LV Copper N2xsy Iec

This document provides specifications for 3 types of copper conductor, XLPE insulated power cables with PVC sheathing and copper tape screening. It includes information on cable construction details, electrical properties, current carrying capacity and short circuit ratings for various cable cross sectional areas. Key details listed are cable dimensions, weights, insulation thickness, conductor configurations and drum packaging dimensions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
88 views4 pages

LV Copper N2xsy Iec

This document provides specifications for 3 types of copper conductor, XLPE insulated power cables with PVC sheathing and copper tape screening. It includes information on cable construction details, electrical properties, current carrying capacity and short circuit ratings for various cable cross sectional areas. Key details listed are cable dimensions, weights, insulation thickness, conductor configurations and drum packaging dimensions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

N2XSY 1 x (1.5 - 630) mm² 0.

6/1 kV
(Copper Conductor, XLPE Insulated, PVC Sheathed With
Copper Tape Screened Power Cables)

Standard Specification : IEC 502

Construction Data
Conductor Thickness of Approximate Standard Delivery
Nom. Number Shape Insulation Outer Overall Cable Length Drum
Cross of Wires Sheath Diameter Weight Dimension
Sect.
- - - nom. min. - - - -
mm² - - mm mm mm kg/km m mmxmm
50 19 cm 1.0 1.24 16.0 641 1000 ± 2% 1050 x 724
70 19 cm 1.1 1.24 18.0 864 1000 ± 2% 1130 x 724
95 19 cm 1.1 1.24 19.5 1126 1000 ± 2% 1230 x 754
120 37 cm 1.2 1.24 21.5 1367 1000 ± 2% 1460 x 1000
150 37 cm 1.4 1.24 23.5 1654 1000 ± 2% 1460 x 1000
185 37 cm 1.6 1.24 25.5 2025 1000 ± 2% 1460 x 1000
240 61 cm 1.7 1.24 28.0 2572 1000 ± 2% 1460 x 1000
300 61 cm 1.8 1.32 30.5 3173 1000 ± 2% 1460 x 1000

Electrical Data
Conductor Insulation Current-Carrying Capacity Short-circuit Current
Nom. DC AC Inductance Capacitance in Ground in Air Rating of
Cross Resistance Resistance Resistance of of at 30oC at 30oC Screen Conductor
Sect. at 20oC at 90oC at 20oC Conductor Conductor 1sec 0.1sec 0.5sec 1sec
- max. max. min. calculated calculated max. max. max. max. max. max.
mm² ohm/km ohm/km G.ohm.km mH/km uF/km A A kA kA kA kA
50 0.387 0.494 3.0 0.322 0.611 194 207 0.23 22.61 10.11 7.15
70 0.268 0.342 3.0 0.307 0.664 237 263 0.23 31.65 14.16 10.01
95 0.193 0.247 2.5 0.296 0.756 284 325 0.23 42.96 19.21 13.59
120 0.153 0.196 2.5 0.288 0.781 323 380 0.34 54.26 24.27 17.16
150 0.124 0.159 2.5 0.284 0.750 364 437 0.34 67.83 30.33 21.45
185 0.0991 0.128 2.5 0.279 0.731 412 507 0.34 83.66 37.41 26.46
240 0.0754 0.0981 2.5 0.272 0.782 479 604 0.34 108.53 48.54 34.32
300 0.0601 0.0791 2.0 0.268 0.820 540 697 0.34 135.66 60.67 42.90

N2XSY 2 x (1.5 - 300) mm² 0.6/1 kV


(Copper Conductor, XLPE Insulated, PVC Sheathed With
Copper Tape Screened Power Cables)

Standard Specification : IEC 502

Construction Data
Conductor Thickness of Approximate Standard Delivery
Nom. Number Shape Insulation Outer Overall Cable Length Drum
Cross of Wires Sheath Diameter Weight Dimension
Sect.
- - - nom. min. - - - -
mm² - - mm mm mm kg/km m mmxmm
4 1 re 0.7 1.24 13.5 273 1000 ± 2% 960 x 694
4 7 rm 0.7 1.24 14.0 296 1000 ± 2% 950 x 724
6 1 re 0.7 1.24 14.5 338 1000 ± 2% 1050 x 724
6 7 rm 0.7 1.24 15.0 362 1000 ± 2% 1050 x 724
10 1 re 0.7 1.24 16.0 455 1000 ± 2% 1050 x 724
10 7 rm 0.7 1.24 17.0 496 1000 ± 2% 1160 x 714
16 7 rm 0.7 1.24 19.0 665 1000 ± 2% 1230 x 754
25 7 cm 0.9 1.24 22.0 943 1000 ± 2% 1460 x 1000
35 7 cm 0.9 1.24 24.5 1208 1000 ± 2% 1560 x 994
50 19 cm 1.0 1.24 27.5 1523 1000 ± 2% 1430 x 1096
Electrical Data
Conductor Insulation Current-Carrying Capacity Short-circuit Current
Nom. DC AC Inductance Capacitance in in Rating of
Cross Resistance Resistance Resistance of of Ground Air Screen Conductor
Sect. at 20oC at 90oC at 20oC Conductor Conductor at 30oC at 30oC 1sec 0.1sec 0.5sec 1sec
- max. max. min. calculated calculated max. max. max. max. max. max.
mm² ohm/km ohm/km G.ohm.km mH/km uF/km A A kA kA kA kA
4 4.61 5.88 6.5 0.285 0.308 58 48 0.17 1.81 0.81 0.57
6 3.08 3.93 5.5 0.271 0.360 72 61 0.17 2.71 1.21 0.86
10 1.83 2.33 4.5 0.255 0.449 97 83 0.23 4.52 2.02 1.43
16 1.15 1.47 3.5 0.238 0.544 128 113 0.23 7.24 3.24 2.29
25 0.727 0.927 3.5 0.240 0.516 167 150 0.34 11.31 5.06 3.58
35 0.524 0.668 3.5 0.233 0.598 201 186 0.34 15.83 7.08 5.01
50 0.387 0.494 3.0 0.232 0.611 239 226 0.34 22.61 10.11 7.15

N2XSY 3 x (1.5 - 300) mm² 0.6/1 kV


(Copper Conductor, XLPE Insulated, PVC Sheathed With
Copper Tape Screened Power Cables)

Standard Specification : IEC 502

Construction Data
Conductor Thickness of Approximate Standard Delivery
Nom. Number Shape Insulation Outer Overall Cable Length Drum
Cross of Wires Sheath Diameter Weight Dimension
Sect.
- - - nom. min. - - - -
mm² - - mm mm mm kg/km m mmxmm
2.5 1 re 0.7 1.24 13.0 249 1000 ± 2% 960 x 694
2.5 7 rm 0.7 1.24 13.5 269 1000 ± 2% 960 x 694
4 1 re 0.7 1.24 14.0 316 1000 ± 2% 950 x 724
4 7 rm 0.7 1.24 14.5 341 1000 ± 2% 1050 x 724
6 1 re 0.7 1.24 15.0 399 1000 ± 2% 1050 x 724
6 7 rm 0.7 1.24 16.0 425 1000 ± 2% 1050 x 724
10 1 re 0.7 1.24 17.0 551 1000 ± 2% 1160 x 714
10 7 rm 0.7 1.24 18.0 596 1000 ± 2% 1130 x 724
16 7 rm 0.7 1.24 20.0 814 1000 ± 2% 1310 x 854
25 7 cm 0.9 1.24 23.5 1172 1000 ± 2% 1460 x 854
35 7 cm 0.9 1.24 26.0 1521 1000 ± 2% 1560 x 994
50 19 sm 1.0 1.24 28.0 1739 1000 ± 2% 1430 x 1096

Electrical Data
Conductor Insulation Current-Carrying Capacity Short-circuit Current
Nom. DC AC Inductance Capacitance in in Rating of
Cross Resistance Resistance Resistance of of Ground Air Screen Conductor
Sect. at 20oC at 90oC at 20oC Conductor Conductor at 30oC at 30oC 1sec 0.1sec 0.5sec 1sec
- max. max. min. calculated calculated max. max. max. max. max. max.
mm² ohm/km ohm/km G.ohm.km mH/km uF/km A A kA kA kA kA
2.5 7.41 9.45 8.0 0.305 0.255 38 32 0.17 1.13 0.51 0.36
4 4.61 5.88 6.5 0.285 0.308 49 41 0.17 1.81 0.81 0.57
6 3.08 3.93 5.5 0.271 0.360 60 52 0.17 2.71 1.21 0.86
10 1.83 2.33 4.5 0.255 0.449 97 71 0.23 4.52 2.02 1.43
16 1.15 1.47 3.5 0.238 0.544 108 96 0.23 7.24 3.24 2.29
25 0.727 0.927 3.5 0.240 0.516 141 130 0.34 11.31 5.06 3.58
35 0.524 0.668 3.5 0.233 0.598 170 159 0.34 15.83 7.08 5.01
50 0.387 0.494 3.0 0.236 0.564 201 193 0.34 22.61 10.11 7.15
N2XSY 4 x (1.5 - 300) mm² 0.6/1 kV
(Copper Conductor, XLPE Insulated, PVC Sheathed With
Copper Tape Screened Power Cables)

Standard Specification : IEC 502

Construction Data
Conductor Thickness of Approximate Standard Delivery
Nom. Number Shape Insulation Outer Overall Cable Length Drum
Cross of Wires Sheath Diameter Weight Dimension
Sect.
- - - nom. min. - - - -
mm² - - mm mm mm kg/km m mmxmm
1.5 1 re 0.7 1.24 13.0 231 1000 ± 2% 960 x 694
1.5 7 rm 0.7 1.24 13.5 247 1000 ± 2% 960 x 694
2.5 1 re 0.7 1.24 14.0 288 1000 ± 2% 950 x 724
2.5 7 rm 0.7 1.24 14.5 311 1000 ± 2% 1050 x 724
4 1 re 0.7 1.24 15.0 372 1000 ± 2% 1050 x 724
4 7 rm 0.7 1.24 16.0 401 1000 ± 2% 1050 x 724
6 1 re 0.7 1.24 16.0 476 1000 ± 2% 1050 x 724
6 7 rm 0.7 1.24 17.0 506 1000 ± 2% 1160 x 714
10 1 re 0.7 1.24 18.0 668 1000 ± 2% 1130 x 724
10 7 rm 0.7 1.24 19.5 720 1000 ± 2% 1230 x 754
16 7 rm 0.7 1.24 22.0 1002 1000 ± 2% 1460 x 1000
25 7 cm 0.9 1.24 25.5 1458 1000 ± 2% 1560 x 994
35 7 cm 0.9 1.24 28.5 1905 1000 ± 2% 1630 x 1096
50 19 sm 1.0 1.32 30.5 2232 1000 ± 2% 1630 x 1096

Electrical Data
Conductor Insulation Current-Carrying Capacity Short-circuit Current
Nom. DC AC Inductance Capacitance in in Rating of
Cross Resistance Resistance Resistance of of Ground Air Screen Conductor
o o o o
Sect. at 20 C at 90 C at 20 C Conductor Conductor at 30 C at 30oC 1sec 0.1sec 0.5sec 1sec
- max. max. min. calculated calculated max. max. max. max. max. max.
mm² ohm/km ohm/km G.ohm.km mH/km uF/km A A kA kA kA kA
1.5 12.1 15.4 10.0 0.329 0.211 29 23 0.17 0.68 0.30 0.21
2.5 7.41 9.45 8.0 0.305 0.255 38 32 0.17 1.13 0.51 0.36
4 4.61 5.88 6.5 0.285 0.308 49 41 0.17 1.81 0.81 0.57
6 3.08 3.93 5.5 0.271 0.360 60 52 0.17 2.71 1.21 0.86
10 1.83 2.33 4.5 0.255 0.449 97 71 0.23 4.52 2.02 1.43
16 1.15 1.47 3.5 0.238 0.544 108 96 0.23 7.24 3.24 2.29
25 0.727 0.927 3.5 0.240 0.516 141 130 0.34 11.31 5.06 3.58
35 0.524 0.668 3.5 0.233 0.598 170 159 0.34 15.83 7.08 5.01
50 0.387 0.494 3.0 0.235 0.571 201 193 0.34 22.61 10.11 7.15

N2XSY 5 x (1.5 - 50) mm² 0.6/1 kV


(Copper Conductor, XLPE Insulated, PVC Sheathed With
Copper Tape Screened Power Cables)

Standard Specification : IEC 502

Construction Data
Conductor Thickness of Approximate Standard Delivery
Nom. Number Shape Insulation Outer Overall Cable Length Drum
Cross of Wires Sheath Diameter Weight Dimension
Sect.
- - - nom. min. - - - -
mm² - - mm mm mm kg/km m mmxmm
1.5 1 re 0.7 1.24 13.5 266 1000 ± 2% 950 x 724
1.5 7 rm 0.7 1.24 14.0 286 1000 ± 2% 950 x 724
2.5 1 re 0.7 1.24 14.5 336 1000 ± 2% 1050 x 724
2.5 7 rm 0.7 1.24 15.5 364 1000 ± 2% 1050 x 724
4 1 re 0.7 1.24 16.0 439 1000 ± 2% 1050 x 724
4 7 rm 0.7 1.24 17.0 474 1000 ± 2% 1160 x 714
6 1 re 0.7 1.24 17.5 566 1000 ± 2% 1160 x 714
6 7 rm 0.7 1.24 18.5 603 1000 ± 2% 1230 x 754
10 1 re 0.7 1.24 19.5 804 1000 ± 2% 1230 x 754
10 7 rm 0.7 1.24 21.0 866 1000 ± 2% 1310 x 854
16 7 rm 0.7 1.24 24.0 1206 1000 ± 2% 1560 x 994
25 7 cm 0.9 1.24 28.5 1674 1000 ± 2% 1430 x 1096
35 7 cm 0.9 1.24 31.5 2189 1000 ± 2% 1630 x 1096
50 19 cm 1.0 1.40 35.5 2992 1000 ± 2% 1950 x 1334
Electrical Data
Conductor Insulation Current-Carrying Capacity Short-circuit Current
Nom. DC AC Inductance Capacitance in in Rating of
Cross Resistance Resistance Resistance of of Ground Air Screen Conductor
Sect. at 20oC at 90oC at 20oC Conductor Conductor at 30oC at 30oC 1sec 0.1sec 0.5sec 1sec
- max. max. min. calculated calculated max. max. max. max. max. max.
mm² ohm/km ohm/km G.ohm.km mH/km uF/km A A kA kA kA kA
1.5 12.1 15.4 10.0 0.329 0.211 24 21 0.17 0.68 0.30 0.21
2.5 7.41 9.45 8.0 0.305 0.255 32 28 0.17 1.13 0.51 0.36
4 4.61 5.88 6.5 0.285 0.308 41 37 0.23 1.81 0.81 0.57
6 3.08 3.93 5.5 0.271 0.360 52 47 0.23 2.71 1.21 0.86
10 1.83 2.33 4.5 0.255 0.449 69 65 0.23 4.52 2.02 1.43
16 1.15 1.47 3.5 0.238 0.544 90 87 0.34 7.24 3.24 2.29
25 0.727 0.927 3.5 0.240 0.516 116 115 0.34 11.31 5.06 3.58
35 0.524 0.668 3.5 0.233 0.598 139 142 0.34 15.83 7.08 5.01
50 0.387 0.494 3.0 0.232 0.611 165 172 0.45 22.61 10.11 7.15