www.kmi.co.
id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XSY 1 x (1.5-800) mm 0.6/1 kV
N2XSY 1 x (1.5-800) mm 0.6/1 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For  power  plants  and  switchgear  as  well  as 
for  installation  of  sub-station;  for  installation 
indoors in confinned spaces and cable channels 
because  of  small  bending  radius.  As  burried 
cable,  because  of  its  light  weight  prefered  in 
where installation is difficult.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted 
circular stranded (cm) conductor shape
Standard Packing
1.5 - 300 sqmm supplied in wooden drum @ 1000 m
400 - 800 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum  2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm   kg/km
Construction Data
Conductor Inductance   Current - Carrying Capacity at 30 C * Short
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
Trefoil
formation
(mH/km)
Flat
formation
(mH/km)
in air
Max. 
(A)
in ground
Max.
(A)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.526  0.572  28  32  29  33  0.21 
  2.5  7.41  9.449  0.487  0.533  37  42  38  43  0.36 
  4  4.61  5.878  0.451  0.498  49  54  50  56  0.57 
  6  3.08  3.927  0.425  0.471  62  68  63  70  0.86 
  10  1.83  2.333  0.390  0.437  84  90  86  93  1.43 
  16  1.15  1.466  0.364  0.410  110  116  113  120  2.29 
  25  0.727  0.927  0.344  0.390  148  150  152  155  3.58 
  35  0.524  0.668  0.328  0.374  181  180  186  186  5.01 
  50  0.387  0.494  0.313  0.360  221  214  227  221  7.15 
  70  0.268  0.342  0.301  0.347  279  263  287  270  10.01 
  95  0.193  0.247  0.289  0.335  343  315  353  324  13.59 
  120  0.153  0.196  0.282  0.328  399  358  410  368  17.16 
  150  0.124  0.160  0.278  0.325  457  402  470  412  21.45 
  185  0.0991  0.128  0.274  0.320  530  455  546  466  26.46 
  240  0.0754  0.099  0.266  0.312  632  527  650  539  34.32 
  300  0.0601  0.080  0.261  0.307  728  594  749  606  42.90 
  400  0.0470  0.064  0.261  0.308  846  670  868  684  57.20 
  500  0.0366  0.052  0.257  0.304  979  755  1003  768  71.50 
  630  0.0283  0.043  0.253  0.299  1128  845  1153  858  90.09 
  800  0.0221  0.036  0.251  0.298  1274  931  1299  942  114.40
Electrical Data
  1.5  8.6  103 
  2.5  9.1  120 
  4  9.6  143 
  6  10.2  170 
  10  11.1  223 
  16  12.1  291 
  25  14.0  415 
  35  15.1  519 
  50  16.8  677 
  70  18.7  898 
  95  21.0  1,152 
  120  22.5  1,403 
  150  24.5  1,683 
  185  27.0  2,088 
  240  30.0  2,682 
  300  32.5  3,234 
  400  36.5  4,143 
  500  40.5  5,263 
  630  45.5  6,794 
  800  50.5  8,532
Non-hygroscopic Tape
PVC Inner Sheath
PVC Sheath
Copper Tape Screen
Copper Conductor
XLPE Insulation
1
4
6
3
3
-
0
1
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Electrical Data
Conductor Inductance   Current - Carrying
Capacity
at 30C *
Short 
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)   (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  29  34  0.21   
  2.5  7.41  9.449  0.293  38  45  0.36   
  4  4.61  5.878  0.275  51  59  0.57   
  6  3.08  3.927  0.263  64  74  0.86   
  10  1.83  2.334  0.248  88  99  1.43   
  16  1.15  1.467  0.238  117  129  2.29   
  25  0.727  0.927  0.240  156  167  3.58   
  35  0.524  0.669  0.233  192  201  5.01   
  50  0.387  0.494  0.232  232  238  7.15   
  70  0.268  0.342  0.229  294  294  10.01   
  95  0.193  0.247  0.224  359  350  13.59   
  120  0.153  0.196  0.223  417  399  17.16   
  150  0.124  0.160  0.224  477  448  21.45   
  185  0.0991  0.128  0.225  547  504  26.46   
  240  0.0754  0.099  0.223  647  583  34.32   
  300  0.0601  0.080  0.221  739  655  42.90
N2XSY 2 x (1.5-300) mm 0.6/1 kV
N2XSY 2 x (1.5-300) mm 0.6/1 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For  power  plants  and  switchgear  as  well  as 
for  installation  of  sub-station;  for  installation 
indoors in confinned spaces and cable channels 
because  of  small  bending  radius.  As  burried 
cable,  because  of  its  light  weight  prefered  in 
where installation is difficult.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
 
Standard Packing
1.5 - 150 sqmm supplied in wooden drum @ 1000 m
185 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum  2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm  mm   kg/km
Construction Data
  1.5  11.8  188 
  2.5  12.8  229 
  4  13.9  285 
  6  15.0  350 
  10  16.9  479 
  16  19.0  643 
  25  22.5  913 
  35  24.5  1,171 
  50  27.5  1,438 
  70  31.5  1,961 
  95  35.5  2,621 
  120  39.0  3,218 
  150  43.0  3,934 
  185  48.0  4,887 
  240  53.5  6,261 
  300  59.0  7,740
XLPE Insulation
Copper Conductor
Copper Tape Screen
PVC Sheath
PVC Inner Sheath
Non-hygroscopic Tape
1
4
6
3
3
-
0
2
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XSY 3 x (1.5-300) mm 0.6/1 kV
N2XSY 3 x (1.5-300) mm 0.6/1 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For  power  plants  and  switchgear  as  well  as 
for  installation  of  sub-station;  for  installation 
indoors in confinned spaces and cable channels 
because  of  small  bending  radius.  As  burried 
cable,  because  of  its  light  weight  prefered  in 
where installation is difficult.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m
150 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum  2%
Electrical Data
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm   kg/km
Construction Data
  1.5  12.3  210 
  2.5  13.3  261 
  4  14.5  332 
  6  15.7  414 
  10  17.8  581 
  16  20.5  795 
  25  23.5  1,146 
  35  26.0  1,488 
  50  28.0  1,726 
  70  32.0  2,411 
  95  35.5  3,200 
  120  39.0  3,948 
  150  43.5  4,866 
  185  48.5  6,010 
  240  54.0  7,791 
  300  59.0  9,587
Conductor Inductance   Current - Carrying
Capacity
at 30C *
Short 
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)   (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  24  29  0.21   
  2.5  7.41  9.449  0.293  32  38  0.36   
  4  4.61  5.878  0.275  43  50  0.57   
  6  3.08  3.927  0.263  54  62  0.86   
  10  1.83  2.334  0.248  75  84  1.43   
  16  1.15  1.467  0.238  100  109  2.29   
  25  0.727  0.927  0.240  132  140  3.58   
  35  0.524  0.669  0.233  163  169  5.01   
  50  0.387  0.494  0.232  201  205  7.15   
  70  0.268  0.342  0.229  254  250  10.01   
  95  0.193  0.247  0.224  311  300  13.59   
  120  0.153  0.196  0.223  361  340  17.16   
  150  0.124  0.160  0.224  414  381  21.45   
  185  0.0991  0.128  0.225  478  432  26.46   
  240  0.0754  0.099  0.223  565  499  34.32   
  300  0.0601  0.080  0.221  648  561  42.90
Non-hygroscopic Tape
PVC Inner Sheath
PVC Sheath
Copper Tape Screen
Copper Conductor
XLPE Insulation
1
4
6
3
3
-
0
3
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Electrical Data
Conductor Inductance   Current - Carrying
Capacity
at 30C *
Short 
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)   (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  27  32  0.21   
  2.5  7.41  9.449  0.293  36  42  0.36   
  4  4.61  5.878  0.275  47  54  0.57   
  6  3.08  3.927  0.263  60  68  0.86   
  10  1.83  2.334  0.248  82  91  1.43   
  16  1.15  1.467  0.238  109  117  2.29   
  25  0.727  0.927  0.240  147  152  3.58   
  35  0.524  0.669  0.233  181  182  5.01   
  50  0.387  0.494  0.232  213  210  7.15   
  70  0.268  0.342  0.229  268  256  10.01   
  95  0.193  0.247  0.224  329  307  13.59   
  120  0.153  0.196  0.223  382  348  17.16   
  150  0.124  0.160  0.224  444  394  21.45   
  185  0.0991  0.128  0.225  508  443  26.46   
  240  0.0754  0.099  0.223  600  512  34.32   
  300  0.0601  0.080  0.221  688  576  42.90
N2XSY 4 x (1.5-300) mm 0.6/1 kV
N2XSY 4 x (1.5-300) mm 0.6/1 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For  power  plants  and  switchgear  as  well  as 
for  installation  of  sub-station;  for  installation 
indoors in confinned spaces and cable channels 
because  of  small  bending  radius.  As  burried 
cable,  because  of  its  light  weight  prefered  in 
where installation is difficult.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
 
Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m
95 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum  2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm   kg/km
Construction Data
  1.5  13.1  240 
  2.5  14.2  303 
  4  15.6  391 
  6  17.0  494 
  10  19.3  710 
  16  22.0  983 
  25  25.5  1,432 
  35  28.5  1,872 
  50  32.0  2,250 
  70  36.5  3,138 
  95  40.5  4,203 
  120  45.5  5,217 
  150  51.5  6,437 
  185  55.5  7,907 
  240  62.0  10,253 
  300  68.0  12,622
XLPE Insulation
Copper Conductor
Copper Tape Screen
PVC Sheath
PVC Inner Sheath
Non-hygroscopic Tape
1
4
6
3
3
-
0
4
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
N2XSY 5 x (1.5-50) mm 0.6/1 kV
PVC Filler
Non-hygroscopic Tape
PVC Inner Sheath
PVC Sheath
Copper Tape Screen
Copper Conductor
XLPE Insulation
N2XSY 5 x (1.5-50) mm 0.6/1 kV
Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
For  power  plants  and  switchgear  as  well  as 
for  installation  of  sub-station;  for  installation 
indoors in confinned spaces and cable channels 
because  of  small  bending  radius.  As  burried 
cable,  because  of  its  light  weight  prefered  in 
where installation is difficult.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum  2%
Electrical Data
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm   kg/km
Construction Data
  1.5  14.0  279 
  2.5  15.3  355 
  4  16.8  464 
  6  18.3  590 
  10  21.0  851 
  16  24.0  1,187 
  25  28.0  1,740 
  35  31.0  2,284 
  50  35.5  2,949
Conductor Inductance   Current - Carrying
Capacity
at 30C *
Short 
circuit current
of conductor
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)   (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  28  33  0.21   
  2.5  7.41  9.449  0.293  37  43  0.36   
  4  4.61  5.878  0.275  49  55  0.57   
  6  3.08  3.927  0.263  62  69  0.86   
  10  1.83  2.334  0.248  85  92  1.43   
  16  1.15  1.467  0.238  113  119  2.29   
  25  0.727  0.927  0.240  153  155  3.58   
  35  0.524  0.669  0.233  189  186  5.01   
  50  0.387  0.494  0.232  229  218  7.15
1
4
6
3
3
-
0
5
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9