24- 9902- 18, Rev.
                                                                            Installation Instructions   T2000 Series
                                                                                          Issue Date    March 2016
            T2000 Series Low Voltage Fan Coil Thermostats
                                                            •   air handling units
Application
                                                            T2000ACx-0C0
 IMPORTANT:            Use this T2000 Series Low
 Voltage Fan Coil Thermostat only as an operating           On the T2000ACx-0C0, switch positions HEAT, OFF,
 control. Where failure or malfunction of thermostat        and COOL provide separate temperature control in the
 could lead to personal injury or property damage to        controlled space. A second switch controls the
 the controlled equipment or other property,                LOW-MED-HIGH fan motor speeds.
 additional precautions must be designed into the
 control system. Incorporate and maintain other             T2000ECx-0C0
 devices, such as supervisory or alarm systems or           On the T2000ECx-0C0, switch positions provide ON
 safety or limit controls, intended to warn of or protect   and OFF temperature control in the controlled space.
 against failure or malfunction of the thermostat.          A second switch controls the LOW-MED-HIGH fan
                                                            motor speeds.
 IMPORTANT :            Utiliser ce Low Voltage Fan Coil
 Thermostat uniquement en tant que dispositif de
                                                            Installation
 régulation. Lorsqu'une défaillance ou un
 dysfonctionnement du thermostat risque de                  Install the T2000 where the occupant can read and
 provoquer des blessures ou d'endommager                    adjust the setpoint dial selector easily. Situate the
 l'équipement contrôlé ou un autre équipement, la           thermostat where the temperature is representative of
 conception du système de contrôle doit intégrer des        the general room conditions. Avoid installing the
 dispositifs de protection supplémentaires. Veiller         T2000 near cold or warm air drafts, radiant heat, on an
 dans ce cas à intégrer de façon permanente d'autres        outside wall, or in direct sunlight.
 dispositifs, tels que des systèmes de supervision ou
 d'alarme, ou des dispositifs de sécurité ou de             Parts Included
 limitation, ayant une fonction d'avertissement ou de       One T2000xCx-0C0 low voltage fan coil thermostat.
 protection en cas de défaillance ou de
 dysfonctionnement du thermostat.                           Mounting
The T2000ACx (Heat-Off-Cool) and T2000ECx                   Mount the T2000 Series thermostat to a
(On-Off) low voltage fan coil thermostats feature local     2 x 4 in. (51 x 102 mm) standard U.S. wallbox.
control of High, Medium, and Low fan speeds.                Follow the instructions for removing the cover and then
The plastic enclosure features a removable cover            proceed to the Wallbox Mounting and the Wiring
imprinted with either a Fahrenheit or a Celsius scale,      sections.
providing direct access to the adjustable temperature       Note: All T2000 Series models require two No. 6
setpoint dial and control switches. The main                mounting screws (not included).
thermostatic element is a gas-filled bellows that drives
an integral snap-action two-position electrical switch.     Removing the Cover
The adjustable setpoint knob sits over the element on
                                                            To remove the cover from the base, insert a 1/8 in.
a Printed Circuit Board (PCB) along with two terminal
                                                            (3.2 mm) Phillips screwdriver into the retention screw
blocks and two control switches. The PCB sits on the
                                                            located in the center of the top of the cover. Loosen
PCB Support, which is hinged at the bottom to the
                                                            (but do not remove) the Phillips head screw and gently
plastic base, swinging free at the top to provide easy
                                                            pull the cover away from the base until it is free.
access during mounting and wiring.
                                                            (See Figure 1.)
Typical low voltage applications are:
•    fan coil units
•    electric heaters
©   2016 Johnson Controls, Inc.                                                                                        1
    Part No. 24-9902-18, Rev. B                                                                  www.johnsoncontrols.com
                                         Retention Screw                           Base          Retaining Screw
                65     70
                               75                                                                             PCB Support
          60
                                                                                                               Base Latch
                                    80
     55
                                    85
     50
                                          5-1/4                                                             3.28
                                          (133)                                                            (83.4)
                HEAT    HIGH
                OFF     MED
                COOL    LOW
                                                                                                              PCB Support
                                                                                                              Base Hinge
               3-15/32 (88)                                1-2/3 (42.5)
     Figure 1: T2000xCF-0C0 Cover and Case
               Dimensions, in. (mm)                                                                         PCB Support
                                                                                                              (Back)
Wallbox Mounting
To mount the T2000-base to the to standard
                                                                                                            PCB Support
U.S. wallbox, refer to Figure 1 and Figure 2 and:                                                         Base Latch Notch
1. Depress the PCB support latch, located above the
   temperature setpoint switch in the upper                                 Figure 2: T2000xCx-0C0 Base with PCB Support
   right-hand corner of the PCB support, and gently                                       Mounting Dimensions
   pushing downward, swing the top of the PCB                             2. Pull the wiring through the square hole in the
   support away from the unit.                                                base.
Note: The PCB support will remain attached at the                         3. Fasten the base to the wallbox using the two
bottom of the base, providing access to the mounting                         vertical holes and two No. 6 screws (not provided)
and wiring holes.
                                                                          4. Pull the wiring through the square hole in the PCB
                                                                             support and gently snap the PCB support to the
IMPORTANT: Do not remove PCB from the PCB                                    PCB Support Base Latch.
support. Removing the PCB from the PCB support
voids the product warranty.                                               5. Proceed to the Wiring section for the correct
                                                                             configuration for the application and unit.
                                                                          Note: The factory-calibrated T2000 thermostat
                                                                          requires no field adjustment. Do not attempt
                                                                          recalibration.
                                                                          6. Reposition the cover and tighten the retention
                                                                             screw.
                                                                          Wiring
                                                                          IMPORTANT: Make all wiring connections in
                                                                          accordance with local, national, and regional
                                                                          regulations. Do not exceed the T2000 Series
                                                                          thermostat’s electrical ratings.
2   T2000 Series Low Voltage Fan Coil Thermostats Installation Instructions
Model T2000ACx-0C0                                           Model T2000ECx-0C0
Wiring terminal designations appear in Table 1. Wiring       Wiring terminal designations appear in Table 2 Wiring
connections for typical T2000ACx applications appear         connections for typical T2000ECx applications appear
in Figure 3 and Figure 4.                                    in Figure 5 and Figure 6.
Table 1: T2000ACx-0C0 Wiring Terminals                       Table 2: T2000ECx-0C0 Wiring Terminals
             Model T2000ACx-0C0                                             Model T2000-ECx-0C0
   Terminal Number         Connection                             Terminal Number           Connection
            1             Heating Valve +                                  3                   Heating Valve Common
            2             Common                                           4                   High Fan Speed
            3             Heating Valve Common                             5                   Cooling Valve Common
            4             High Fan Speed                                   6                   Low Fan Speed
            5             Cooling Valve Common                             7                   Medium Fan Speed
            6             Low Fan Speed                                    8                   24 VAC Power
            7             Medium Fan Speed
            8             24 VAC Power
            9             Cooling Valve                                                                     COOL (C)
                                                              System: ON-OFF                                 Valve
                                                              Fan:
                                                              HIGH-MED-LOW
 System:
                                                                   3 4 5
 HEAT-OFF-COOL
 Fan:                                      HEAT (H)/
 HIGH-MED-LOW                              COOL (C)
                                            Valve
   1 2 3 4 5
                                                                               HIGH
                                                                                                           H
                                                                               MED
                                                                                                   M
                                                                               LOW
                                                                                           L
                 HIGH                                              8 7 6
                 MED                      H                                                                         24 VAC
                                  M
                 LOW                                                                        All Wiring to be
                          L
                                                                                          Supplied by Installers
    9 8 7 6
                                                   24 VAC
                           All Wiring to be
                         Supplied by Installers                 Figure 5: Wiring the T2000ECx-0C0 for Cooling
                                                                Only: 2-Pipe System with 3-Speed Fan Control
      Figure 3: Wiring the T2000ACx-0C0 for                                                                 HEAT (H)/
       Heating/Cooling Only: 2-Pipe System                    System: ON-OFF                                COOL (C)
             with 3-Speed Fan Control                         Fan:                            Strap-on       Valve
                                                              HIGH-MED-LOW                  Thermostat
                                                                   3 4 5               Winter
 System:                         COOL             HEAT
 HEAT-OFF-COOL                    (C)              (H)                                Summer
 Fan:                            Valve            Valve
 HIGH-MED-LOW                                                                  HIGH
   1 2 3 4 5                                                                                               H
                                                                               MED
                                                                                                   M
                                                                               LOW
                                                                                           L
                                                                   8 7 6
                 HIGH                                                                                               24 VAC
                                          H                                                 All Wiring to be
                 MED
                                  M                                                       Supplied by Installers
                 LOW
                          L
    9 8 7 6
                                                   24 VAC           Figure 6: Wiring the T2000ECx-0C0 for
                           All Wiring to be
                         Supplied by Installers               Heating/Cooling Only: 2-Pipe System with 3-Speed
                                                                   Fan Control and Automatic Changeover
      Figure 4: Wiring the T2000ACx-0C0 for
       Heating/Cooling Only: 4-Pipe System
             with 3-Speed Fan Control
                                         T2000 Series Low Voltage Fan Coil Thermostats Installation Instructions         3
Troubleshooting                                                            Repairs and Replacement
For the ACx thermostat to function properly, the                           Do not attempt to repair the T2000 Series thermostat.
Heat-Off-Cool switch must be fully in the desired                          In case of an improperly functioning control, contact
position. For the ECx thermostat to function, the                          the nearest Johnson Controls® representative, and
ON/OFF switch must be fully in the ON position.                            specify the desired product code number. When
                                                                           contacting the supplier for a replacement please state
                                                                           the type/model number of the control located on the
                                                                           data plate or cover label.
Technical Specifications
                         Product      T2000ACC-0C0                        Low Voltage Heat-Off-Cool Wallbox Fan Coil
                                                                          Thermostat with Celsius Temperature Setpoint Scale
                                      T2000ACF-0C0                        Low Voltage Heat-Off-Cool Wallbox Fan Coil
                                                                          Thermostat with Fahrenheit Temperature Setpoint Scale
                                      T2000ECC-0C0                        Low Voltage On-Off Wallbox Fan Coil Thermostat
                                                                          with Celsius Temperature Setpoint Scale
                                      T2000ECF-0C0                        Low Voltage On-Off Wallbox Fan Coil Thermostat
                                                                          with Fahrenheit Temperature Setpoint Scale
           Power Requirements         24 VAC at 50/60 Hz, Class 2
             Thermostat Switch        Setpoint Range                      50 to 85°F; (10 to 30°C)
                 System Switch        ACx Models:                         Double-Pole, Triple Throw (DP3T)
                                      ECx Models:                         Double-Pole, Double Throw (DPDT)
                     Fan Switch       All Models:                         Double-Pole, Triple Throw (DP3T)
           Low Voltage Control        Current:                            2 A 2 A, Non-Inductive
                       Ratings        Power:                              48 VA, Class 2
             Ambient Operating        44 to 85°F; (7 to 30°C) 85% Noncondensing RH
                   Conditions*
               Ambient Storage        -40 to 122°F; (-40 to 50°C) 85% Noncondensing RH
                   Conditions*
                    Dimensions        3.46 x 5.24 x 1.91 in. (88 x 133 x 49 mm)
               Shipping Weight        0.55 lb (0.26 kg)
    *    Operating or storing this thermostat at temperatures outside the stated limits can result in damage to the bellows.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact:                NA/SA Single Point of Contact:                   APAC Single Point of Contact:
JOHNSON CONTROLS                                 JOHNSON CONTROLS                                 JOHNSON CONTROLS
WESTENDHOF 3                                     507 E MICHIGAN ST                                C/O CONTROLS PRODUCT
45143 ESSEN                                      MILWAUKEE WI 53202                               MANAGEMENT
GERMANY                                          USA                                              NO. 22 BLOCK D NEW DISTRICT
                                                                                                  WUXI JIANGSU PROVINCE 214142
                                                                                                  CHINA
                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                              Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                     All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
4       T2000 Series Low Voltage Fan Coil Thermostats Installation Instructions