TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
Range of low profile mixed flow fans with ball bearings and brushless DC motors, of high efficiency and low consumption. Manufactured in plastic, removable fan
body, and rated as standard 90/260V- 50/60Hz, IP44. Fan speed 100% adjustable with an external control type REB-ECOWATT. Suitable for any kind of ventilation
application where the noise level of the ventilation system is of particular importance and, due to continuous operation, a significant energy saving is desirable. It is
also suitable for applications that require a Demand Controlled Ventilation System involving the use of other sensors or controls. Brand S&P model TD-500/150
ECOWATT (90-260V 50/60Hz) NE.for an airflow 200 m³/h and static pressure 165 Pa.
Theoretical Working Point Performance Chart
Airflow 200 m³/h 0,06
Static Pressure 164 Pa
Temperature 20 °C 0,05
Altitude 0m
Input Power (kW)
0,04
Density 1,2 kg/m³
Frequency 50 Hz
0,03
Voltage 1-230V-50Hz
Working Point 0,02
Airflow 200 m³/h
0,01
Static Pressure 165 Pa
Dynamic pressure 5,98 Pa
0,00
Total Pressure 171 Pa
300
Input power 0,033 kW
Outlet speed 3,2 m/s 250
Static Pressure (Pa)
Fan speed 2519 rpm 200
Specific Fan Power 0,59 W/l/s
Voltage speed control 9,3 V 150
Construction 100
Discharge diameter 150 mm 50
Fan size 150
0 4V 6V 8V 9,3V 10V
Weight 2,70 kg
0 100 200 300 400 500 600 700
Motor Characteristics Q- Airflow (m³/h)
Number of poles 2
Voltage 1-230V-50Hz
IP Rating IP44
Motor insulation class F Sound Performance
Drawing 63 125 250 500 1k 2k 4k 8k Overall
Inlet (LwA) 28 36 56 59 59 58 52 45 64
Inlet LpA @ 1,5m 14 21 42 44 44 43 38 31 50
Outlet (LwA) 28 32 54 62 60 54 50 43 65
Outlet LpA @ 1,5m 13 18 40 47 45 40 35 29 50
Breakout (LwA) 21 27 48 45 44 44 36 28 52
Breakout LpA @ 1,5m 6 12 33 31 29 30 22 13 37
X A B C D E F G H
211 295 200 173.5 147 111.5 130 80 60
d I
5.5 273
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 1/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
Performance Chart
0,06
0,05
0,04
Input Power (kW)
0,03
0,02
0,01
0,00
300
250
200
Static Pressure (Pa)
150
100
50
0 4V 6V 8V 9,3V 10V
0 100 200 300 400 500 600 700
Q- Airflow (m³/h)
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 2/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
Drawing
X A B C D E F G H d I
211 295 200 173.5 147 111.5 130 80 60 5.5 273
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 3/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
Accessories
5401613800 - CONTROL ECOWATT AC/DC (90-260Vac 50y60HZ)
Control element for demand controlled ventilation systems in public, commercial residential building it automatically modifies the fan speed to adapt it to the
needs defined in the system, measured with sensors. It has three basic modes of operation: 1. Integral proportional control at constant pressure. 2.
Proportional control with maximum demand criteria with multiple sensor input: temperature, CO2 and relative humidity. 3. Minimum-maximum control with
three-sensor input: CO2, temperature, relative humidity or presence detectors (PIR). DC signal output of 1 to 10 V or signal output for AC voltage variation
for single phase motors at 230 V. ECOWATT C CONTROL: for single phase ventilation units. ECOWATT C CONTROL: for DC ventilation units . Power supply:-
AC model: 1~230 V. - DC model: 1~230 V or 24 VDC..
Dimensions
B H T
165 220 110
5416730700 - CPFL-E
Presence detector for ceiling mount, sensitive to infrared radiation emitted by bodies in movement, with a 360º detecting angle. Power supply: 1-230 V.CPFL-
E: Flush mount model.
Dimensions
A B C E F G H
105 87 55 90 72 69 22
5416730600 - CPFL-S
Presence detector for ceiling mount, sensitive to infrared radiation emitted by bodies in movement, with a 360º detecting angle. Power supply: 1-230 V.
CPFL-S: Surface model.
Dimensions
A B C E F G H
105 87 55 90 72 69 22
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 4/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
5418032800 - MAR-500/150
RECTANGULAR DUCT ADAPTERS - TD MIXVENT SERIES
Dimensions
A B C E F G
320 220 37 200 300 9
5418002100 - MBR-500/150
CIRCULAR CONNECTION FLANGE
Dimensions
D D1 NW L
147 158 150 68
5416589900 - MFL-150 G4
MFL filtration boxes are of G4 grade filtration and are designed for direct connection with standard circular ducting. The MFL-G4 filtration boxes are supplied
with a cover easily removable to replace the filter.
Dimensions
A B D E F
206 229 150 154 218
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 5/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
5418047900 - MPC-500/150
Flow detectors designed to correctly measure pressures at the intlet of series TD devices with airflow straightner.
Dimensions
A B C D E F G H
152 164 147 6 64 35 37 121
5401304100 - REB-CVF (0-10V)
5401304000 - REB-ECOWATT (0-10V)
Electronic voltage regulator
Dimensions
B H T
80 80 68
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 6/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
5416731100 - SCHT-AD
SCHT-AD: Ambient CO2 sensor, temperature and relative humidity with display.
Dimensions
A B C
85 26 100
5416730800 - SCO2-A
SCO2-A: Ambient CO2 and temperature sensor.
Dimensions
A B C
85 26 100
5416730900 - SCO2-AD
SCO2-AD: Ambient CO2 and temperature sensor with display.
Dimensions
B H T
11 130 65
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 7/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
5211816600 - SIL-150
Silencer to be installed either at the inlet or outlet of the fan.
Corrections Dimensions
63 125 250 500 1k 2k 4k 8k
A B C D
-1 -3 -7 -17 -23 -29 -20 -9
150 250 600 780
5416731400 - TDP-D
TDP-D: Pressure sensor, with display. Enables you to control the pressure in the fan inlet.
Dimensions
B H T
11 130 65
5416731300 - TDP-S
TDP-S: Pressure sensor. Enables you to control the pressure in the fan inlet.
Dimensions
A B C
75 80 36
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 8/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
Sound Performance
63 125 250 500 1k 2k 4k 8k Overall
Inlet (LwA) 28 36 56 59 59 58 52 45 64
Inlet LpA @ 1,5m 14 21 42 44 44 43 38 31 50
Outlet (LwA) 28 32 54 62 60 54 50 43 65
Outlet LpA @ 1,5m 13 18 40 47 45 40 35 29 50
Breakout (LwA) 21 27 48 45 44 44 36 28 52
Breakout LpA @ 1,5m 6 12 33 31 29 30 22 13 37
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 9/10
21.11.2018. 12:26:30
TD-ECOWATT
5211023600 - TD-500/150 ECOWATT (90-260V 50/60HZ) NE - IN LINE DUCT FANS
ErP Data
Ecodesign
Commission regulation (EU) N°1253/2014 of July 2014
Information requirements (Annex V)
TD-500/150 ECOWATT
Product description
(90-260V 50/60Hz) NE
Manufacturer's Info S&P ES-08150 CIF-B64911928
Identifier 5211023600
Typology NRVU unidirectional
Drive VSD
Type of HRC None
Thermal efficiency (%) NA
Qnom (m3/s) 0,1
Pelec (kW) 0,05
SFPint (W/m3/s) NA
Face velocity (m/s) 3,25
Δps,ext (Pa) 170,4
Δps,int (Pa) NA
Δps,add (Pa) NA
Static efficiency fans (%) 43,3
External leakage rate (%) 3
Internal leakage rate (%) NA
Filter performance NA
Filter warning NA
LWA dB(A) 55
https://www.solerpalau.com/
S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 10/10
21.11.2018. 12:26:30