0% found this document useful (0 votes)
156 views19 pages

IEC-61850 Transformer Protection Testing

This document discusses testing an IEC 61850 sampled value-based transformer differential protection scheme. It presents three test scenarios: 1) with analog signals on both transformer windings, 2) with sampled value streams from merging units on both windings, and 3) a hybrid approach with analog on one winding and sampled values on the other. The protection relay performance is compared across scenarios. Test results are analyzed in detail, and recommendations are provided based on the comparison with traditional analog differential protection as a benchmark. Maintaining accurate time synchronization is crucial for sampled value-based schemes.

Uploaded by

386
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
156 views19 pages

IEC-61850 Transformer Protection Testing

This document discusses testing an IEC 61850 sampled value-based transformer differential protection scheme. It presents three test scenarios: 1) with analog signals on both transformer windings, 2) with sampled value streams from merging units on both windings, and 3) a hybrid approach with analog on one winding and sampled values on the other. The protection relay performance is compared across scenarios. Test results are analyzed in detail, and recommendations are provided based on the comparison with traditional analog differential protection as a benchmark. Maintaining accurate time synchronization is crucial for sampled value-based schemes.

Uploaded by

386
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/336878700

Testing IEC-61850 Sampled Values-Based Transformer Differential Protection


Scheme

Conference Paper · October 2019

CITATIONS READS

0 33

4 authors, including:

Dinesh Baradi
North Carolina State University
6 PUBLICATIONS   0 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Flex Parse View project

All content following this page was uploaded by Dinesh Baradi on 29 October 2019.

The user has requested enhancement of the downloaded file.


Testing IEC-61850 Sampled Values-Based Transformer Differential Protection Scheme
Mohit Sharma, Lam Nguyen, Sughosh Kuber
Mohit.Sharma@megger.com, Lam.Nguyen@megger.com, Sughosh.Kuber@megger.com
Megger
Dinesh Baradi
dinesh.baradi@us.abb.com
ABB Inc.
US
Abstract -
Following the successful implementation of IEC 61850 at station level over the last decade and
enough user-experience on the standard, the significance of process-oriented communication
using process bus is on an exponential rise. One of the key components of a process bus is
information exchange among the devices through Sampled Values. Sampled Values (SV) are
used for transmitting digitized values of currents and voltages on ethernet frames. With increase
in industry acceptance of SV compliant protective relays, there is a crucial need for testing these
relays and systems to ensure they meet operational and commissioning standards.
Functional testing of SV-based protective relays with the help of a test equipment that can publish
SV streams can be seen as a first step. This paper will discuss in detail on how to test through
fault conditions, pick-up, slope characteristics, and harmonic restraints on a transformer
differential relay that utilizes process bus to subscribe to current samples. Additionally, this paper
will also discuss the effect of network anomaly and the importance of time synchronization in a
process bus-based transformer differential scheme.
Index Terms—Transformer Differential Protection, Process Bus, Hybrid Protection,
Centralized Protection, IEC 61850 9-2 Sampled Values, Nyquist Shannon theory.
I. INTRODUCTION
Transformer Differential Protection (IEC: PTDF, ANSI: 87T) that operates on dual-slope
characteristic is almost ubiquitous and its principles are well proven for various operating
scenarios. While the low-stage (restrained) element of the 87T can provide security against CT
mismatch and transformer tap changer errors and, in some cases, even CT saturation caused as
an effect of through faults of large magnitude, the high-stage (unrestrained) element provides
dependability for in-zone faults. Even order harmonic detection to inhibit blocking of low-stage
has been quite popular method to detect magnetizing in-rush conditions. Out of all the even
harmonics, 2nd harmonics are the most prevalent. Because of this fact, the paper will focus only
on 2nd harmonic restraint.
In modern day digital substation environment with the implementation of IEC 61850 9-2 (Ed.2),
several process bus driven architectures are proposed that provide significant reduction in copper
wiring, facilitate ease of maintenance, thereby providing reduction in capital expenditure as well
as operational benefits. In any process-bus architecture, a merging unit aggregates analogue and
discrete signals and publishes digitized streams to various protection & control devices. This
paper strives to provide findings on the performance of 87T protection element operation that
utilizes sampled values (SV) and compares the performance with 87T element wired to
conventional CTs. In addition, certain recommendations are put forth for consideration while
designing fully process bus driven protection and control systems as well as hybrid systems that
partially utilize process bus data while still relying on conventional as well as non-conventional
instrument transformer connections.
Most internal functions of a microprocessor relays can be represented with a block diagram
represented in Fig. 1. Protection, communication, data logging and control functions are
performed by Central Processing Unit (CPU), in some cases the communication processing may
be performed by a different CPU.
Internal
Transducers

Analogue Signal Analog to Digital signal


Processing (Filters, Digital processing (DSP),
amplifiers etc.) converter CPU etc.

Fig. 1: Microprocessor relay functions

In process bus systems, the protection and other functions are performed remotely, and the
functions can be represented as shown in Fig. 2.
Time
Synchronization
source

Internal Protection Relay


Transducers

Analogue Signal Analog to


Processing (Filters, Digital
Merging Unit amplifiers etc.) converter
Internal
Transducers

Analogue Signal Analog to


Processing (Filters, Digital Process Bus
amplifiers etc.) converter Digital signal processing
(DSP), CPU etc.

Fig. 2: Process Bus systems

With digitization occurring at merging unit and subsequent re-sampling occurring at protection
relay, high accuracy time source is required to accurately sample and utilize data for protection.
Timing source have evolved from 1PPS to IEEE 1588v2 and several other means are available
which utilize GPS/ Glonass constellation as time reference.
IEC 61850 9-2 LE implementation mandates 80 samples per cycle that translates to 4800
samples per second for 60 Hz system, and 4000 samples per second for 50 Hz system. IEC
61850 9-2 LE requires PPS to be used as timing source protocol. However, with the acceptance
of IEEE 1588v2 across the industry due to its benefits over 1PPS & IRIG-B such as its availability
on managed ethernet switches, several process bus systems are utilizing it as a de-facto standard
for time synchronization.
An IEEE-1588 enabled switch can be either a transparent clock (TC) or a boundary clock (BC).
Using it as a transparent clock, the switch can monitor the ingress and egress PTP message and
provide hardware timestamping, thereby publish the time delta in correction field. The ordinary
clocks can utilize the correction field data and apply any offset to their respective internal clocks,
hence achieving greater degree if accuracy with respect to the Grandmaster clock (GMC)/ Master
clock.
Due to a high accuracy time synchronization source requirement for Sampled Value based
protection applications, in this paper the protection relay itself used to synchronize the merging
unit(s) and test set by means of IEEE1588 – Precision Time protocol (PTP) and no GPS enabled
satellite clock were utilized. This setup provides a proof-of-concept that in the event a
Grandmaster clock source is unavailable, the relay can serve as a backup Master clock.
The paper is divided into the following sections -
a) Test Scenarios and system Parameters – In this section, three scenarios based on the
system design are discussed - i) analog signals on both windings of 87T, ii) SV streams from
merging units on both windings of 87T and iii) hybrid of analog signals and merging unit (SV
streams) on either winding of 87T. The behavior of protective relay performance is compared in
each case. Protective relay settings considered as base reference are also provided.

b) Traditional Transformer Differential Vs SV Based Differential: Theory of Operation – In this


section, theory of operation behind the considered transformer differential scheme is explained.
Details of test set up used for each scenario is provided along with the calculations of test values
used for each test type. Test results are provided for up to five tests under each test type and
subsequently analyzed.

c) Test Analysis and Results – This section will cover the results for all the test scenarios and
case types and a detailed analysis will be done

d) Recommendations and Conclusion – Based on the test results, a comparison is drawn


between the performance of various scenarios and test types keeping results of traditional analog
differential as a benchmark. Additionally, a GOOSE data attribute programmed for 87T trip was
compared against the dedicated IED GOOSE trip signal for the scenario with hybrid signals to
validate the performance and provide recommendations.

II. TEST SCENARIO AND SYSTEM PARAMETERS


Fig. 3 shows the transformer under consideration for which the protection functions under test are
highlighted. The CT Ratios are arbitrarily chosen, and the transformer construction is Delta-Wye
grounded with phase shift of 30o with primary side leading.
52

3
A 51P 50P-1 50P-3 49T
(1)
B 600:5A
50
46
BF

52
87T
Dyn1
69.00/ REF
36.5kV Δ 50G-2 (Low
Z)
ONAN
40 MVA
Y
51N
52

50
51P 50P-1 50P-3 46
BF

2000:5A
(2)
3

52

Fig. 3: Scenario: 1- Traditional Analog Differential Scheme

Using these system parameters two additional test cases are derived which utilize merging units
to publish SV streams. Fig. 4 shows MU_9201 and MU_9202 current merging units which publish
SV Streams to the 87T and the Fig. 5 shows only MU_9201 publishing SV stream & a bushing
CT that are utilized for 87T Protection, which represents hybrid protection systems.
Process Bus
52 MU
Merging Unit

C
MU 51P 50P-1 50P-3 49T
3 9202
A
(1)
50
B 46
BF

52
87T
Dyn1
69.00/ REF
36.5kV Δ 50G-2
(Low Z)
ONAN
40 MVA
Y
51N
52

50
51P 50P-1 50P-3 46
BF

(2) MU
9201
3

52

Fig. 4: Scenario: 2 - SV Based Differential Scheme


Process Bus

MU Merging Unit

52 3I Low Power
Current
Sensor

C
51P 50P-1 50P-3 49T
3
A
(1)
50
B 46
BF

52
87T
Dyn1
69.00/ REF
36.5kV Δ 50G-2
(Low Z)
ONAN
40 MVA
Y
51N
52

50
51P 50P-1 50P-3 46
BF

(2) 3I MU
9201

52

Fig. 5: Scenario: 3: Hybrid Differential Scheme

Scenario: 3 presents challenges to the sampling and filtering mechanics in the relay and the test
results are compared with Scenario:1.
A. Multi-Rate sampling
To comprehend the execution of Scenario: 3, it is crucial to understand the concept of multi-rate
sampling. A protection relay may receive current and voltage data from different secondary
instruments – conventional instrument transformers (CIT), non-conventional instrument
transformers (NCIT) as well as merging units which are connected to CIT and NCIT. Protection
relays may need to accommodate all different types of sampling frequencies from different current
and voltage sources. For instance, per IEC 60044-8, the rated value of NCIT’s output data rate
can be 1000Hz, 2400Hz or 4000Hz (for 50Hz systems). A merging unit per IEC 61850 9-2
publishes SV stream at 80 samples per power system cycle which translates to 5 Mbit/sec traffic
on ethernet port of the subscriber. Protection relays receiving this data must be able to sample/
re-sample phasors by deriving fundamental frequency, harmonic content. A continuous digital low
pass filter based on time domain continuous finite impulse response filter can be used. However,
all techniques would still need to adhere to the Shannon-Nyquist theorem, which states that the
sampling frequency should be at least twice the highest frequency contained in the signal, in
mathematical terms:
fs ≥ 2 fc
fs – sampling frequency
fc – high frequency contained in the signal
NCIT are known to provide wide range of harmonic content and a merging unit connected to NCIT
should also be able to adhere to Shannon-Nyquist theory if it were to be publish SV streams with
greater resolution of harmonic content which can be utilized by protection relay for purpose of
filtering power system transients.
B. Settings
Considering the CT ratio correction are 1.0 on both sides of the winding, the settings identified in
Fig. 6 are utilized for all test cases. The settings are programmed in terms of %Ir which indicates
the percentage of rated current. To the plot between Id (diff. current) Vs. Ib (biasing current) is
shown to the right-hand side of the figure. The operation of the 87T is verified against this to
ensure erroneous operations are identified.
Fig. 6: Settings & 87T Operation Characteristics

III. TRADITIONAL TRANSFORMER DIFFERENTIAL VS SV BASED TRANSFORMER DIFFERENTIAL:


THEORY OF OPERATION

A. Implementation of Traditional Transformer Differential


As discussed earlier, the transformer differential protection that has been considered in this paper
uses a two staged percent differential scheme.
The biased low stage provides a fast clearance of faults while remaining stable with high currents
passing through the protected zone increasing errors on current measuring. The second harmonic
restraint ensures that the low stage does not operate due to the transformer inrush currents. The
fifth harmonic restraint ensures that the low stage does not operate on apparent differential
current caused by a harmless transformer over-excitation.
The instantaneous high stage provides a very fast clearance of severe faults with a high
differential current regardless of their harmonics.

Both elements – low staged and high staged – operate phase-wise on a difference of incoming
and outgoing currents. The differential current Id is a vector sum of winding-1 (Iw1) and winding-
2 (Iw2) currents.
Id = |Iw1 + Iw2|
The stabilizing current Ibias (Ib) of the protection relay in question uses the formula:
Ib = |Iw1 − Iw2| /2

Fig. 7 provides the parameters that were used in this example. The calculated currents and phase
angles to be injected are shown below.
Low Stage Minimum Differential Pickup = 5% x Rated current, since the rated current is
considered equal to the nominal current.
Low Stage Minimum Differential Pickup= 5% x 5A (Secondary)
= 0.25 Amps
High Stage Unrestrained Differential Pick-up = 500% x 5 = 25 Amps (Secondary)

Dyn1
69.00/
36.5kV
ONAN
40 MVA

87T

Fig. 7: Differential Scheme Under Test

Based on Fig. 7, it is evident that there has to be 180-degree phase shift on winding-2 currents
with respect to winding-1 to simulate an in-zone fault condition. In addition to that, the effect of
phase shift due to the transformer connection has to be considered. A connection type of Dyn1
will introduce 30 degrees on winding-2. Test phase angles should add -30 degrees on winding-2.

Test Case-1: Low Staged Differential Trip for an In-Zone Fault


To obtain trip time, the test was run with pre-fault and fault states. During the pre-fault, the system
under normal load conditions was simulated for 3 seconds. A low staged differential condition was
simulated in the fault state. Currents I1, I2, and I3 were injected into winding-1 whereas I4, I5,
and I6 into winding-2 respectively.
Fig. 8: Pre-Fault State Fig. 9: Fault State

Test Case-2: High Staged Differential Trip for an In-Zone Fault


Similar to Case-1, both pre-fault and fault states were simulated to reflect an actual power system
phenomenon. A high staged differential condition was simulated in the fault state.

Fig. 10: Pre-Fault State Fig. 11: Fault State

Test Case-3: 2nd Harmonic Restraint Element Operation for Magnetizing Inrush Condition

Fig. 12: Pre-Fault State Fig. 13: Fault State

TEST SYSTEM SET-UP


Timing tests for 87T operations were recorded using analogue (hard-wired) I/O, timing tests for
2nd harmonic restrain pickup were recorded internally in the protection relay. Binary input was
programmed to start oscillographic recorder when 2nd harmonic currents were injected. The time
delta was calculated when 2nd Harmonic block picked up. Considering that the harmonic restrains
are internally utilized within the 87T element, utilizing a binary input wired to test set to calculate
time delta would add additional delays. Hence a simplified test methodology was utilized. A high-
speed output was mapped to 87T trip in the protection relay.

Protection Relay
(Device under Test)

BIO CT inputs
BIO – Binary
Input Output
channel

3 3
BIO
Test Set

Fig. 14: Test Setup- Scenario -1

B. Implementation of SV-Based Transformer Differential (Scenario:2)


Similar to traditional scheme with purely analog inputs, this test scenario employed Sampled
Value streams (SV) and GOOSE messages to measure the performance of the relay. For time
synchronization purposes, IEEE 1588 protocol was selected. The relay served as the boundary
clock (without GPS tracking), and the test equipment synchronized to the relay. Being IEEE 1588-
synchronized to the relay, the test set simulated two Merging Units by publishing two SV streams.
The first stream simulated the three currents from the primary winding, and the second stream
simulated the three currents from the secondary winding. With the help of a Managed Network
Switch, all the SV frames and GOOSE traffics were exchanged between the test set and the
relay. The relay subscribed to two SV streams and was programmed to publish the GOOSE
carrying trip command to the test set.
Once the network setting up was done, testing became as seamless as it was with analog
injection. Two Sampled Values streams carrying prefault currents for 5 seconds were injected
into the network. The test set then changed quantities to a fault condition and started the timer.
The relay tripped and sent out a trip GOOSE. Monitoring the trip GOOSE from the relay, the test
set stopped the timer and reversed the fault quantities to normalized quantities. Test times are
recorded below:
Test System Set-up
Testing for this case involved using a test set that was synchronized to the protection relay using
IEEE 1588 PTP and published SV Streams. IEC 61850 GOOSE message was used as a trip
signal from the relay to the test equipment to perform harmonic restraint and 87T timing tests. A
general Trip LD0.TR2PTRC1.Op.general (General Protection Trip) was mapped to publish Trip
when 87T tripped.
Protection Relay
(Device under Test) Boundary
NIC – Clock
Network BIO NIC Port
Interface
Card

Managed Network Transparent


Switch clock

Ordinary
clock
NIC Port
Test Set

Fig. 15: Test Setup – Scenario -2

B. Implementation of Hybrid Transformer Differential (Scenario-3)


This test scenario employed the hybrid signals. To achieve this objective, the test set mainly
injected 6 analog currents. Three of the six analog currents were connected straight into the relay
as if they were from the primary winding of the transformer. The other three analog currents were
connected into the Merging Unit (MU). Synchronized to the relay via IEEE 1588, the MU translated
the three analog currents into one SV stream and published it to the relay. Effectively, the relay
took three analog currents and three SV-based currents as input for transformer differential
protection. The test set is subscribed to the trip GOOSE being sent out when the simulated fault
condition occurred.

Considering the hybrid nature of this setup, an analogue method – like what was utilized in
Scenario- 1 it was decided to hard-wire contacts to measure the 87T trip time. One set of test
currents were injected into protection relay and another set was injected into the merging unit. A
high-speed output on relay was programmed to trip on 87T operate and was wired to the binary
input of the test set.
NIC –
Network Protection Relay
Interface (Device under Test) Boundary
Card CT Clock
Input BIO
BIO NIC Port
Ordinary
Transparent clock
clock
Managed Network MU_9202
Switch

Ordinary
3 clock
BIO NIC Port
Test Set
3

Fig. 16: Test Setup – Scenario 3

IV. TEST RESULTS AND ANALYSIS


Timing tests were performed for each test case, these tests include five iterations for restrained
operations and five iterations for unrestrained operation. Five additional timing tests were run to
determine the 2nd harmonic pickup timing. A managed network switch with hardware PTP
implementation was set to be a transparent clock and the protection relay was set to be a
boundary clock to synchronize the other merging unit(s) and Test set. Traffic prioritization and
network segregation were not performed.
Test currents were injected at random phase angle in all the iterations. For the restrained case
the differential current of 2 time the set value was injected and for unrestrained cases a differential
current of 5.8 times of the rated current was inject.
Table 1: Results Test Scenario 1

87T Trip Time (msec) 2nd Harmonic


detection (msec)

Restrained Unrestrained
Scenario- 1 Test 1 25.7 20.1 4.167
Test 2 27.7 20.4 6.25
Test 3 28.1 20.7 6.25
Test 4 24.1 20.4 6.25
Test 5 28.8 19.1 4.167
Average 26.68 20.14 5.41
Table 2: Results Test Scenario2

2nd Harmonic
87T Trip Time (msec)
detection (msec)
Restrained Unrestrained
Test 1 29.5 19.6 5.1
Scenario - 2
Test 2 28.6 17.6 5.3
Test 3 28.0 19.8 4.9
Test 4 29.9 17.4 4.9
Test 5 30.1 18.2 4.0
Average 29.22 18.52 4.84

It is observed that when compared to scenario 1, the deviation of the average for restrained pickup
is within 2.5 ms and well within the published maximum operation times of the protection relay.
This minor deviation can be attributed a few factors – no prioritization and segmentation between
GOOSE and SV traffic and the fault was injected at an arbitrary phase angle.

Table 3: Results Test Scenario- 3

2nd Harmonic
87T Trip Time (msec)
detection (msec)
Restrained Unrestrained
Test1 27.1 20.9 8.3
Scenario 3
Test 2 28.4 20.6 8.5
Test3 25.6 21.1 7.4
Test 4 27.8 20.9 8.6
Test5 28.5 21.1 7.9
Average 27.48 20.92 8.14

The deviation in average for restrained pickup between scenario 3 and scenario 1 is marginally
better in scenario 3. It was observed that the waveform from merging unit was re-sampled and
aligned in the protection relay to provide dependable protection. The average of the harmonic
restrain pickup was observed to be 2.72 msec faster than Scenario- 3, this is attributed to the
additional security built into the protection relay algorithm to accurately detect magnetizing inrush
by taking he ratio of the 2nd harmonic differential current with the fundamental differential current.
Considering that deviation in average trip times are within 1.5 msec, it is noted that harmonic
restrain doesn’t compromise the dependability of the protection as the protection is still operating
within published margins.
A line graph is plotted for restrained trip times for visual comparison in Graph 1, it is noted that for
biggest deviation is observed for iteration 4 of case 2 and the Comtrade capture for this case
shows that unrestrained element operated in 21.35 msec. The additional time observed is the
processing time for GOOSE publishing, network propagation delay and GOOSE subscription
time.

Restrained Trip times (msec)


35

30

25

20

15

10

0
Case 1 Case 2 Case 3 Case 4 Case 5
Restrained

87T Trip Time (msec) Scenario 2 87T Trip Time (msec) Scenario 3
87T Trip Time (msec) Scenario 1

Graph 1: Restrained Trip Times (msec)


Fig. 17: Comtrade Case 2 – Iteration 4

V. RECOMMENDATIONS
Performance of the network and redundancy are critical to the overall performance of protection
and control systems that are process bus driven. Traffic prioritization and management on
network switches becomes critical for guaranteed service to protection traffic. [4] is a technical
report which documents the guidelines for communication network and systems engineering.
Methods for testing loss of packet(s) and their impact on protection and control systems need
further refinement. IEC 61850 station bus engineering also requires due engineering diligence.
While performing testing on case 3, an additional GOOSE data attribute
LD0.TR2HPDIF1.Op.general (unrestrained 87T trip) was used for timing tests and results are
compared against TR2PTC GOOSE trip
Table 4: TR2PTRC vs TR2HPIF Timing

TR2PTC GOOSE timing (msec) TR2HPDIF - GOOSE timing (msec)


Iteration 1 20.0 18.3
Iteration 2 19.7 18.3
Iteration 3 20.4 18.3
Iteration 4 20.0 19.8
Iteration 5 19.9 19.1

TR2HPDIF operating times are marginally better, since the TR2HPDIF had a higher execution
priority in the relay.
VI. CONCLUSIONS
Fundamental concepts of using SV for protection of fully digital transformer differential protection
as well as semi-digital (hybrid) protection are proven by test cases and corroborated with results
and COMTRADE analysis. It is observed that the relay protection can propagate communication
signals (GOOSE) within 5msec and consequences of loss of Grandmaster clock synchronization
can be mitigated by using a relay as a back-up master clock. The average operation time of the
protection (87T) was found to be well within the relay manufacturer published data regardless of
whether the input was derived from conventional CT’s or merging unit as analyzed by comparing
results from Scenario: 1 with Scenario: 2 and Scenario: 3 individually.
VII. REFERENCES
1. Sub- Nyquist Rate ADC Sampling in Digital Relays and PMUs: Advantages and
Disadvantages. [Sarasij Das, IISC Bangalore]
2. Viability and assessment of central protection and control system architectures in MV
Substations [Bruno De Oliveira E Sousa, Janne Starck, Jani Valtari, ABB]
3. Centralized Protection & Control, IEEE PES PSRC Report of Working Group K15 of
Substation Protection Subcommittee.
4. IEC 61850-90-4 [Technical Report] – Communication networks and systems for power
utility automation – Network Engineering guidelines.

View publication stats

You might also like