Accredited Standards Committee

C2-2012

Errata to
2012 Edition
National Electrical Safety Code®
Correction Sheet
Issued 29 April 2013

Copyright © 2013 by the Institute of Electrical and Electronics Engineers, Inc.


All rights reserved. Published 2013. Printed in the United States of America.
This correction sheet may be freely reproduced and distributed in order to
maintain the utility and currency of the underlying Standard. This correction
sheet may not be sold, licensed, or otherwise distributed for any commercial
purposes whatsoever. The content of this correction sheet may not be modified.

The following corrections should be made:

Page 2: There is a typographical error in Rule 011A4. The sentence should contain a closing parenthesis.
4. Street and area lights that provide a supply of lumens where these facilities are supplied by
underground or overhead conductors installed and/or maintained under the exclusive control of
utilities (including their authorized contractors or other qualified persons).

Page 33: There is an error in Rule 97D2. The last sentence should refer to Rule 93D3.

Page 90: There is an error in Table 230-1. The heading for Zone 4 should read “Warm islands located at 0 to 25
degrees latitude.”

Page 90: The values in the last two columns of Table 230-1 should not be underlined.

Pages 94 and 98: There is an error in Table 232-1 (m) and Table 232-1 (ft). References to Footnote 25 should be
references to Footnote 26.

Page 96: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (m). Item (f) should
contain “215C4 or.”
(f) Grounded guys, guys meeting Rules 279A1 and 215C4 or 215C5 exposed to 0 to 300 V 2.9

Page 96: There is an error in Footnote 15 that appears at the end of Table 232-1 (m). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.

25 April 2013 Insert to STDPT97085


Accredited Standards Committee
C2-2012

Page 97: There are errors that appear at the end of Table 232-1 (m). Although Footnote 25 was deleted from the
previous version, it should have been listed as follows. Therefore, the inserted footnote should have been shown as
Footnote 26.

This footnote not used in this edition.


When designing a line to accommodate oversized vehicles, these clearance values shall be increased by the difference
between the known height of the oversized vehicle and 4.3 m.

Pages 97, 98, and 99: There is an error in Table 232-1 (ft). The cells in columns 2 and 5 of the header row should
state “(ft)” for feet and not “(m)” for meters.

Supply Trolley and


cables over electrified
750 V railroad contact
Insulated conductors and
meeting Open
communication associated span or
Rule 230C2 supply
conductors and messenger
or 230C3; conductors,
cable; messengers; wires
open supply over 750 V
overhead shield/
Noninsulated conductors, to 22 kV;
surge-protection
communication 0 to unground
wires; grounded
conductors; 750 V ; -ed portions
guys; ungrounded
Nature of surface supply cables ungrounded of guys
portions of guys
underneath wires, of 0 to 750 V portions of meeting
meeting Rules
conductors, or cables meeting Rule guys Rules Over
215C4, 215C5, and
230C2 or meeting 215C4, 0 to 750 V
279A1 exposed to 0
230C3 Rules 215C5, and 750 V to 22
to 300 V ;
(ft) 215C4, 279A1 to kV
neutral conductors
215C5, and exposed to ground to
meeting Rule 230E1;
279A1 750 V to (ft) ground
supply cables
exposed to 22 kV (ft)
meeting Rule 230C1
over 300 V (ft)
(ft)
to
750 V
(ft)

Page 100: There is an error in item (f) of Footnote 10 that appears at the end of Table 232-1 (ft). Item (f) should
contain “215C4 or.”

(f) Grounded guys, guys meeting Rules 279A1 and 215C4 or 215C5 exposed to 0 to 300 V 9.5

Page 100: There is an error in Footnote 15 that appears at the end of Table 232-1 (ft). The word “215C5” should be
replaced with “215C4.”

The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.

Although Footnote 25 was deleted from the previous version, it should have been listed as follows. Therefore, the
inserted footnote should have been shown as Footnote 26.

This footnote not used in this edition.


When designing a line to accommodate oversized vehicles, these clearance values shall be increased by the difference
between the known height of the oversized vehicle and 14 ft.

25 April 2013 Insert to STDPT97085


Accredited Standards Committee
C2-2012

Page129: There are three errors in Figure 234-4(b). At the top of the figure, the two instances of “H” should read
“A.” The text associated with “A” in the legend should read “B + 5.5 m (18 ft)” and not “V + 5.5 m (18 ft).”

Figure 234-4(b)—Clearance envelope for grain bins filled by portable augers,


conveyors, or elevators

25 April 2013 Insert to STDPT97085


Accredited Standards Committee
C2-2012

Pages 130, 131, and 132: There is an error in Table 234-1 (m). The cell in column 6 of the header row should
contain “ungrounded equipment cases, 750 V to 22 kV.”

Insulated
communication Unguarded
conductors and rigid live parts,
Unguarded
cables; 0 to 750 V;
rigid live
messengers; noninsulated
parts, over
overhead shield/ communication
750 V to
surge-protection conductors; Supply
22 kV;
wires; ungrounded cables over
ungrounded
grounded guys; Supply equipment 750 V
equipment
ungrounded cables of cases, 0 to meeting Open
cases, 750 V
portions of guys 0 to 750 V 750 V; and Rule 230C2 supply
to 22 kV;
meeting Rules meeting ungrounded or 230C3; conductors,
Clearance of ungrounded
215C4, 215C5, Rule portions of open over 750 V
portions of
and 279A1 230C2 or guys meeting supply to 22 kV
guys meeting
exposed to 230C3 Rules 215C4, conductors, (m)
Rules 215C4,
0 to (m) 215C5, and 0 to
215C5, and
300 V 279A1 750 V
279A1
neutral exposed to (m)
exposed to
conductors open supply
over 750 V
meeting Rule conductors of
to 22 kV
230E1; supply over 300 V to
(m)
cables meeting 750 V
Rule 230C1 (m)
(m)

Pages 130, 131, and 132: There are errors in some of the footnotes that appear in Table 234-1 (m).

All mentions of Footnote 12 should be Footnote 14.


All mentions of Footnote 13 should be Footnote 15.
All mentions of Footnote 14 should be Footnote 16.
All mentions of Footnote 15 should be Footnote 17.
All mentions of Footnote 16 should be Footnote 18.

Page 131: The ˄ symbol in row 1b(4), first value column of Table 234-1(m), should be replaced with 4.7 since this
is a metric table.

Page 133: There is an error in Footnote 11 that appears at the end of Table 234-1 (m). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.

Although Footnotes 12 and 13 were deleted from the previous version, the remaining footnotes should not have been
renumbered. They should be listed as follows:

This footnote not used in this edition.


This footnote not used in this edition.
For clearances above railings, walls, or parapets around balconies, decks, or roofs, use the clearances required for
row 1b(1). For such clearances where an outside stairway exists to provide access to such balconies, decks, or roofs,
use the clearances required for row 2b(2).
Does not include neutral conductors meeting Rule 230E1.
These clearance values also apply to guy insulators.
It is presumed that a flag or banner is fully extended but that there is no deflection or displacement of the flagpole or
other supporting structure due to wind and that the conductors, cables, or rigid live parts are not displaced by the
wind. The specified clearance is measured to the point of maximum displacement of the banner or flag towards the
overhead utility facility.
When designing a line to accommodate oversized vehicles, these clearance values shall be increased by the difference
between the known height of the oversized vehicle and 4.3 m.

25 April 2013 Insert to STDPT97085


Accredited Standards Committee
C2-2012

Pages 134, 135, and 136: There is an error in Table 234-1 (ft). The cell in column 6 of the header row should
contain “ungrounded equipment cases, 750 V to 22 kV.”

Insulated
communication
conductors and Unguarded
cables; rigid live parts,
Unguarded
messengers; 0 to 750 V;
rigid live
overhead noninsulated
parts, over
shield/ communication
Supply 750 V to
surge- conductors;
cables over 22 kV;
protection Supply ungrounded
750 V ungrounded
wires; cables equipment
meeting equipment Open
grounded guys; of 0 to cases, 0 to
Rule cases, 750 V supply
ungrounded 750 V 750 V; and
230C2 or to 22 kV; conduc-
portions of guys meeting ungrounded
Clearance of 230C3; ungrounded tors, over
meeting Rules Rule portions of
open portions of 750 V to 22
215C4, 215C5, 230C2 guys meeting
supply guys meeting kV
and 279A1 or Rules 215C4,
conduc- Rules 215C4, (ft)
exposed to 230C3 215C5, and
tors, 0 to 215C5, and
0 to (ft) 279A1
750 V 279A1
300 V exposed to
(ft) exposed to
neutral open supply
over 750 V
conductors conductors of
to 22 kV
meeting Rule over 300 V to
(ft)
230E1; supply 750 V
cables meeting (ft)
Rule 230C1
(ft)

Pages 134, 135, and 136: There are errors in some of the footnotes that appear in Table 234-1 (ft).

All mentions of Footnote 12 should be Footnote 14.


All mentions of Footnote 13 should be Footnote 15.
All mentions of Footnote 14 should be Footnote 16.
All mentions of Footnote 15 should be Footnote 17.
All mentions of Footnote 16 should be Footnote 18.

Page 137: There is an error in Footnote 11 that appears at the end of Table 234-1 (ft). The word “215C5” should be
replaced with “215C4.”
The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.

Although Footnotes 12 and 13 were deleted from the previous version, the remaining footnotes should not have been
renumbered. They should be listed as follows:

This footnote not used in this edition.


This footnote not used in this edition.
For clearances above railings, walls, or parapets around balconies, decks, or roofs, use the clearances required for
row 1b(1). For such clearances where an outside stairway exists to provide access to such balconies, decks, or roofs,
use the clearances required for row 2b(2).
Does not include neutral conductors meeting Rule 230E1.
These clearance values also apply to guy insulators.
It is presumed that a flag or banner is fully extended but that there is no deflection or displacement of the flagpole or
other supporting structure due to wind and that the conductors, cables, or rigid live parts are not displaced by the
wind. The specified clearance is measured to the point of maximum displacement of the banner or flag towards the
overhead utility facility.
When designing a line to accommodate oversized vehicles, these clearance values shall be increased by the difference
between the known height of the oversized vehicle and 14 ft.

25 April 2013 Insert to STDPT97085


Accredited Standards Committee
C2-2012

Page 138: There is a typographical error in Table 234-2 (m). The underscore should be removed from the comma in
the last sentence of the parenthetical statement below the table caption.

Table 234-2—
Clearance of wires, conductors, cables, and unguarded rigid live parts from bridges
(Voltages are phase to ground for effectively grounded circuits and those other circuits where all ground faults
are cleared by promptly de-energizing the faulted section, both initially and following subsequent breaker
operations. See the definitions section for voltages of other systems. Clearances are with no wind displace-
ment except where stated in the footnotes below.
See Rules 234A, 234D1a, and 234H4.)

Page 142: There is an error in Footnote 2 that appears at the end of Table 234-3 (m). The word “215C5” should be
replaced with “215C4.”

The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.

Page 143: There is an error in Footnote 2 that appears at the end of Table 234-3 (ft). The word “215C5” should be
replaced with “215C4.”

The portion of anchor guys below the lowest insulator meeting Rules 279A1 and 215C4 may have the same clearance
as grounded guys.

Page 166: There is an error in Table 235-6 (mm). The cell in column 2 of row 2c should read “75” and not “3.”

c. All other 75 150 150 150 150 plus 10 580 plus 10


per kV per kV
in excess of in excess of
8.7 kV 50 kV

Page 222: There is a typographical error in Footnote 3 that appears at the end of Table 261-1. Delete the
strikethrough (“R”) in the last sentence of the footnote.

Wood and reinforced structures shall be replaced or rehabilitated when deterioration reduces the structure strength
to 3/4 of that required when installed. When new or changed facilities modify loads on existing structures, the re-
quired strength shall be based on the revised loadings. If a structure or component is replaced, it shall meet the
strength required by Table 261-1. If a structure or component is rehabilitated, the rehabilitated portions of the
structures shall have strength greater than 3/4 of that required when installed.

Page 230: There is an error in Rule 279A2b(1). The sentence should contain “215C4 or.”

(1) The guy is otherwise insulated to meet the requirements of Rules 215C4 or 215C5
and 279A1.

25 April 2013 Insert to STDPT97085


Accredited Standards Committee
C2-2012

Page 262: There is a typographical error in Rule 410A3b. The exception and notes are applicable to Rule 410A3
and not Rule 410A3b.

410. General requirements


A. General
3. The employer shall ensure that an assessment is performed to determine potential exposure to
an electric arc for employees who work on or near energized lines, parts, or equipment.
If the assessment determines potential employee exposure, clothing made from acetate, nylon,
polyester, or polypropylene shall not be worn, unless arc rated.
If the assessment determines a potential employee exposure greater than 2 cal/cm2 exists (see
Neal, Bingham, and Doughty [B63]), the employer shall:
a. Perform a detailed arc hazard analysis, or use Table 410-1, 410-2, or 410-3 to determine
the effective arc rating of clothing or a clothing system to be worn by employees working
on or near energized lines, parts, or equipment at voltages 50 V to 800 000 V.
The arc hazard analysis shall include a calculation of the estimated arc energy based on
the available fault current, the duration of the arc (cycles), and the distance from the arc to
the employee.
b. Require employees to wear clothing or a clothing system with an effective arc rating not
less than the anticipated level of arc energy.
EXCEPTION: If the clothing or clothing system required by this rule has the potential to create additional
or greater hazards than the possible exposure to the heat energy of the electric arc, then clothing or a
clothing system with an effective arc rating less than that required by the this rule may be worn.
NOTE 1: Assessments performed to determine potential exposure to an electric arc consider the affected
employee’s assigned tasks and/or work activities.
NOTE 2: A clothing system (multiple layers) that includes an outer layer of flame resistant material and
an inner layer of non-flame resistant natural fiber material has been shown to block more heat than a
single layer. The effect of the combination of these multiple layers may be referred to as the effective arc
rating (e.g., EBT, ATPV).
NOTE 3: Engineering controls can be utilized to reduce arc energy levels and work practices can be
utilized to reduce exposure levels.

25 April 2013 Insert to STDPT97085


Accredited Standards Committee
C2-2012

Page 263: There is a typographical error in Table 410-1. Delete the repeated header rows.

Nominal voltage range and cal/cm2


Equipment type
50 V to 250 V 251 V to 600 V 601 V to 1000 V

Self-contained meters / cabinets 4 20 30

Pad-mounted transformers 4 4 6

CT meters and control wiring 4 4 6

Metal-clad switchgear / motor control 8 40 60


centers

Pedestals / pull boxes / hand holes 4 8 12

Open air (includes lines) 4 4 6

Nominal voltage range and cal/cm2


Equipment type
50 V to 250 V 251 V to 600 V 601 V to 1000 V

Network protectors 4

Panel boards—single phase (all) / 4 8 12


three phase (≤100 A)

Panel boards—three phase (>100 A) 4

Page 265: There is a typographical error in Table 410-2. The underscore in the cell of column 1 in the first row
should be removed.

1.1 to 15 5 46.5 93.0 139.5

Page 280: There is a typographical error in the first sentence of Rule 441. The underlined formatting should be
removed.

Employees shall not approach (within the reach or extended reach), or knowingly permit others to
approach, any exposed ungrounded part normally energized except as permitted by this rule.

Page 280: There is an error in Rule 441A1. “Table 441-4” should be renumbered as “Table 441-2.”

Employees shall not approach or bring any conductive object within the minimum approach
distance listed in Table 441-1 or Table 441-2 or distances as determined by an engineering
analysis to exposed parts unless one of the following is met:

25 April 2013 Insert to STDPT97085