Hon 60974 A

The XLS-NCD Network Control Display is a modern 10" touch screen interface for the XLS-NET network, compatible with various fire alarm control panels. It offers extensive system control, status displays, and user-friendly features such as a history buffer and customizable settings. The device is UL listed and designed for reliable operation in a range of environmental conditions.

Uploaded by

nguyenanhtuanb
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views3 pages

Hon 60974 A

The XLS-NCD Network Control Display is a modern 10" touch screen interface for the XLS-NET network, compatible with various fire alarm control panels. It offers extensive system control, status displays, and user-friendly features such as a history buffer and customizable settings. The device is UL listed and designed for reliable operation in a range of environmental conditions.

Uploaded by

nguyenanhtuanb
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

XLS-NCD

Network Control Display

The XLS-NCD Network Control Display is the


next generation of network control
annunciators for the XLS-NET network. Its
contemporary design meets today’s building
aesthetics.
The intuitive 1024 x 600 10" touch screen provides detailed color coded system status and
point information. It is compatible with the XLS4000 Fire Alarm Control panel (FACP), ACM-
30 annunciator and XLS-RLD remote display, and other FACPs such as the XLS3000,
XLS140-2, and XLS120. XLS-NCD mounted in XLS-NBB-2
The XLS-NCD provides system control and status/history display capabilities for all, or for
selected network nodes. It can also be used as the primary display for control and status
capabilities on a displayless node via direct connect.

FEATURES AND BENEFITS


HARDWARE FEATURES FUNCTION FEATURES • Individual Enable/Disable or group Enable/
• Full supervision of all inputs and network • Device information, including point address Disable for networked panels.
integrity. and description, can be quickly identified. • Control ON/OFF for networked panel
• High definition 10" 1024 x 600 color • Network-wide: Acknowledge, Silence, Reset. control points.
touchscreen display. • Lamp Test. • Read Status for networked panel points and
• LED status indicators for power and off • Interactive Summary Event Count display zones.
normal and event handling. • History Buffer (10,000 events, 3000
• Requires 24 VDC, and a network connection • Intuitive user guidance program. displayed).
or direct connect. • Fully programmable node-mapping • Up to 50 unique users and 5 different user
• Three USB 2.0 connections, USB C, USB subsystem. levels.
Micro, and USB A. • Up to 2000 programmable logic zones • Read Status from event display.
• Trouble Relay. • Up to 32 custom action buttons • History filters for report displaying.
• Tamper and Trouble inputs. • Environmental adjustment controls to • Timer control for Auto Silence, AC Fail Delay.
• Panel Compatibility: XLS4000, XLS3000, maximize display legibility. • Custom wallpaper
XLS140-2, and XLS120 • Color coded Icon based event notification.
• Can be used as FACP primary display.
• Supports standard and high speed network
systems.
• Event vectoring for quick viewing of event
groups.
• Virtual alphanumeric QWERTY keypad and
numeric keypad displays for data input.
XLS-NCD INDICATORS AND mode fiber, and media conversion models are available. See 74-
4082.
CONTROLS XLS-NBB-2: Ten inch display annunciator backbox, surface, red.
Mounts XLS-NCD and one network control module.
LED INDICATORS
CAB-4 Series Enclosure: Available in five sizes, “AA” through “D”.
Green LED illuminates when 24 VDC power is applied; When on Backbox and door ordered separately; requires BP2-4 battery plate.
battery backup, the green LED will not illuminate. See 85-3002.
Yellow LED illuminates when an off normal condition exists. CAB-5 Series Enclosure: Available in five sizes, “A” through “E”.
Backbox and door ordered separately; requires BP-5 battery dress
VIRTUAL EVENT INDICATORS
plate. See HON-62113.
• FIRE ALARM (red) illuminates when at least one fire alarm event
DP-GDIS2: Graphic Annunciator Dress Plate. Dress plate is used
exists.
when the 10" graphic display is mounted in CAB-4 Series cabinet,
• CO Alarm (blue) illuminates when at least one CO alarm event exists.
except top row.
• SUPERVISORY (yellow) illuminates when at least one supervisory
event exists (i.e., sprinkler valve off normal, low pressure, fire pump DP-GDIS1: Graphic Annunciator Dress Plate. Dress plate is used
running, guard’s tour, etc.). when the 10" graphic display is mounted in the top row of a CAB-4
• TROUBLE (yellow) illuminates when at least one trouble event exists. Series cabinet.
• POINT DISABLED (yellow) illuminates when at least one disable DP-T2A: Graphic Annunciator Dress Plate. Dress plate is used when
exists on the network or in the system. the 10" graphic display is mounted in any row of a CAB-5 Series
• OTHER (varies) illuminates for SECURITY, PRE-ALARM, CO PRE- cabinet.
ALARM, and CRITICAL PROCESS.
• SIGNALS SILENCED (yellow) illuminates if the NCD Silence touch
point has been pressed or if any other node sent a Network Silence
command.

FUNCTION TOUCHPOINTS
• Menu
• Login
• Acknowledge
• Signal Silence
• System Reset
• Drill
Ack (Acknowledge): Tap this touchpoint to acknowledge off all
active events.
Silence (Signal Silence): Tap this touchpoint to turn off all control
modules, notification appliance circuits, and panel output circuits
that have been programmed as Silenceable.
Reset (System Reset): Tap this touchpoint to clear all latched
alarms and other events and clear event indicators.
Drill: Hold this touchpoint down for two seconds, to activate all
silenceable output circuits. Note: when enabled the drill touchpoint
will be displayed in the Alert Bar.

MENU FUNCTION TOUCHPOINTS


Menu function touchpoints are accessed with the menu dialogs.
• About: Tap this touchpoint to view current firmware and hardware
revision numbers.
• Display: Tap this touchpoint to adjust display settings.
• Lamp Test: Tap this touchpoint to test display pixels, LED indicators
and piezo.

PRODUCT LINE INFORMATION


XLS-NCD: Network Control Display. Requires a network
communications module (NCM) for networking. In direct connect
applications, the NCM is not required.
NCM-W, NCM-F: Standard Network Communications Modules.
Wire and multi-mode fiber versions available. See 85-3007.
HS-NCM-W-2/MF/SF/WMF-2/WSF-2/MFSF: High-speed
network communications modules. Wire, single-mode fiber, multi-

Page 2 of 3 — HON-60974:A • 3/3/2023


XLS-NCD TECHNICAL SPECIFICATIONS
ELECTRICAL environment with a nominal room
temperature of 15°C to 27°C (60°F to 80°F). Honeywell® and FlashScan® are
The XLS-NCD may be powered from any UL-
Listed non-resettable 24 VDC source from a registered trademarks of Honeywell
AGENCY LISTINGS AND
compatible fire panel (see panel data International Inc.
APPROVALS
sheets).
The file number(s) below reference the specific This document is not intended to be
Power source: A supervised +24 VDC power listings for the equipment in this document. In
supply, UL-listed for fire protective service. used for installation purposes. We
some cases, certain modules or applications
try to keep our product information
Current consumption: 360 mA. may not be listed by certain approval agencies,
or listing may be in process. Consult up-to-date and accurate. We cannot
PHYSICAL Honeywell for latest listing status. cover all specific applications or
Shipping Weight: 3 lbs (1.36 kg) • UL Listed: S470 anticipate all requirements. All
Temperature and Humidity Ranges: This specifications are subject to change
system meets NFPA requirements for STANDARDS AND CODES without notice.
operation at 0°C to 49°C (32°F to 120°F); These listings and approvals below apply to
and at a relative humidity (non-condensing) the XLS-NCD. In some cases, certain Country of origin: USA
of 85% at 30°C (86°F) per NFPA. However, modules or applications may not be listed
the useful life of the system’s standby by certain approval agencies, or listing may
batteries and the electronic components be in process. Consult Honeywell for latest
may be adversely affected by extreme listing status.
temperature ranges and humidity. • UL 864, 10th edition
Therefore, it is recommended that this • NFPA 72 National Fire Protection
system and all peripherals be installed in an Association

Honeywell Building Solutions


715 Peachtree Street NE
Atlanta, GA 30308
800.345.6770
HON-60974 | A | 03/23
www.honeywell.com ©2023 Honeywell International Inc.