Amps X 1000 Bus3 (Nom. KV 11, Plot Ref. KV 11) : 22EC15 FLA - Other 65 Relay1 Amont - P - 51 OC1

This document contains a one-line diagram showing electrical components on Bus 3 including transformers and protective relays. It summarizes the specifications of two Siemens 7SJ63 relays including their current transformer ratios, inverse time overcurrent settings, and tripping times. It also notes a 0.181 second difference in tripping times between the two relays.

Uploaded by

Youness Ben
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views1 page

Amps X 1000 Bus3 (Nom. KV 11, Plot Ref. KV 11) : 22EC15 FLA - Other 65 Relay1 Amont - P - 51 OC1

This document contains a one-line diagram showing electrical components on Bus 3 including transformers and protective relays. It summarizes the specifications of two Siemens 7SJ63 relays including their current transformer ratios, inverse time overcurrent settings, and tripping times. It also notes a 0.181 second difference in tripping times between the two relays.

Uploaded by

Youness Ben
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 1000 Bus3 (Nom. kV=11, Plot Ref.

kV=11)
,5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
22EC15
FLA - Other 65 47 MVA
500 500
22EC15
Relay1 amont - P - 51
300 OC1 300

22EC15 Siemens
7SJ63
Inrush
CT Ratio 3000:5
100 IEC - Normal Inverse Relay1 amont
100
I>
Pickup = 4,93 (0,5 - 10 Sec - 5A)
Time Dial = 0,21
50 50
3x = 1,32 s, 5x = 0,899 s, 8x = 0,692 s
30 30

I> Relay aval HT

10 10

5 5

Seconds
Seconds

22EC15
3 3
47 MVA (Secondary) 12,5 %Z
Delta-Wye Solid Grd

1 1

,5 ,5

,3 ,3

Relay aval HT - P - 51
OC1
∆ 0,181 s
,1 Siemens ,1
7SJ63
CT Ratio 3000:5
,05 IEC - Normal Inverse ,05
Pickup = 5 (0,5 - 10 Sec - 5A)
,03 Time Dial = 0,13 ,03
3x = 0,819 s, 5x = 0,556 s, 8x = 0,429 s

,01 ,01
,5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 1000 Bus3 (Nom. kV=11, Plot Ref. kV=11) ETAP Star 16.0.0C

Star26

Project: Date: 05-09-2020


Location: SN: 4359168
Contract: Rev: Base
Engineer: Fault: Phase
Filename: C:\ETAP 1600\simulationB\simulationB.OTI