IKU FACULTY of ARCHITECTURE PHYSICAL ENVIRONMENTAL CONTROL 2
Table 4: Wall Type Condenser Boilers
Width Length Height
KW (mm) (mm) (mm)
29 560 431 685
43 900 431 685
60 900 431 685
80 520 465 1.280
100 520 465 1.280
200 1.040 465 1.280
300 1.560 465 1.280
400 2.080 465 1.280
500 2.600 465 1.280
600 3.120 465 1.280
700 3.640 465 1.280
800 4.160 465 1.280 elevation
416 cm elevation
Calculation of Flue Section
F smoke = ( 0,03 or 0,02 ) * Qk / h
F fresh air = F / 2
F exhaust air = F / 4
F smoke = Smoke flue section, cm2
F fresh air = Fresh air flue section, cm2
F exhaust air = Exhaust air flue section, cm 2
0,03 = Coefficient if coal is used as fuel
0,02 = Coefficient if liquid fuel or natural gas is used
Qk = Boiler capacity, W
h = Flue vertical height, m
12