0% found this document useful (0 votes)
63 views2 pages

Panel Remoto

The document provides information on the FireFinder XLS System-Status Display Series (SSD Series). The SSD Series is a remote LED/LCD display that shows the status of a FireFinder XLS fire alarm system. It has LEDs to indicate alarm, supervisory, trouble and security events, as well as a four-line LCD screen to display event details. The display can be mounted in its own enclosure or a remote enclosure. Models are available with or without optional local system control capabilities. It connects to the FireFinder system over a Class B or Class A circuit and receives power from the system or an auxiliary power supply.

Uploaded by

Miguel Coronado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views2 pages

Panel Remoto

The document provides information on the FireFinder XLS System-Status Display Series (SSD Series). The SSD Series is a remote LED/LCD display that shows the status of a FireFinder XLS fire alarm system. It has LEDs to indicate alarm, supervisory, trouble and security events, as well as a four-line LCD screen to display event details. The display can be mounted in its own enclosure or a remote enclosure. Models are available with or without optional local system control capabilities. It connects to the FireFinder system over a Class B or Class A circuit and receives power from the system or an auxiliary power supply.

Uploaded by

Miguel Coronado
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

s Catalog Sheet 

Fire Safety & Security Products 

FireFinder XLS
System-Status Display Series
Models SSD, SSD-C and SSD-C-REM

• 4 x 40” backlit LCD screen


• Event and audible status LEDs
• Scroll buttons to view additional events
• Local sounder
• Supports Style 4 or Style 7 wiring
• Built-in transient protection
• Mounts in its own enclosure or REMBOX
• Optional local-system control
• Downloadable firmware
• UL 864 9th Edition Listed and ULC Listed;
FM, CSFM & NYMEA Approved

Product Overview
The System-Status Display (SSD Series) is a remote LED / The LCD display on the SSD Series display has four (4)
LCD display that shows the local status of a FireFinder rows – 40 characters for each row. When the FireFinder
XLS system. A LED will illuminate when Alarm, XLS system is in its normal supervisory state with no
Supervisory, Trouble and Security events occur on events present, the display will annunciate the system
the system. A four-line LCD will give details of the ID information, the date and the time of day.
event in alphanumeric form. The display can be When an event occurs on the system, the LCD display
toggled to display additional events. Optional will show the event type and address, the time of the
remote-system control capabilities are available. event, the custom message for that address, the usage
of the device, and whether the event is acknowledged
Specifications or not. Additionally, the display will show the total
The SSD Series display has separate LEDs for Alarm, number of all types of events present on the system.
Supervisory, Trouble and Security events on the The display has a backlight feature that operates upon
FireFinder XLS system. Each LED will flash when receiving any event information or when any operator
unacknowledged events of that type are present on the buttons are pressed.
system. The LED will change to steady, upon A local sounder is included with the SSD Series display
acknowledgment of the event. Also, there are two (2) that operates when any events are displayed on the
LEDs that indicate the state of audible circuits on the system. The sounder can be optionally disabled
system: one (1) LED to indicate that the circuits are through software programming. Pressing any
active and one (1) LED to indicate the circuits have operator buttons will silence the local sounder
been silenced. when an event is present.

FireFinder XLS 6326


s Industry, Inc.
Building Technologies Division
Specifications – (continued) Details for Ordering
The SSD Series display has two (2) display-control buttons
Model Part
that are used to display the next or the previous event Description
Number Number
information in the sequence, and a local sounder silence
button. Programming for the SSD Series display is done SSD 500-034170 System-Status Display
with the Zeus programming tool.
SSD-C 500-648733 System-Status Display [with control]
Models SSD-C and Model SSD-C-REM have three (3)
System-Status Display [with control for
additional control buttons for acknowledging events, SSD-C-REM 500-634773
remote-lobby enclosure]
silencing audible circuits, and resetting the system.
Model SSD-C has an integral key switch that enables these REMBOX2 500-633772 Small Remote-Lobby Enclosure
control buttons to operate. Model SSD-C-REM is located
REMBOX4 500-633914 Large Remote-Lobby Enclosure
within a locked cabinet, so no additional key switch is
required for enabling the control buttons. BCM 500-033320 Blank Control Module Plate
The SSD Series display is remotely connected to the
H-Net communication bus from any Model NIC-C interface in a
FireFinder XLS system enclosure using Class B, Style 4 or
Class A, Style 7 wiring. 24VDC is required to run the SSD
Electrical Ratings
Series display, and can be provided from a Model PSC-12
Power Supply or PSX-12 Power Supply Extender in the
FireFinder XLS system enclosure. Power from other
UL Listed 24VDC power sources is also acceptable.
The SSD Series display has screw terminals capable of Notes:   An auxiliary‐regulated, power‐limited power supply may be used 
supporting 12 to 22-gage wires. The H-Net to provide power to Model SSD. The power supply must be  UL Listed for 
communication from the FireFinder XLS system can be Fire‐Protection Signaling Application.  Be sure to also include Model SSD‐C 
terminated on the SSD Series display, or may pass  
in the battery calculations.

through for communication with other modules.


Diagnostic LEDs on the SSD Series display indicate
power and communication status.
Models SSD and SSD-C can be mounted in a (2) two-gang
electrical box or a (4) four-inch square electrical box. No
flush-trim kit is required. The unit is approximately Notes: An auxiliary‐regulated, power‐limited power supply may be used to 
10-1/2“(26.7cm.) wide, 6-1/8” (15.2cm.) high, and provide power to Model SSD. The power supply must be  UL Listed for Fire‐
Protection Signaling Application.
1-1/2” (3.8cm.) deep.
The Model SSD-C-REM is mounted in a Model
REMBOX2 or Model REMBOX4 Remote Lobby Enclosure, or
any CAB enclosure inner door. Model SSD-C-REM requires
two (2) module spaces in the remote lobby enclosure,
and its bracket supports the mounting of four (4) inner
door modules (such as Model SCM-8 or Model LCM-8 Notes: An auxiliary‐regulated, power‐limited power supply may be used 
modules) below the display. The inner door module spaces to provide power to Model SSD‐C‐REM. The power supply must be  UL / 
are arranged in two (2) rows of (2) two-module spaces. ULC approved for Fire Protection Signaling Application.  Be sure to also 
include Model SSD‐C‐REM in the battery calculations.
Products are UL 864 9th Edition listed for indoor dry
locations within a temperature range of 120+/-3°F
(49+/-2°C) to 32+/-3°F (0+/-2°C) and at a relative
humidity of 93+/-2% at a temperature of 90+/-3°F
(32+/-2°C).

Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 2 Kenview Boulevard
s Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
August 2010
Building Technologies Division Tel: (973) 593-2600 (SII) L6T 5E4 / Canada
Supersedes sheet dated 5/10
FAX: (908) 547-6877 Printed in U.S.A.  Tel: (905) 799-9937 (Rev. 3)
URL: www.SBT.Siemens.com/FIS   FAX: (905) 799-9858