
                  3.14.2 Smoke Damage Index <0.4
                  3.14.3 Corrosion Damage Index <2.0
                         NOTE: Email from Factory Mutual in May 1999 indicated the
                         Corrosion Index might be dropped because it was not
                         reproducible.
          3.15 Freeboard: The distance from the top of the sink down to the liquid’s
               surface.
          3.16 Freeboard Height: The distance from the top of the solvent or solvent drain
               to the top of the sink (Bay Area Air Quality Management District
               Regulation 8, Rule 30)      .
          3.17 Freeboard Ratio: The freeboard height divided by the smaller of the length
               or width of the sink or reservoir.
          3.18 Hazardous Production Material (HPM): Any gas, liquid, or solid with a
               degree of hazard rating in health, flammability, or reactivity of Class 3 or 4
               as ranked by UFC Standard 79-3 and NFPA Standard 704-M.
          3.19 Heated Bath: A heated bath is a bath containing liquids above room
               temperature. This is achieved by a device used to heat liquids by transferring
               heat from heating elements to the liquid.
          3.20 Hot Plate: An electrical heating device that operates by conducting heat
                                     Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group       January 2000                        Page 5 of 29
                through the wall of a container and into the liquid.
           3.21 Immersion Heater: A device used to heat liquids by immersing an
                electrically heated element directly into the liquid to be heated.
           3.22 In-line IR Heater: A system to heat liquids. Very useful with large baths of
                chemicals. The chemical in the bath is circulated and passes through
                "tubing" that is surrounded by heat-lamp like devices.
           3.23 Laboratory Fume Hood: A device enclosed on five sides except for the
                exhaust face which is designed to draw air inward by means of mechanical
                ventilation, operated with insertion of only the hands and arms of the user,
                and in which hazardous substances are used. This Wet Bench Guideline
                does not apply to laboratory fume hoods.
           3.24 Laminar Flow Bench: An enclosure designed to draw, filter (through a
                HEPA filter), and provide clean air to a work surface. In a vertical laminar
                flow unit, the air is drawn and filtered through the top of the unit to provide
                a down-flow of clean air to the work surface. With a horizontal laminar
                flow unit, the air is drawn and filtered through the rear of the unit across the
                work surface towards the operator. These units ARE NOT designed for
                handling or storage of hazardous materials, but rather, for particle control.
           3.25 LFPM: Linear Feet Per minute. Also abbreviated lfm.
           3.26 LEL: "Lower explosive limit" is the minimum volume percent of a
                substance in air that can be ignited. This is synonymous with the Lower
                Flammable Limit (LFL).
           3.27 LFM: See LFPM.
           3.28 Lip Exhaust: Exhaust slots at the top edge of workstation deck.
           3.29 Make-up Air: Air supplied to a building or a space to replace air that is
                exhausted.
           3.30 Modify vs Move: To modify a workstation means that some essential
                element of the plenum or process operation has been changed, e.g. change
                chemistry, add heat sources. Moving a workstation without changes to the
                physical configuration of the bench or its process flow is not considered a
                modification, e.g. the same bench is used for the same purpose but in a
                different location.
           3.31 OS&Y Valves: "Outside screw and yoke" valve-used for isolating a section
                of an automatic sprinkler system.
           3.32 PEL: Permissible exposure limit as defined by OSHA.
           3.33 Plenum Exhaust: Exhaust provided for a workstation cavity.
           3.34 Safe Level: (referring to airborne contaminant concentrations) ½ of the
                Occupational Exposure Level (such as TLV, PEL). The reference in SEMI
                                      Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group     January 2000                        Page 6 of 29
                S2 to <1% of TLV, PEL is for ventilation design.
          3.35 Significant Modification: Change of a wet bench that increases the health,
               environmental or safety hazards. A change in plumbing system, a change in
               the heating systems or change in sink size is typically a significant
               modification. Moving a wet bench to a different location is not considered a
               significant modification.
          3.36 Slot Exhaust: Slots located above the source, designed to draw
               contaminants away from the operator.
          3.37 Splash Shield: Device used to alter the direction of air flow; secondary
               benefit from the use of a splash shield is that it provides limited protection
               for the operator against splashes.
          3.38 TLV: Threshold Limit Value as defined by the American Conference of
               Governmental Industrial Hygienists (ACGIH)
          3.39 UEL: "Upper explosive limit" is the maximum volume percent of a
               substance in air that can be ignited. This is synonymous with the Upper
               Flammable Limit (UFL).
          3.40 Wet Bench: A workstation that may be free-standing or enclosed on as
               many as three sides and is used for chemical processes. The configuration of
               these units usually includes sink or wells locally exhausted (through the
               plenum below the deck). In a free-standing unit, the work surface may be
               partially or completely perforated for exhaust, as well as for drainage of
               liquids. An enclosed unit will most likely have adjustable slots in the back
               wall and may also have front lip exhaust.
          3.41 Wipe Sample Results: The method used to determine if surface
               contamination is acceptable is taken from the Industrial Hygiene manual.
               The criteria is: “A wipe standard does not exist, however, one simple
               generic approach that is often used follows the steps below:
                  3.41.1 take the airborne standard (e.g., 10 µg/m3 for arsenic, 50 µg/m3 for
                         lead...);
                  3.41.2 use the average amount of air inhaled during an 8-hr shift, 10 m3;
                  3.41.3 assuming total retention of the inhaled material during the shift,
                         calculate an effective dose (e.g., 100 µg for arsenic, 500 µg for
                         lead...);
                  3.41.4 apply it to the typical surface area that is wiped to obtain the
                         sample, 100 cm2, to obtain the "standard" for the material (e.g., 100
                         µg/100 cm2 for arsenic, 500 µg/100 cm2 for lead.).
          3.42 Work Station: A space or independent principal piece of equipment using
               hazardous production materials where a specific function, laboratory
               procedure, or research activity occurs. Approved cabinets shall serve the
                                    Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group        January 2000                     Page 7 of 29
                work station whenever flammable liquids are used. The station may contain
                ventilation equipment, fire protection devices, hazardous materials sensors,
                electrical devices, and other processing and scientific equipment.
   4.0   DESIGN CRITERIA
         4.1   General
         New wet benches should be evaluated against the SEMI S2 and SEMI S8
         guidelines. Any discrepancies noted during these evaluations should be addressed
         by the local EHS department. Existing wet benches should be evaluated against the
         minimal acceptable guidelines listed in paragraph 6.8.
              4.1.1 Sinks containing chemicals should be located in the back row of the
         deck. (Rinse stations are typically in front.)
         4.2   Ventilation
         The term “adequate ventilation” needs to consider several factors. These include
         health hazards, fire hazards and quality of workplace issues. In general, ventilation
         should maintain airborne concentrations in the employees’ breathing zone to below
         ½ of occupational exposure limit. (Typically the OSHA –PEL; ACGIH-TLV or
         other country’s recognized airborne exposure limit.) (Be sure to include
         maintenance operations also.) Adequate ventilation also should assure
         concentrations below 10% of the LEL outside of the ventilation exhaust system.
         This is a “shall” requirement per UFC 5101 unless equipment within 5 feet of the
         wet bench is constructed to meet Class1 Division 2 electrical requirements.
         Adequate ventilation can also be defined as the absence of odors if odors are
         adversely affecting employees and/or adversely affecting production. The absence
         of chemical odors in the workplace should be a goal. SEMI S2 guidelines
         recommend controlling exposures to <1% of PEL, TLV in their design criteria.
         Adequate exhaust may be achieved through exhaust slots around sinks, lateral
         exhaust slots in the rear of the bench, plenum exhaust, lip exhaust or any
         combination.
         Laminar flow in a cleanroom environment often means typical ventilation control
         methods need to be modified to assure adequate exhaust is achieved. Paragraph 6.9
         gives some alternative evaluation methods.
               4.2.1 To help provide adequate capture velocity, wet benches should have
                     the following design criteria:
                      4.2.1.1 A splash shield that:
                              4.2.1.1.1 Hangs down from the vertical laminar flow unit or
                                         extends outward from the wet bench control head
                                         case toward the front of the wet bench.
                                      Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group         January 2000                     Page 8 of 29
                              4.2.1.1.2 Is hinged, flexible, removable or slides to allow
                                          access to the bench
                      4.2.1.2 Side baffles that extend along side of the deck
               4.2.2 Sinks containing chemical baths should have slot/lip exhaust designed
                     with sufficient velocities to capture and control any airborne
                     contaminants. (See ACGIH Industrial Ventilation Design Criteria –
                     Reference in 23rd edition Page 3-10 Figure 3.9 titled “Flow
                     capture/velocity”)
               4.2.3 The face of the wet bench where ventilation face velocities are
                     measured is defined as the plane between the splash shield, the front
                     edge of the sinks containing the chemicals and the side baffles. The
                     average face velocity of the plane should be at least 100 fpm with no
                     point less than 80 fpm and no point should be greater than 120 fpm.
                     Higher flow rates have been shown to cause eddy currents that can
                     actually increase emissions into the employee working area. Higher
                     flow rates also do not support our company’s energy conservation
                     principles. See the H&S Manual, Section 535.082 for evaluation
                     methods. Heated chemicals, carcinogens or compounds with high
                     vapor pressures may need alternative capture methods. Contact your
                     EHS department for determining specific needs for these situations.
               4.2.4 A means to determine adequate ventilation should be in place on all
                     wet benches.
                      4.2.4.1 The preferred device is one that provides a continuous reading.
                              These devices include (but are not limited to):
                              4.2.4.1.1 Magnehelics,
                              4.2.4.1.2 Photohelics
                              4.2.4.1.3 Incline manometers
                              4.2.4.1.4 Sail switches
                      Readings must be recorded and documented at least monthly, and
                      records must be maintained for 5 years per corporate Hewlett-
                      Packard/Agilent Technologies H&S manual requirements. If using
                      these methods, an annual check, compared to a primary standard,
                      needs to be completed. Also, these devices must be maintained per
                      manufacturer recommendations.
                      4.2.4.2 Other methods that meet corporate requirements include
                              quarterly evaluations with velocity measuring devices. (See
                              Hewlett-Packard/Agilent Technologies H&S Manual Section
                              535.082 for minimum requirements.)
               4.2.5 Ventilation performance must be recorded and maintained for 5 years
                                      Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group       January 2000                     Page 9 of 29
                     (Hewlett-Packard/Agilent Technologies H&S Manual -- Process
                     Ventilation 535.082). It is also recommended that the minimum
                     specification and performance to that specification be posted on the
                     wet bench. Parameters may include static pressure measurements,
                     total pressure measurements, actual CFM and actual fpm.
              4.2.6   Methods for Evaluating Ventilation Systems
                      4.2.6.1 Laminar flow requirements in a clean room often complicates
                              exhaust ventilation measurements. Other test methods may be
                              beneficial in evaluating the adequacy of wet bench ventilation.
                              Paragraph 6.9 describes the various systems. Some alternative
                              methods are:
                             4.2.6.1.1 Dry ice visual observations
                             4.2.6.1.2 Water mist visual evaluation
                             4.2.6.1.3 Tracer gas analysis per SEMI F15
                             4.2.6.1.4 Smoke tubes measurements may also be useful in
                                        areas where particulate generation is not a concern.
       4.3    Electrical
              Electrical installations must conform to the applicable standards (National
              Electric Code and/or OSHA NRTL Certifications 29CFR1910.303 and .399)
              Some jurisdictions require a third party electrical certification in addition to
              the equipment meeting SEMI S2. In Europe, the equipment must meet CE
              electrical requirements -- EN60204-1 (TEC204-1).
              4.3.1 Electrical equipment and devices within five feet of a wet bench in
                    which flammable liquids are used shall comply with the requirements
                    of the NEC for Class I Division 2 hazardous locations. (UFC 5101)
                    (EXCEPTION):If adequate air removal within the wet bench can
                    provide a non-flammable atmosphere, (less that 10% LEL measured
                    outside of the wet bench) on a continuous basis, the requirement for
                    Class I, Division 2 locations does not apply.
              4.3.2 An emergency off device [EMO (emergency machine off) or EPO
                    (emergency power off)] should be installed to interrupt all power to the
                    wet bench in the case of an emergency. This device should be placed
                    in accordance with the recommendations of SEMI S8.
              4.3.3 All electric heaters should have ground fault protection (SEMI S3)
              4.3.4 Controls should be located away from the wet surfaces and their
                    placement should not require the operator to reach over any hazardous
                    process. Controls should be located in the head case or in front of the
                    wet bench and should meet SEMI S8 guidelines.
                                     Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group      January 2000                    Page 10 of 29
              4.3.5 Electrical equipment within the head case of the wet bench does not
                     need to meet Class 1 Division 2 requirements if the head case is
                     purged with an inert gas on a continuous basis. {NEC 501-8(a)(3)}
              4.3.6 Electric junction boxes, wires and connections should be mounted in a
                    non-combustible surface.
              4.3.7 A means of lock-out/tag out should be readily accessible.
                                     Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group         January 2000                   Page 11 of 29
                     4.5.2.2 Detection of fire should be accomplished using an UV/IR
                              sensor. When the sensor is activated, the fire extinguisher
                              agent should automatically discharge. In addition, a means to
                              manually activate the fire suppression system should be
                              provided. Discharge of the fire suppression system must
                              activate an audible and visual alarm and disable all electrical
                              inputs to the bench. (UFC97 8003.1.11) However, the exhaust
                              ventilation for the bench should remain functional. (FM7-7
                              2.5.1,3 fire protection for wet benches and other process tools)
                              In addition to electrical sources, bulk chemical delivery
                              systems and other possible conditions that increase the risk of
                              fire propagation should also be shut down.
                      4.5.2.3 Wet bench manufacturers and FM should be consulted to
                              properly design a fire suppression system, especially the
                              placement of fire suppression discharge heads.
                      4.5.2.4 Sprinkler coverage of the horizontal work surface of the wet
                              bench shall not be obstructed. If coverage is blocked (e.g., by
                              vertical laminar flow hoods, sashes, splash shields, etc.),
                              additional sprinkler heads should be installed. In lieu of
                              additional fire sprinklers, a fire suppression system could be
                              installed.
                      4.5.2.5 Exhaust Ducts
                              4.5.2.5.1 Exhaust ducts greater than 10” in diameter and made
                                        with non-fire safe materials must have sprinkler heads
                                        or other approved fire suppression system. The first
                                        head shall be placed between the wet bench and the
                                        duct damper. It must also be within two feet
                                        downstream of the wet bench connection. (UFC
                                        Article 5101.11)
                              4.5.2.5.2 A sprinkler head shall be required if the duct is
                                        greater than 10” in diameter and carries flammable
                                        gases or vapors. (97UFC5101.11) The ICSG
                                        recommends this if >10% LEL concentrations are
                                        routinely anticipated.
                              4.5.2.5.3 Wet benches made of fire safe materials and that do
                                        not contain combustible solvents are the only tools
                                        exempt from duct fire protection.
                              4.5.2.5.4 The sprinkler head, and its connecting piping within
                                        the duct should be coated with a corrosion inhibitor
                                        (such as bee's wax), if necessary, to prevent corrosion.
                                        The head should be accessible through an access port
                                      Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group         January 2000                    Page 12 of 29
                                        for periodic visual inspections. Sprinkler heads shall
                                        be inspected for corrosion on an annual basis.
              4.5.3 For fire prevention and protection of existing wet benches, see 6.6.2.
              4.5.4 Maintenance of fire suppression systems.
                     4.5.4.1 Proper maintenance is important to assure a system will
                             function when needed. Be sure to follow manufacturer’s
                             recommendations regarding routine maintenance.
       4.6    Heating Devices
              4.6.1 Whenever possible, process liquid heating should be done using heat
                    transfer systems using hot water or other noncombustible heat transfer
                    media. Another option would be to remotely heat the chemicals
                    themselves in a properly designed heat exchanger that is external to the
                    tool.
              4.6.2 The heating of any flammable/combustible liquid shall only be done in
                    a noncombustible (metal) bench or tool.
              4.6.3 Preventive maintenance and testing of all safety interlock systems
                    should be conducted as follows:
                     4.6.3.1 At least monthly, low liquid level and high temperature
                             interlocks should be tested to assure proper operation.
                     4.6.3.2 All electrical connections to heating systems and their controls
                             should be visually inspected at least semiannually. (FM also
                             recommends an IR scan of all electrical components annually)
              4.6.4 Heating sources for wet benches should incorporate the following
                     4.6.4.1 A non-combustible outer jacket/enclosure
                     4.6.4.2 A liquid temperature control (e.g., thermocouple controller
                             feedback)
                     4.6.4.3 A heater over-temperature interlock
                     4.6.4.4 A liquid level interlock
                     4.6.4.5 A ground fault protection
                     4.6.4.6 A manual reset
              4.6.5 The interlocks listed above should interrupt power to the heating
                    elements and activate an alarm if the set points are reached. Activated
                    interlocks must be manually reset prior to allowing resumed operation
                    of the bath. Float-type liquid level sensors shall not be used for
                    corrosive applications. Optical or capacitance sensors are
                    recommended. All safety devices must be successfully tested prior to
                    the initial use. All safety devices should be placed on a regular
                                     Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group     January 2000                     Page 13 of 29
                     preventative maintenance schedule to be tested at least annually or as
                     recommended by manufacturer or per local requirements. FM
                     recommends monthly checks of interlocks, 7-7 2.4.2, 6a
              4.6.6 SEMI S3 and NFPA 318 Paragraph 8-4 should be reviewed for
                    guidelines in the design of heated chemical sinks.
       4.7    Ergonomic Considerations
              4.7.1 SEMI S8 criteria should be used in the design of wet benches.
              4.7.2 If manual filling of sinks is required, systems should be added to the
                    wet bench to eliminate the ergonomic and safety hazards associated
                    with this task.
                      4.7.2.1 Maximum reach distance to the point of pour - 325 mm (13")
                              (measured from the front edge of the module to the point where
                              the chemical flow from the bottle enters the module)
                      4.7.2.2 Pour height - minimum 900 mm (35") - maximum 1025 mm
                              (40") (vertical distance from standing surface to average hand
                              position during pour)
                      4.7.2.3 Hand and arm clearances when pouring - minimum width 550
                              mm (22"), minimum height - bottle height plus 130mm (5").
                      4.7.2.4 Visual clearance - If pouring directly into a bath where visual
                              access into the bath is required, the module should be designed
                              such that all operators can view the bath without obstructions
                              and without bending or twisting.
                      4.7.2.5 If pouring into a module where the level of the chemical is not
                              readily seen or requires non-neutral postures to view, an
                              indicator light or other mechanism for visually alerting the
                              operator that the module is full should be present.
                      4.7.2.6 Whenever possible, a funnel or other mechanism should be
                              provided to reduce the precision associated with the pouring
                              task.
                      4.7.2.7 Whenever possible, a funnel or other mechanism should be
                              provided upon which the operator may rest the weight of the
                              bottle during the pour.
                      4.7.2.8 If a sash is required on a wet bench for proper ventilation
                              design, the minimum opening required is 400 mm (15”). (This
                              may need to be adjusted depending on the height of the work
                              surface and the anthropometric measurements of the operator.)
                                     Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group       January 2000                   Page 16 of 29
                     4.10.4.4       If the chemical is flammable, the additional criteria
                                    must be added to the design. (UFC 7903.1.3.5)
                             4.10.4.4.1     Tubing must be metal braid/Teflon, flexible
                                            steel, or welded metal tubing. If chemical
                                            compatibility issues need the tubing to be of
                                            combustible materials, the outer piping needs to
                                            be of fire safe material.
                             4.10.4.4.2     Pressurized containers of Class 1 and Class 2
                                            flammables are allowed in containers of less
                                            than 20 liters (5.3 gallons).
                             4.10.4.4.3 If dispensed using pressure, the gas must be inert.
                             4.10.4.4.4 The canister must have a pressure relief device.
                             4.10.4.4.5 Bonding and grounding procedures must be in place
              4.10.5 All chemical containers shall be marked with approved hazard
                     communication labels. Approved labels include chemical identity and
                     hazard warning appropriate to that chemical.
       4.11   Other Issues
              4.11.1 Decommissioning and decontamination of wet benches should be
                     completed before they are removed or shipped. (For a recommended
                     procedure see paragraph 6.6)
              4.11.2 If ozone is used in the wet bench, the ICSG Semiconductor HPM Gas
                     Safety Standard should be reviewed regarding delivery and monitoring
                     recommendations.
              4.11.3 A New Equipment Purchase process (Hewlett-Packard/Agilent
                     Technologies H&S Manual Section 535.100) shall be followed with
                     each purchase requisition for a wet bench. A form addressing this
                     process must be reviewed and approved by EHS, or their designated
                     representative, before a purchase order is issued. It is strongly
                     recommended that arrangement be made with equipment suppliers to
                     review internal requirements prior to the construction of the tool. See
                     paragraph 6.4 for an example of the new equipment purchase process.
              4.11.4 Prior to equipment being released to engineering and production, an
                     EHS review and check sheet should be completed. See paragraph 6.5
                     as an example.
              4.11.5 Seismic Considerations -- Wet bench construction must be designed to
                     withstand general seismic activity expected in the local seismic rating
                     zone. In seismic zones, wet benches must be seismically braced
                     against movement that would damage chemical lines, drain lines, and
                     exhaust connections. For additional seismic considerations, see SEMI
                                     Agilent Technologies
  :HW%HQFK*XLGHOLQHV
  ICSG: Integrated Circuit Safety Group      January 2000                   Page 17 of 29
                       S2, section 17 Earthquake protection and FM 7-7, 2.7
     5.0 REFERENCES AND TECHNICAL GUIDANCE
             5.1 See Code Reference Table (paragraph 6.7) for specific code references
             5.2 Semiconductor Exhaust Ventilation Guidebook, First Edition, D. Jeff
                  Burton, 1995
             5.3 Water Mist Generator Procedure
                             http://sjntweb1.sj.hp.com/icsg/water-mister.pdf
     6.0 Guidance Documents
             6.1 Wet Bench diagram and terms
Magnehelic
Headcase
                                    Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group      January 2000                   Page 19 of 29
                                     Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group               January 2000                                        Page 20 of 29
                                                                                                                                                  maint .
                                                                     In use
                                                                            No
                         Facilities to dispose
                         of sink as a Non                  Submit WO to facilities for physical removal of sink from area
                         Hazardous waste
                                                           Facilities to disconnect drain services and cut exhaust
                                                           connection
                                                                                                                                                  Facilities
                         Facilities to evaluate
                         for possible exhaust              Facilities to cap all disconnected services
                         re-balancing
                                        (1)       For benches containing corrosives, rinse with water. For benches containing organic solvents,
                                                  rinse with appropriate solvent
                                        (2)       See Definition “Wipe Sample Results”
                                         Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group   January 2000                          Page 21 of 29
                  6.7 Wet Bench Code Reference Table
           Materials of
       4.4 Construction   Meets FM4910 protocol                                                                       X
                                                                 Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group               January 2000                  Page 23 of 29
                                                     Wet Bench Code Reference Table
                                                                    Required                CA Code               Guidelines
                                                                          Company                                                  ICSG
Reference                                                                   H&S                                                Recommended
    #     Criteria        Specification               UBC/UFC      OSHA    Manual    EPA     BAAQMD   SEMI   NFPA 318   FM        practice
                          Interlocks should
                          interrupt power to the
                          heating element                                                                               X
           Ergonomic      ergonomic guidelines
       4.7 Considerations specified in 4.6.2                                                                                       X
                          Front safe zone and
                          rear hazardous zone                                                                                      X
                          Position of aspirators,
                          chemical drains,
                          air/nitrogen guns                                                                                        X
                          Manual filling of sinks                                                                                  X
           Environmental
       4.8 Considerations Freeboard ratios                                                        X
                          Lid on chemical baths                                                   X                                X
                          Design fo preventing
                          chemical spills                X                                             X
                          Exhaust abatement and
                          separation                                                                   X                           X
       4.9 Chemical Use Quantities                       X
                          Incompatible Chemical
                          not allowed in the same
                          bench                                                                                                    X
                          Canister's construction
                          material must be
                          compatible with
                          chemical                       X                             X
                          Requirements for
                          pressurized containers         X
                                                                    Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group            January 2000                  Page 24 of 29
                                                   Wet Bench Code Reference Table
                                                                 Required                CA Code               Guidelines
                                                                       Company                                                  ICSG
Reference                                                                H&S                                                Recommended
    #     Criteria        Specification            UBC/UFC      OSHA    Manual    EPA     BAAQMD   SEMI   NFPA 318   FM        practice
                          Tubing requirements                                                                         X
                          Labeling of containers                 X                  X
           Other          Decommissioning
     4.10. considerations procedures                                                                                            X
                          New Equipment
                          purchase process
                          requirements                                    X
                          EHS review prior
                          release of equipment                                                                                  X
                                                                 Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group             January 2000                        Page 25 of 29
       (1)          Automatically shuts down power (I.e. electrical, pneumatic, chemical dispense) within the wet
                    bench upon detection of flame or over-temperature condition.
       (2)
                    Shuts down power (I.e. electrical, pneumatic, chemical dispense) within the wet bench upon
                    activation of manual button.
      (3a)          Fire suppression system covers deck, plenum and headcase (if not under inert purge) (This is in
                    addition to house sprinkler system)
      (3b)          Unobstructed sprinkler protection required
       (4)          When required, duct material must be of fire safe material and must have sprinkler system in
                    exhaust ducts of >10" diameter within 2 feet downstream of the wet bench/exhaust duct
                    connection.
                                    Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group     January 2000     Page 27 of 29
                                    Agilent Technologies
:HW%HQFK*XLGHOLQHV
ICSG: Integrated Circuit Safety Group     January 2000     Page 28 of 29
Agilent Technologies