VESDA LCD PROGRAMMER

UL S5198, ULC S7554, FM 1DOA4.AY, LPC, SSL, VdS

DESCRIPTION
The Programmer Module allows direct access to all VESDAnet
devices on a VESDA smoke detection system. It allows
configuration and status reporting of detectors, displays and
interfaces and is required when installing, commissioning
and maintaining a VESDA network. By incorporating a user
friendly menu, navigation through the comprehensive features
of VESDAnet is convenient and simple.

The programmer module is available as a handheld device


or can be mounted into a LaserPLUS or LaserSCANNER
detector, a remote mounting box or a 19in sub rack.

The two rows of large push buttons enable the user to log ON
and navigate through the menu trees to the various command
and parameter setting functions. The top row of keys are called
“Soft Keys” and are assigned programming options appropriate
to the screen being viewed.

Some of the parameters that can be accessed via the


programmer include device status reporting, zone number and
name allocation, flow normalization, alarm threshold setting
(day, night, weekend), initiation of AutoLearn™, wiring order,
relay testing and event log review.

Up to 14 assigned Users or Administrators with an individual 4 digit Personal Identification Number (PIN), and one
Distributor, can log onto a VESDAnet system under one of three levels of access which are password protected.

User (USR) is only able to view parameters, check status, alarms and reset the system.

Administrator (ADM) has access to most commands and programming parameters.

Distributor (DST) is the topmost level and has unlimited access to all commands and parameters in the system.

Lost PIN numbers can be overcome by obtaining a once only pass number from your VESDA distributor.

The programmer automatically logs OFF when not in use for more than 10 minutes. The user is prompted with a
beeping sound at 1 minute and at 15 seconds before log OFF. Any key may be pressed to cancel the automatic log
OFF process.

PROGRAMMING FUNCTIONS
• System Configuration • Commissioning and Testing
• Detector Zone Configuration and set up • Set Date and Time
• Detector Zone Control • Referencing
• System Status • AutoLearn™
• Smoke Threshold and Detector Sensitivity Settings • Passwords and User Configuration
• Event Log Interrogation • System Fault Diagnostic

Form No. V.1.03.01-1


704 S. 10th Street · P.O. Box 610 · Blue Springs, Missouri 64013-0610 U.S.A. · (816) 229-3405 · (816) 229-4615 · www.fike.com
FEATURES
• User Friendly Menu System • Locates Communications Failures
• Supports Multiple Languages • Password Security
• Single Point Access to Entire VESDAnet System • Hand Held or Remote Mounting
• Alarm and Fault Simulation • Automatic Logoff when Inactive
• Shows Wiring Order • Backlit LCD Screen

SPECIFICATIONS
Supply Voltage: 18 to 30VDC
Module Hand Held Remote
Power (W) @ Min. 0.6W 1.3W 1.3W
24VDC Max. 2.3W 3.0W 3.0W
Current (mA) @ Min. 20mA 50mA 50mA
24VDC Max. 80mA 110mA 110mA
In. 3 x 5.1 x 1.21 4.1 x 5.3 x 2.4 5.5 x 5.9 x 3.5
Dimensions (WHD)
Mm. 98 x 130 x 30 105 x 135 x 60 140 x 150 x 90
Terminal connector to Head 15 pin D-type connector. VESDAnet RS485 VESDAnet field wiring.
Connections Processor Card or to expansion cable required connect to detector To Screw terminal blocks (30-12
connector on another VESDA device or remote VESDAnet socket AWG, 0.2-2.5mm2)

Screen Display Size: 2.75in x 1.45in (70mm x 37mm), full graphic display, large characters, 8
lines, 21 characters per line, adjustable backlit screen with contrast control
Inactivity Time Out: 10 minutes (defaults to log on screen). Beeps at 1 minutes and then 15
seconds before logoff
Push Button Keys: 2 rows x 4 keys, each 0.75in x 0.50in (19mm x 12mm)
Security Access: 3 characters user ID
4 digit personal identification number (PIN) per User Number of User Levels:
10 USR, 3 ADM, 1 DST
Default ID:
USR- User (operator level)
ADM - Administrator (access most functions)
DST - VESDA distributor (access all functions)
Operating Temperature: Ambient: 32° to 103°F (0° to 39°C)
Humidity: 10 - 99% RH, non-condensing
System Functions Accessed: Status & software version
Descriptive Alarm & Faults
Smoke & Flow readings
Push-Button lockout
Display name (21 chars)
Alarm Thresholds (Alert, Action, Fire 1 & Fire 2)
Alarm delays (0-60 seconds)
Day/Night/Weekend/Holiday Options
Event Log (up to 18,000 events)
Zone number and name (21 chars)
Pipes in use (pipe 1 to 4)
Aspirator Speed & Flow control
Confirmation of filter change
Relay configuration
Referencing
AutoLearn™
Addressed Devices: 250 VESDA devices maximum
VESDA Addressed Devices: LaserPLUS Detectors & Displays
LaserSCANNER Detectors & Displays
LaserCOMPACT Detectors & Displays
HLI (High Level Interface) LaserFOCUS with Vnet card
Relay modules Remote Relays
REMOTE MOUNTING BOX

19” SUB RACK


ORDERING INFORMATION
Fike Part Number Manufacturers Part Number Description
Programmer Module (Mounts to
68-026 VSP-001
LaserPLUS or LaserSCANNER)
Programmer with Remote Termination Card,
68-030 VRT-100
No Relay (Remote Mount)

The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied)
is made as to the completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the
right to change designs or specifications without obligation and without further notice. Except as otherwise provided,
all warranties, express or implied, including without limitation any implied warranties of merchantability and fitness for a
particular purpose are expressly excluded.

This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their
respective owners.Your use of this document does not constitute or create a license or any other right to use the name
and/or trademark and/or label.

This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the public,
adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior written consent
of Xtralis

Copyright © Fike Corporation All Rights Reserved.


Form No. V.1.03.01-1 April, 2008 Specifications are subject to change without notice.