AHU Fan performance testing
AHU Flow Pressure of fan Power Temperature AIR
No M3/hr Pa KW *C
1
Fan pressure mean differential pressure across fan
Power in KW when other parmeters are taken at that time only
Pump performance testing
Pump Flow Pressure of Pump Power Temperature or water
No M3/hr Kg/cm2 KW *C
Pump pressure mean differential pressure across Pump (Discharge - suction)
Power in KW when other parmeters are taken at that time only
IY PLANT – AHU TR
VELO
CITY AREA
DBT (ºC) WBT (ºC) h1 h2
(M/SE (M²)
C)
AHU
15.5 15.5 5.517 1.17 68.134 40.546
01
SUPPLY AIR
RETURN AIR 25.5 23
AHU
15.5 14 6 1.17 68.134 42.218
02
SUPPLY AIR
RETURN AIR 25.5 23
AHU
13.5 11 8.133 4.532 52.25 39.292
03
SUPPLY AIR
RETURN AIR 26.5 18.5
U AHU04
SUPPLY AIR 20.5 18.5 13.45 8.35 64.372 50.16
AH
20 18.5 5.811 8.4 69.47 55.5
05
SUPPLY AIR
RETURN AIR 33.5 23.5
RETURN AIR 31.5 22
AHU
20.5 19 4.117 6.21 64.372 48.906
06
SUPPLY AIR
RETURN AIR 32 22 2.33 2.96 64.372 48.906
AHU
13.2 12.5 6.66 1.205 68.134 35.112
10
SUPPLY AIR
RETURN AIR 25.5 23
AHU
15.5 14.5 5.222 5.197 58.52 52.25
11
SUPPLY AIR
RETURN AIR 27 20.3
AHU
22.3 20.5 6.53 9.5 68.134 59.356
12
SUPPLY AIR
RETURN AIR 31.5 23
AHU
23 21 4.15 2.8 68.134 67.298
13
SUPPLY AIR
RETURN AIR 29 22.8
R DESEGN DATA OF AHU
CHANG FLOW IN
E IN SUPPLY TR TEMP (ºC) RH (%)
ENTHAL (M³/HR)
PY
27.588 23236.2 58.8281571428571
14±1 75±5
25.916 25272 60.1045714285714 14±1 75±5
12.958 132696.96 157.797046349206 12±1 95-100
14.212 404307 527.310452380952
13.97 175728 225.287602339181
15.466 92032.2 130.622421428572 26±2 60±5
15.466 24828.48 35.2393638095238
33.022 28891.08 87.5522014285714 14±1 85±5
6.27 97703.6 56.2183412698412 17±1 95-100
8.778 223326 179.9015 26±2 60±5
0.836 41832 3.20933333333333 26±2 55±5
13.4444444444444
EGN DATA OF AHU
FLOW IN
SUPPLY TR
(M³/HR)
36000 200
36000 200
140600 270
185000 166.6
40000 220
190000 195
225000 275
80000 125