Conductor Inductance Current - Carrying Capacity at 30 C * Short
circuit current
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km)
Trefoil
formation
(mH/km)
Flat
formation
(mH/km)
in air
Max. 
(A)
in ground
Max.
(A)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.452  0.498  25  33  26  33  0.21 
  2.5  7.41  9.449  0.417  0.463  34  43  35  43  0.36 
  4  4.61  5.878  0.387  0.433  45  56  46  55  0.57 
  6  3.08  3.927  0.364  0.410  57  69  58  68  0.86 
  10  1.83  2.334  0.336  0.382  78  92  80  91  1.43 
  16  1.15  1.466  0.315  0.361  104  118  107  117  2.29 
  25  0.727  0.927  0.302  0.348  141  152  145  151  3.58 
  35  0.524  0.668  0.289  0.335  173  182  178  180  5.01 
  50  0.387  0.494  0.279  0.325  213  216  220  214  7.15 
  70  0.268  0.342  0.270  0.316  271  265  279  261  10.01 
  95  0.193  0.247  0.263  0.310  335  316  346  312  13.59 
  120  0.153  0.196  0.259  0.305  392  359  404  355  17.16 
  150  0.124  0.160  0.259  0.305  451  403  466  397  21.45 
  185  0.0991  0.128  0.258  0.304  526  455  543  449  26.46 
  240  0.0754  0.099  0.253  0.300  630  527  650  519  34.32 
  300  0.0601  0.080  0.249  0.295  728  593  751  584  42.90 
  400  0.0470  0.064  0.249  0.295  848  671  875  660  57.20 
  500  0.0366  0.052  0.246  0.292  985  757  1018  744  71.50 
  630  0.0283  0.043  0.243  0.289  1141  849  1179  834  90.09 
  800  0.0221  0.036  0.241  0.287  1295  937  1339  921  114.40 
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
  1.5  5.9  48 
  2.5  6.4  61 
  4  6.9  80 
  6  7.5  102 
  10  8.5  147 
  16  9.5  207 
  25  11.3  315 
  35  12.4  410 
  50  14.1  555 
  70  16.1  759 
  95  18.1  1,006 
  120  19.9  1,244 
  150  22.5  1,518 
  185  25.0  1,917 
  240  28.0  2,504 
  300  30.5  3,039 
  400  34.5  3,892 
  500  38.5  4,981 
  630  43.5  6,478 
  800  48.0  8,134
N2XY 1 x (1.5-800) mm 0.6/1 kV
N2XY 1 x (1.5-800) mm 0.6/1 kV
Cu / XLPE / PVC
Application :
Power cable : Indoors, cable trunking, outdoors 
and  burried  in  the  ground,  for  power  stations, 
industry  and  switchgear  as  well  as  for  urban 
supply  networks,  if  mechanical  damage  is 
unlikely.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted 
circular stranded (cm) conductor shape
Standard Packing
1.5 - 10 sqmm supplied in coil @ 100 m
16 - 400 sqmm supplied in wooden drum @ 1000 m
500 - 800 sqmm supplied in wooden drum on available length
Length Tolerance per drum  2%
Construction Data
Electrical Data
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specifcation : IEC 60502-1
PVC Sheath
Copper Conductor
XLPE Insulation
1
5
7
3
3
-
0
1
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short 
circuit current
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  29  34  0.21 
  2.5  7.41  9.449  0.293  38  44  0.36 
  4  4.61  5.878  0.275  50  58  0.57 
  6  3.08  3.927  0.263  64  73  0.86 
  10  1.83  2.334  0.248  88  98  1.43 
  16  1.15  1.467  0.238  116  128  2.29 
  25  0.727  0.927  0.240  154  165  3.58 
  35  0.524  0.669  0.233  190  199  5.01 
  50  0.387  0.494  0.232  230  236  7.15 
  70  0.268  0.342  0.229  292  292  10.01 
  95  0.193  0.247  0.224  356  348  13.59 
  120  0.153  0.196  0.223  414  397  17.16 
  150  0.124  0.160  0.224  474  445  21.45 
  185  0.0991  0.128  0.225  544  502  26.46 
  240  0.0754  0.099  0.223  644  582  34.32 
  300  0.0601  0.080  0.221  737  654  42.90 
N2XY 2 x (1.5-300) mm
2
 0.6/1 kV
N2XY 2 x (1.5-300) mm
2
 0.6/1 kV
Cu / XLPE / PVC
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape             
16  sqmm supplied in non compacted circular stranded (rm) conductor shape   
25 - 300 sqmm supplied in  compacted circular stranded (cm) conductor shape   
           
Standard Packing
1.5 - 150 sqmm supplied in wooden drum @ 1000 m       
185 -  300 sqmm will be suplied in wooden drum on available length     
Length Tolerance per drum  2%           
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
  1.5  12.0  182 
  2.5  13.0  223 
  4  14.1  279 
  6  15.2  344 
  10  17.2  474 
  16  19.2  639 
  25  22.5  912 
  35  25.0  1,173 
  50  27.5  1,411 
  70  31.5  1,929 
  95  35.5  2,589 
  120  39.0  3,182 
  150  43.5  3,894 
  185  48.0  4,847 
  240  54.0  6,217 
  300  59.5  7,697 
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
Power cable : Indoors, cable trunking, outdoors 
and  burried  in  the  ground,  for  power  stations, 
industry  and  switchgear  as  well  as  for  urban 
supply  networks,  if  mechanical  damage  is 
unlikely.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
XLPE Insulation
Copper Conductor
PVC Sheath
PVC Inner Sheath
1
5
7
3
3
-
0
2
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short 
circuit current
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  21  28  0.21 
  2.5  7.41  9.449  0.293  32  37  0.36 
  4  4.61  5.878  0.275  43  49  0.57 
  6  3.08  3.927  0.263  54  61  0.86 
  10  1.83  2.334  0.248  74  83  1.43 
  16  1.15  1.467  0.238  99  107  2.29 
  25  0.727  0.927  0.240  131  139  3.58 
  35  0.524  0.669  0.233  162  167  5.01 
  50  0.387  0.494  0.232  200  203  7.15 
  70  0.268  0.342  0.229  252  248  10.01 
  95  0.193  0.247  0.224  309  298  13.59 
  120  0.153  0.196  0.223  359  339  17.16 
  150  0.124  0.160  0.224  411  379  21.45 
  185  0.0991  0.128  0.225  475  430  26.46 
  240  0.0754  0.099  0.223  562  497  34.32 
  300  0.0601  0.080  0.221  645  560  42.90 
N2XY 3 x (1.5-300) mm
2
 0.6/1 kV
N2XY 3 x (1.5-300) mm
2
 0.6/1 kV
Cu / XLPE / PVC
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape             
16  sqmm supplied in non compacted circular stranded (rm) conductor shape   
25 - 35 sqmm supplied in  compacted circular stranded (cm) conductor shape   
50 - 300 sqmm supplied in  sector shaped stranded (sm) conductor     
         
Standard Packing
1.5 - 120 sqmm supplied in wooden drum @ 1000 m       
150 -  300 sqmm will be suplied in wooden drum on available length     
Length Tolerance per drum  2%           
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
  1.5  12.5  203 
  2.5  13.5  253 
  4  14.7  324 
  6  16.0  405 
  10  18.0  572 
  16  20.5  786 
  25  24.0  1,139 
  35  26.0  1,483 
  50  28.0  1,698 
  70  32.5  2,382 
  95  36.0  3,168 
  120  39.0  3,895 
  150  44.0  4,830 
  185  48.5  5,971 
  240  54.5  7,752 
  300  59.0  9,544 
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
Power cable : Indoors, cable trunking, outdoors 
and  burried  in  the  ground,  for  power  stations, 
industry  and  switchgear  as  well  as  for  urban 
supply  networks,  if  mechanical  damage  is 
unlikely.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
PVC Sheath
Copper Conductor
XLPE Insulation
PVC Inner Sheath
1
5
7
3
3
-
0
3
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short 
circuit current
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  27  31  0.21 
  2.5  7.41  9.449  0.293  35  41  0.36 
  4  4.61  5.878  0.275  47  53  0.57 
  6  3.08  3.927  0.263  59  67  0.86 
  10  1.83  2.334  0.248  81  89  1.43 
  16  1.15  1.467  0.238  108  116  2.29 
  25  0.727  0.927  0.240  146  151  3.58 
  35  0.524  0.669  0.233  180  181  5.01 
  50  0.387  0.494  0.232  212  208  7.15 
  70  0.268  0.342  0.229  265  254  10.01 
  95  0.193  0.247  0.224  327  305  13.59 
  120  0.153  0.196  0.223  379  347  17.16 
  150  0.124  0.160  0.224  442  392  21.45 
  185  0.0991  0.128  0.225  504  441  26.46 
  240  0.0754  0.099  0.223  597  511  34.32 
  300  0.0601  0.080  0.221  685  576  42.90 
N2XY 4 x (1.5-300) mm
2
 0.6/1 kV
N2XY 4 x (1.5-300) mm
2
 0.6/1 kV
Cu / XLPE / PVC
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape             
16  sqmm supplied in non compacted circular stranded (rm) conductor shape   
25 - 35 sqmm supplied in  compacted circular stranded (cm) conductor shape   
50 - 300 sqmm supplied in  sector shaped stranded (sm) conductor     
               
Standard Packing
1.5 - 70 sqmm supplied in wooden drum @ 1000 m       
95 -  300 sqmm will be suplied in wooden drum on available length     
Length Tolerance per drum  2%           
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
  1.5  13.3  232 
  2.5  14.5  294 
  4  15.8  382 
  6  17.2  484 
  10  19.5  700 
  16  22.0  973 
  25  26.0  1,422 
  35  28.5  1,864 
  50  32.5  2,218 
  70  36.5  3,105 
  95  40.5  4,148 
  120  45.5  5,180 
  150  51.5  6,371 
  185  56.0  7,861 
  240  62.5  10,208 
  300  68.0  12,573 
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
Power cable : Indoors, cable trunking, outdoors 
and  burried  in  the  ground,  for  power  stations, 
industry  and  switchgear  as  well  as  for  urban 
supply  networks,  if  mechanical  damage  is 
unlikely.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
PVC Inner Sheath
PVC Sheath
Copper Conductor
XLPE Insulation
1
5
7
3
3
-
0
4
 
 
R
e
v
.
 
2
.
0
 
/
 
2
0
0
9
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
Electrical Data
Conductor Inductance Current - Carrying
Capacity
at 30C *
Short 
circuit current
at
1 sec
Max.
(kA)
Nom.
Cross
Sect.
(mm)
DC
Resistance
at 20C
Max.
(/km)
AC
Resistance
at 90C
Max.
(/km) (mH/km)
in air
Max.
(A)
in ground
Max.
(A)
  1.5  12.1  15.429  0.315  27  32  0.21 
  2.5  7.41  9.449  0.293  36  42  0.36 
  4  4.61  5.878  0.275  48  54  0.57 
  6  3.08  3.927  0.263  61  68  0.86 
  10  1.83  2.334  0.248  84  91  1.43 
  16  1.15  1.467  0.238  112  118  2.29 
  25  0.727  0.927  0.240  152  153  3.58 
  35  0.524  0.669  0.233  187  184  5.01 
  50  0.387  0.494  0.232  227  217  7.15 
N2XY 5 x (1.5-50) mm
2
 0.6/1 kV
N2XY 5 x (1.5-50) mm
2
 0.6/1 kV
Cu / XLPE / PVC
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) 
conductor shape             
16  sqmm supplied in non compacted circular stranded (rm) conductor shape   
25 - 50 sqmm supplied in  compacted circular stranded (cm) conductor shape   
         
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m       
Length Tolerance per drum  2%
Nom.
Cross
Section
Area
Overall
Diameter
Cable
Weight
approx. approx.
mm mm kg/km
Construction Data
  1.5  14.2  269 
  2.5  15.5  345 
  4  17.0  453 
  6  18.5  579 
  10  21.5  838 
  16  24.0  1,174 
  25  28.5  1,728 
  35  31.5  2,273 
  50  36.0  2,917 
(Copper Conductor, XLPE Insulated, PVC Sheathed)
Standard Specifcation : IEC 60502-1
Application :
Power cable : Indoors, cable trunking, outdoors 
and  burried  in  the  ground,  for  power  stations, 
industry  and  switchgear  as  well  as  for  urban 
supply  networks,  if  mechanical  damage  is 
unlikely.
Special Features on Request
  Fire Resistance
  Oil Resistance
  UV Resistance
  Flame Retardant Cat. A, B, C
  Flame Retardant Non Category
  Anti Termite
  Anti Rodent
  Low Smoke Zero Halogen
  Nylon Coated
PVC Filler
PVC Inner Sheath
XLPE Insulation
Copper Conductor
PVC Sheath