NAYY
NAYY 11xx(10-800)
          (10-800) mm²
                  mm²    0.6/1
                      0.6/1 kV kV
Al / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
                                            Application :
  Nom.       Overall      Cable
                                            Power cable : Indoors, cable trunking, outdoors                                         Aluminium Conductor
  Cross     Diameter      Weight            and burried in the ground, for power stations,
 Section                                    industry and switchgear as well as for urban
  Area       approx.      approx.           supply networks, if mechanical damage is                                                PVC Insulation
  mm²          mm         kg/km             unlikely.
   10          9.1         103              Special Features on Request :
                                            •	 Oil Resistance                                                                       PVC Sheath
   16          10.3        135
                                            •	 UV Resistance
   25          11.9        186              •	 Flame Retardant Cat. A, B, C
   35          13.1        231              •	 Flame Retardant Non Category
                                            •	 Heat Resistance
   50          15.0        306
                                            •	 Anti Termite
   70          17.1        391              •	 Anti Rodent
                                            •	 Low Smoke Zero Halogen
   95          19.2        498
                                            •	 Nylon Coated
   120         21.0        583
   150         23.5        725
   185         26.0        886              Note :
                                            Conductor Shape
   240         29.0        1,142
                                            10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
   300         32.0        1,388            25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted
                                            circular stranded (cm) conductor shape
   400         35.5        1,706
   500         40.5        2,219            Standard Packing
   630         44.5        2,709            10 - 800 sqmm supplied in wooden drum @ 1000 m
                                            Length Tolerance per drum ± 2%
   800         48.5        3,272
Electrical Data
              Conductor                         Inductance                   Current - Carrying Capacity at 30° C *                                      Short
                                                                                                                                                     circuit current
 Nom.         DC              AC         Trefoil           Flat
                                                                                                                                                            at
 Cross     Resistance     Resistance   formation        formation         in air        in ground              in air          in ground                 1 sec
 Sect.      at 20°C        at 70°C
             Max.           Max.                                          Max.             Max.                Max.               Max.                     Max.
 (mm²)      (Ω/km)         (Ω/km)      (mH/km)          (mH/km)            (A)              (A)                 (A)                (A)                     (kA)
  10          3.08          3.701       0.350                0.396         49                59                 50                  58                      0.76
  16          1.91          2.295       0.323                0.370         66                77                 68                  76                      1.22
  25          1.20          1.442       0.313                0.359         88                98                 91                  97                      1.90
  35         0.868          1.043       0.298                0.344        109               118                112                 117                      2.66
  50         0.641          0.770       0.290                0.336        134               140                138                 138                      3.80
  70         0.443          0.533       0.279                0.325        170               171                175                 169                      5.32
  95         0.320          0.385       0.274                0.320        210               205                216                 202                      7.22
  120        0.253          0.305       0.270                0.316        244               233                251                 229                      9.12
  150        0.206          0.249       0.265                0.312        283               261                291                 258                     11.40
  185        0.164          0.198       0.264                0.310        328               296                339                 292                     14.06
  240        0.125          0.152       0.260                0.306        395               344                407                 339                     18.24
  300        0.100          0.122       0.258                0.304        456               388                471                 382                     22.80
  400       0.0778          0.096       0.252                0.298        548               447                565                 440                     27.20
  500       0.0605          0.076       0.251                0.298        633               507                653                 499                     34.00
  630       0.0469          0.061       0.246                0.293        738               576                762                 566                     42.84
  800       0.0367          0.050       0.242                0.289        848               646                877                 635                     54.40
                                                                                                                                                                                  24233-01 Rev. 2.1 / 2015
                                                                                                                                                    www.kmi.co.id
                                                                             PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NAYY
NAYY 22xx(10-300)
          (10-300) mm²
                  mm²    0.6/1
                      0.6/1 kV kV
Al / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
                                                 Application :
  Nom.      Overall       Cable                                                                                                             Aluminium Conductor
                                                 Power cable : Indoors, cable trunking, outdoors
  Cross    Diameter       Weight                 and burried in the ground, for power stations,
 Section                                         industry and switchgear as well as for urban                                               PVC Insulation
  Area     approx.        approx.                supply networks, if mechanical damage is
  mm²        mm            kg/km                 unlikely.
                                                                                                                                            PVC Inner Sheath
   10        18.4           411                  Special Features on Request :
                                                 •	 Oil Resistance
   16        21.0           536                  •	 UV Resistance                                                                             PVC Sheath
   25        23.5           675                  •	 Flame Retardant Cat. A, B, C
                                                 •	 Flame Retardant Non Category
   35        26.0           834                  •	 Heat Resistance
                                                 •	 Anti Termite
   50        29.5           964                  •	 Anti Rodent
   70        33.0          1,229                 •	 Low Smoke Zero Halogen
                                                 •	 Nylon Coated
   95        38.0          1,632
   120       41.0          1,926
   150       44.0          2,259                 Note :
                                                 Conductor Shape
   185       50.5          2,877                 10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
                                                 25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
   240       55.5          3,576
   300       61.5          4,375                 Standard Packing
                                                 10 - 150 sqmm supplied in wooden drum @ 1000 m
                                                 185 - 300 sqmm will be suplied in wooden drum on available length
                                                 Length Tolerance per drum ± 2%
Electrical Data
                    Conductor                             Inductance                       Current - Carrying                                          Short
  Nom.            DC                   AC                                                      Capacity                                            circuit current
                                                                                               at 30°C *                                                  at
  Cross      Resistance             Resistance                                                                                                         1 sec
  Sect.       at 20°C                at 70°C                                          in air                    in ground
                Max.                  Max.                                            Max.                          Max.                                 Max.
  (mm²)        (Ω/km)                (Ω/km)                (mH/km)                     (A)                           (A)                                 (kA)
   10           3.08                  3.701                  0.269                      54                           61                                   0.76
   16           1.91                  2.295                  0.253                      73                           81                                   1.22
   25           1.20                  1.442                  0.257                      94                          103                                   1.90
   35          0.868                  1.043                  0.247                     116                          125                                   2.66
   50          0.641                  0.770                  0.247                     141                          148                                   3.80
   70          0.443                  0.533                  0.238                     178                          183                                   5.32
   95          0.320                  0.385                  0.238                     218                          219                                   7.22
   120         0.253                  0.305                  0.233                     253                          250                                   9.12
   150         0.206                  0.248                  0.235                     285                          279                                  11.40
   185         0.164                  0.198                  0.233                     331                          317                                  14.06
   240         0.125                  0.152                  0.232                     390                          366                                  18.24
   300         0.100                  0.122                  0.231                     447                          413                                  22.80
                                                                                                                                                                                       24233-02 Rev. 2.0 / 2009
                                                                                                                                                         www.kmi.co.id
                                                                                  PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NAYY
NAYY 33xx(10-400)
          (10-400) mm²
                  mm²    0.6/1
                      0.6/1 kV kV
Al / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
                                                 Application :
  Nom.      Overall        Cable                                                                                                                 Aluminium Conductor
                                                 Power cable : Indoors, cable trunking, outdoors
  Cross    Diameter        Weight                and burried in the ground, for power stations,
 Section                                         industry and switchgear as well as for urban                                                    PVC Insulation
  Area     approx.        approx.                supply networks, if mechanical damage is
  mm²        mm            kg/km                 unlikely.
                                                                                                                                                 PVC Inner Sheath
   10        19.4           459                  Special Features on Request :
   16        22.5           601                  •	 Oil Resistance
                                                 •	 UV Resistance                                                                                PVC Sheath
   25        24.5           767                  •	 Flame Retardant Cat. A, B, C
   35        27.5           952                  •	 Flame Retardant Non Category
                                                 •	 Heat Resistance
   50        30.0           986
                                                 •	 Anti Termite
   70        34.0          1,301                 •	 Anti Rodent
                                                 •	 Low Smoke Zero Halogen
   95        38.5          1,682
                                                 •	 Nylon Coated
   120       41.5          1,973
   150       46.0          2,399
   185       50.5          2,936                 Note :
                                                 Conductor Shape
   240       57.0          3,741
                                                 10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
   300       62.5          4,534                 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
   400       69.0          5,644                 50 - 400 sqmm supplied in sector shaped stranded (sm) conductor
                                                 Standard Packing
                                                 10 - 150 sqmm supplied in wooden drum @ 1000 m
                                                 185 - 400 sqmm will be suplied in wooden drum on available length
                                                 Length Tolerance per drum ± 2%
Electrical Data
                    Conductor                             Inductance                       Current - Carrying                                          Short
  Nom.          DC                     AC                                                      Capacity                                            circuit current
                                                                                               at 30°C *                                                  at
  Cross      Resistance             Resistance                                                                                                         1 sec
  Sect.       at 20°C                at 70°C                                          in air                    in ground
               Max.                   Max.                                            Max.                          Max.                                 Max.
  (mm²)        (Ω/km)                (Ω/km)                (mH/km)                     (A)                           (A)                                 (kA)
   10           3.08                  3.701                  0.269                      46                           52                                   0.76
   16           1.91                  2.295                  0.253                      62                           69                                   1.22
   25           1.20                  1.442                  0.257                      81                           88                                   1.90
   35          0.868                  1.043                  0.247                     100                          106                                   2.66
   50          0.641                  0.770                  0.247                     126                          131                                   3.80
   70          0.443                  0.533                  0.238                     158                          160                                   5.32
   95          0.320                  0.385                  0.238                     194                          192                                   7.22
   120         0.253                  0.305                  0.233                     225                          219                                   9.12
   150         0.206                  0.248                  0.235                     257                          245                                  11.40
   185         0.164                  0.198                  0.233                     297                          278                                  14.06
   240         0.125                  0.152                  0.232                     352                          322                                  18.24
   300         0.100                  0.122                  0.231                     405                          364                                  22.80
   400         0.0778                 0.096                  0.229                     471                          415                                  27.20
                                                                                                                                                                                       24233-03 Rev. 2.0 / 2009
                                                                                                                                                         www.kmi.co.id
                                                                                  PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NAYY
NAYY 44xx(10-400)
          (10-400) mm²
                  mm²    0.6/1
                      0.6/1 kV kV
Al / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
                                                 Application :
  Nom.      Overall       Cable
                                                 Power cable : Indoors, cable trunking, outdoors
  Cross    Diameter       Weight                                                                                                                  Aluminium Conductor
                                                 and burried in the ground, for power stations,
 Section                                         industry and switchgear as well as for urban
  Area     approx.        approx.                supply networks, if mechanical damage is                                                         PVC Insulation
  mm²        mm            kg/km                 unlikely.
                                                                                                                                                  PVC Inner Sheath
   10        21.5           541                  Special Features on Request :
                                                 •	 Oil Resistance
   16        24.5           715                  •	 UV Resistance
   25        27.0           920                  •	 Flame Retardant Cat. A, B, C                                                                  PVC Sheath
                                                 •	 Flame Retardant Non Category
   35        30.0          1,147                 •	 Heat Resistance
                                                 •	 Anti Termite
   50        35.5          1,306                 •	 Anti Rodent
   70        39.0          1,659                 •	 Low Smoke Zero Halogen
                                                 •	 Nylon Coated
   95        44.5          2,163
   120       48.5          2,599
   150       54.5          3,164                 Note :
                                                 Conductor Shape
   185       59.0          3,867                 10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
                                                 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
   240       66.0          4,854                 50 - 400 sqmm supplied in sector shaped stranded (sm) conductor
   300       72.5          5,884
                                                 Standard Packing
   400       82.5          7,473                 10 - 120 sqmm supplied in wooden drum @ 1000 m
                                                 150 - 400 sqmm will be suplied in wooden drum on available length
                                                 Length Tolerance per drum ± 2%
Electrical Data
                    Conductor                             Inductance                       Current - Carrying                                          Short
  Nom.            DC                   AC                                                      Capacity                                            circuit current
                                                                                               at 30°C *                                                  at
  Cross      Resistance             Resistance                                                                                                         1 sec
  Sect.       at 20°C                at 70°C                                          in air                    in ground
                Max.                  Max.                                            Max.                          Max.                                 Max.
  (mm²)        (Ω/km)                (Ω/km)                (mH/km)                     (A)                           (A)                                 (kA)
   10           3.08                  3.701                  0.269                      53                           59                                   0.76
   16           1.91                  2.295                  0.253                      71                           77                                   1.22
   25           1.20                  1.442                  0.257                      93                           99                                   1.90
   35          0.868                  1.043                  0.247                     115                          119                                   2.66
   50          0.641                  0.770                  0.247                     134                          135                                   3.80
   70          0.443                  0.533                  0.238                     167                          165                                   5.32
   95          0.320                  0.385                  0.238                     207                          198                                   7.22
   120         0.253                  0.305                  0.233                     240                          225                                   9.12
   150         0.206                  0.248                  0.235                     277                          254                                  11.40
   185         0.164                  0.198                  0.233                     316                          286                                  14.06
   240         0.125                  0.152                  0.232                     377                          332                                  18.24
   300         0.100                  0.122                  0.231                     433                          376                                  22.80
   400         0.0778                 0.096                  0.229                     510                          432                                  27.20
                                                                                                                                                                                       24233-04 Rev. 2.0 / 2009
                                                                                                                                                         www.kmi.co.id
                                                                                  PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NAYY 5  x (10-50) mm 2
                       0.6/1
NAYY 5 x (10-50) mm 0.6/1
                   2
                          kV kV
Al / PVC / PVC
(Aluminium Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
                                                 Application :
  Nom.      Overall        Cable                                                                                                                 PVC Filler
                                                 Power cable : Indoors, cable trunking, outdoors
  Cross    Diameter        Weight                and burried in the ground, for power stations,                                                  Aluminium Conductor
 Section                                         industry and switchgear as well as for urban
  Area     approx.        approx.                                                                                                                PVC Insulation
                                                 supply networks, if mechanical damage is
  mm²        mm            kg/km                 unlikely.
                                                                                                                                                 PVC Inner Sheath
   10        23.0           636                  Special Features on Request :
   16        26.5           847                  •	 Oil Resistance
                                                 •	 UV Resistance
   25        29.5          1,098                 •	 Flame Retardant Cat. A, B, C
   35        33.0          1,389                 •	 Flame Retardant Non Category                                                                 PVC Sheath
                                                 •	 Heat Resistance
   50        38.0          1,731
                                                 •	 Anti Termite
                                                 •	 Anti Rodent
                                                 •	 Low Smoke Zero Halogen
                                                 •	 Nylon Coated
                                                 Note :
                                                 Conductor Shape
                                                 10 - 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
                                                 25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape
                                                 Standard Packing
                                                 10 - 50 sqmm supplied in wooden drum @ 1000 m
                                                 Length Tolerance per drum ± 2%
Electrical Data
                    Conductor                             Inductance                       Current - Carrying                                          Short
  Nom.          DC                     AC                                                      Capacity                                            circuit current
                                                                                               at 30°C *                                                  at
  Cross      Resistance             Resistance                                                                                                         1 sec
  Sect.       at 20°C                at 70°C                                          in air                    in ground
               Max.                   Max.                                            Max.                          Max.                                 Max.
  (mm²)        (Ω/km)                (Ω/km)                (mH/km)                     (A)                           (A)                                 (kA)
   10           3.08                  3.701                  0.269                      54                           60                                   0.76
   16           1.91                  2.295                  0.253                      73                           78                                   1.22
   25           1.20                  1.442                  0.257                      97                          101                                   1.90
   35          0.868                  1.043                  0.247                     120                          121                                   2.66
   50          0.641                  0.771                  0.247                     147                          144                                   3.80
                                                                                                                                                                                       24233-05 Rev. 2.0 / 2009
                                                                                                                                                         www.kmi.co.id
                                                                                  PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification