CALCULATION OF Vk FOR 1.6 MVA TRANSFORMER NEUTRAL (6.6KV/0.
433KV)
         CT ratio 2500/ 1 CL PS
                                 VK    > 2If (RCT + 2RL)
FAULT LEVEL CALCULATION
6.25% OF IMPEDANCE.
Fault Level for 1.6 MVA with 6.25% of Z is
                                  1.6 MVA x 100                               1.6 MVA x 100
                       =         --------------------------   =            -------------------
                                 % OF IMPEDENCEx1.732x0.433kV              6.25 x 1.732x0.433kV
Fault KA               =         34.135 KA
Fault current (If ) at Secondary side
                        34135
         If     =      -----------
                         2500
                                  If    =    13.654 A
Cable resistance (RL )
         RL for one Kilo meter          =     14.5     (Considering 3Cx2.5 SQ.MM cable)
                                           14.5
          RL for 60 meters (RL)         = ---------- X 60 = 0.87
                                           1000
                                 2RL     =    1.74 
CT Resistance (Rct)
         RCT                            =     2.5 per 1000 turns.
                                              2.5
         RCT for 2500 turns             = ---------X 2500             = 6.25 
                                            1000
505071571.doc
                                RCT    = 6.25 
KNEE VOLTAGE (VK)
         VK     >   2If (RCT + 2RL)
         VK     >   2 x 13.654 x (6.25 +1.74)
         VK     > 218.193
FOR 2500/1 CT                 VK      > 219 V
                            I mag     < 30 mA at VK / 2
505071571.doc