Purpose: Profibus Link Between Siemens S7 400-Plcs Etic'S MTI 133-100 MODEMS

This document provides instructions for establishing a PROFIBUS transmission between two Siemens S7 400 PLCs using ETIC MTI 133-100 modems over a 2-wire dedicated line. It describes connecting the modems to the PLCs via CP443-5 couplers and CAB590 cables. It also explains configuring the modems' dip switches to set the data rate and configuring the PLCs in the programming software to enter the PROFIBUS transmission parameters.

Uploaded by

fitasmounir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
81 views2 pages

Purpose: Profibus Link Between Siemens S7 400-Plcs Etic'S MTI 133-100 MODEMS

This document provides instructions for establishing a PROFIBUS transmission between two Siemens S7 400 PLCs using ETIC MTI 133-100 modems over a 2-wire dedicated line. It describes connecting the modems to the PLCs via CP443-5 couplers and CAB590 cables. It also explains configuring the modems' dip switches to set the data rate and configuring the PLCs in the programming software to enter the PROFIBUS transmission parameters.

Uploaded by

fitasmounir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PROFIBUS LINK BETWEEN SIEMENS

S7 400-type PLCs WITH ETIC’S


MTI 133-100 MODEMS
Application note N° FA124-02-E

1. PURPOSE
To establish a profibus transmission (FDL) between PLCs on a 2-wire dedicated line .

2. SYNOPSIS
SIEMENS PLC SIEMENS PLC
412-2-2XG00-0AB0

443-5DX02-0XE0

414-1XG02-0AB0

443-5DX01-0XE0
CP443-5 Ext

CP443-5 Ext
CPU 412-2

CPU 414-1
CAB590

3. CABLES CAB590

CAB590
CP 443-5 MDM192
9-pin male SubD Cable end
3 9B
8 10 A

4. INSTRUCTIONS
4.1. Configuring the modems (MDM 192)

1 Configure the modems by positioning the DIP Switches.


Set the data rate either at 19200 b/s or at 9600 b/s.

DIP Switches positioning


OFF ON OFF ON

19 200 b/s 9 600 b/s


* refer to user guide at configuration section

ETIC TELECOMMUNICATIONS – 13, Chemin du Vieux Chêne – 38240 MEYLAN – France


Tél. : 33 (0) 4 76 04 20 05 – Fax. : 33 (0) 4 76 04 20 01 – E-mail : hotline@etictelecom.com
Web : etictelecom.com
Page 2
Application note FA124-02-E

4.2. Connecting the modems to the PLCs


1 Connect the modems to the CP443-5 couplers with the CAB590 cable.

4. CONFIGURING THE PLCS


1 Open the programming software (SIMATIC Manager) and enter the transmission parameters of the
profibus network on each PLC.

3 Tslot_init = 200
1 Choose 19.2 kbits/ s
or 9.6 kbits/s

2 Profile : Personalized