Errata To: 2012 Edition National Electrical Safety Code
Errata To: 2012 Edition National Electrical Safety Code
C2-2012
Errata to
2012 Edition
National Electrical Safety Code®
Correction Sheet
Issued 29 April 2013
Page 2: There is a typographical error in Rule 011A4. The sentence should contain a closing parenthesis.
4. Street and area lights that provide a supply of lumens where these facilities are supplied by
underground or overhead conductors installed and/or maintained under the exclusive control of
utilities (including their authorized contractors or other qualified persons).
Page 33: There is an error in Rule 97D2. The last sentence should refer to Rule 93D3.
Page 90: There is an error in Table 230-1. The heading for Zone 4 should read “Warm islands located at 0 to 25
degrees latitude.”
Page 90: The values in the last two columns of Table 230-1 should not be underlined.
Pages 94 and 98: There is an error in Table 232-1 (m) and Table 232-1 (ft). References to Footnote 25 should be
references to Footnote 26.
Page 96: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (m). Item (f) should
contain “215C4 or.”
(f) Grounded guys, guys meeting Rules 279A1 and 215C4 or 215C5 exposed to 0 to 300 V 2.9
Page 96: There is an error in Footnote 15 that appears at the end of Table 232-1 (m). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.
Page 97: There are errors that appear at the end of Table 232-1 (m). Although Footnote 25 was deleted from the
previous version, it should have been listed as follows. Therefore, the inserted footnote should have been shown as
Footnote 26.
Pages 97, 98, and 99: There is an error in Table 232-1 (ft). The cells in columns 2 and 5 of the header row should
state “(ft)” for feet and not “(m)” for meters.
Page 100: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (ft). Item (f) should
contain “215C4 or.”
(f) Grounded guys, guys meeting Rules 279A1 and 215C4 or 215C5 exposed to 0 to 300 V 9.5
Page 100: There is an error in Footnote 15 that appears at the end of Table 232-1 (ft). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.
Although Footnote 25 was deleted from the previous version, it should have been listed as follows. Therefore, the
inserted footnote should have been shown as Footnote 26.
Page129: There are three errors in Figure 234-4(b). At the top of the figure, the two instances of “H” should read
“A.” The text associated with “A” in the legend should read “B + 5.5 m (18 ft)” and not “V + 5.5 m (18 ft).”
Pages 130, 131, and 132: There is an error in Table 234-1 (m). The cell in column 6 of the header row should
contain “ungrounded equipment cases, 750 V to 22 kV.”
Insulated
communication Unguarded
conductors and rigid live parts,
Unguarded
cables; 0 to 750 V;
rigid live
messengers; noninsulated
parts, over
overhead shield/ communication
750 V to
surge-protection conductors; Supply
22 kV;
wires; ungrounded cables over
ungrounded
grounded guys; Supply equipment 750 V
equipment
ungrounded cables of cases, 0 to meeting Open
cases, 750 V
portions of guys 0 to 750 V 750 V; and Rule 230C2 supply
to 22 kV;
meeting Rules meeting ungrounded or 230C3; conductors,
Clearance of ungrounded
215C4, 215C5, Rule portions of open over 750 V
portions of
and 279A1 230C2 or guys meeting supply to 22 kV
guys meeting
exposed to 230C3 Rules 215C4, conductors, (m)
Rules 215C4,
0 to (m) 215C5, and 0 to
215C5, and
300 V 279A1 750 V
279A1
neutral exposed to (m)
exposed to
conductors open supply
over 750 V
meeting Rule conductors of
to 22 kV
230E1; supply over 300 V to
(m)
cables meeting 750 V
Rule 230C1 (m)
(m)
Pages 130, 131, and 132: There are errors in some of the footnotes that appear in Table 234-1 (m).
Page 131: The ˄ symbol in row 1b(4), first value column of Table 234-1(m), should be replaced with 4.7 since this
is a metric table.
Page 133: There is an error in Footnote 11 that appears at the end of Table 234-1 (m). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.
Although Footnotes 12 and 13 were deleted from the previous version, the remaining footnotes should not have been
renumbered. They should be listed as follows:
Pages 134, 135, and 136: There is an error in Table 234-1 (ft). The cell in column 6 of the header row should
contain “ungrounded equipment cases, 750 V to 22 kV.”
Insulated
communication
conductors and Unguarded
cables; rigid live parts,
Unguarded
messengers; 0 to 750 V;
rigid live
overhead noninsulated
parts, over
shield/ communication
Supply 750 V to
surge- conductors;
cables over 22 kV;
protection Supply ungrounded
750 V ungrounded
wires; cables equipment
meeting equipment Open
grounded guys; of 0 to cases, 0 to
Rule cases, 750 V supply
ungrounded 750 V 750 V; and
230C2 or to 22 kV; conduc-
portions of guys meeting ungrounded
Clearance of 230C3; ungrounded tors, over
meeting Rules Rule portions of
open portions of 750 V to 22
215C4, 215C5, 230C2 guys meeting
supply guys meeting kV
and 279A1 or Rules 215C4,
conduc- Rules 215C4, (ft)
exposed to 230C3 215C5, and
tors, 0 to 215C5, and
0 to (ft) 279A1
750 V 279A1
300 V exposed to
(ft) exposed to
neutral open supply
over 750 V
conductors conductors of
to 22 kV
meeting Rule over 300 V to
(ft)
230E1; supply 750 V
cables meeting (ft)
Rule 230C1
(ft)
Pages 134, 135, and 136: There are errors in some of the footnotes that appear in Table 234-1 (ft).
Page 137: There is an error in Footnote 11 that appears at the end of Table 234-1 (ft). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.
Although Footnotes 12 and 13 were deleted from the previous version, the remaining footnotes should not have been
renumbered. They should be listed as follows:
Page 138: There is a typographical error in Table 234-2 (m). The underscore should be removed from the comma in
the last sentence of the parenthetical statement below the table caption.
Table 234-2—
Clearance of wires, conductors, cables, and unguarded rigid live parts from bridges
(Voltages are phase to ground for effectively grounded circuits and those other circuits where all ground faults
are cleared by promptly de-energizing the faulted section, both initially and following subsequent breaker
operations. See the definitions section for voltages of other systems. Clearances are with no wind displace-
ment except where stated in the footnotes below.
See Rules 234A, 234D1a, and 234H4.)
Page 142: There is an error in Footnote 2 that appears at the end of Table 234-3 (m). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.
Page 143: There is an error in Footnote 2 that appears at the end of Table 234-3 (ft). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.
Page 166: There is an error in Table 235-6 (mm). The cell in column 2 of row 2c should read “75” and not “3.”
Page 222: There is a typographical error in Footnote 3 that appears at the end of Table 261-1. Delete the
strikethrough (“R”) in the last sentence of the footnote.
Wood and reinforced structures shall be replaced or rehabilitated when deterioration reduces the structure strength
to 3/4 of that required when installed. When new or changed facilities modify loads on existing structures, the re-
quired strength shall be based on the revised loadings. If a structure or component is replaced, it shall meet the
strength required by Table 261-1. If a structure or component is rehabilitated, the rehabilitated portions of the
structures shall have strength greater than 3/4 of that required when installed.
Page 230: There is an error in Rule 279A2b(1). The sentence should contain “215C4 or.”
(1) The guy is otherwise insulated to meet the requirements of Rules 215C4 or 215C5
and 279A1.
Page 262: There is a typographical error in Rule 410A3b. The exception and notes are applicable to Rule 410A3
and not Rule 410A3b.
Page 263: There is a typographical error in Table 410-1. Delete the repeated header rows.
Pad-mounted transformers 4 4 6
Network protectors 4
Page 265: There is a typographical error in Table 410-2. The underscore in the cell of column 1 in the first row
should be removed.
Page 280: There is a typographical error in the first sentence of Rule 441. The underlined formatting should be
removed.
Employees shall not approach (within the reach or extended reach), or knowingly permit others to
approach, any exposed ungrounded part normally energized except as permitted by this rule.
Page 280: There is an error in Rule 441A1. “Table 441-4” should be renumbered as “Table 441-2.”
Employees shall not approach or bring any conductive object within the minimum approach
distance listed in Table 441-1 or Table 441-2 or distances as determined by an engineering
analysis to exposed parts unless one of the following is met: