Overvoltage protection
(surge arrester)
Agenda
●Choose the best surge protection.
●Install overvoltage protection.
●Choose the best upstream protection for a surge arrester.
●Installation rules.
  Electrical overvoltage,
  unique characteristics
            Sources                                Characteristics
                                                                                       Lightning
● Lightning                                        ● Ultra-rapid transient
                                                     phenomenon. Unit        Voltage
                                                     of measurement =
                                                     kV/ µs                                        Operations
                                                   ● Highly destructive
                                                     energy.
● Overvoltage                                      ● Repetitive
  generated by                                       phenomenon
  operations or                                      leading to
                                                                                                                    Irms
  incidents on the                                   premature aging.
  network.
                                                   ● Malfunction which
                                                     may even result in
                                                     permanent damage.
 Schneider Electric – Surge Protection – 03/2010                                                                3
 Lightning and its consequences
 ●The main effect of lightning is electrical      overvoltage which
     exposes the electrical installations to a serious risk of:
                                                  ● malfunction,
                                                  ● destruction of equipment,
                                                  ● unavailability of production tools,
                                                  ● etc.
                         The overvoltages come either from the electricity
                         network from the earth.
Schneider Electric – Surge Protection – 03/2010                                           4
  The damage caused by lightning
  ● 90% of sockets power sensitive equipment and an overvoltage
        can damage them (Total values estimated amount = €3,650).
                                                                                  Living-room: TV, home
                                                   Bedroom: computer, hi-fi,     cinema, rolling shutters,
                                                      telephone (€650)            air-conditioning, ADSL
                                                                                     modem (€1,000)
                                                                               Kitchen: microwave oven,
                                                                               oven, fridge, dishwasher
 Laundry: freezer, washing                                                               (€500)
machine, dryer, boiler, alarm
         (€1,500)
 Schneider Electric – Surge Protection – 03/2010                                                             5
                                            Choose the best
                                            surge protection
Schneider Electric – Surge Protection – 03/2010                6
    A means of protection for every situation
                                  No LPS*                           With LPS*                                   Type of
                         Type 2 surge arrester                               Types 1 and 2 surge arrester        surge
                                                                                                                arrester
                                                                                                            T1: only used
Distance of the                                                                                             when LPS is
loads < 30m                                                                                                 present
                                                                                                            T2: used
                                                                                                            systematically.
                                                                                                            T3: only used in
                                                                                                            addition to a
                                                                                                            T2 (as lower
Distance of the                                                                                             discharge
loads                                                   T3                                                  capacity), if the
> 30m**                                                 T3                                                  loads are more
                                                        T3                                                  than 30m from the
                                         T2                           T1 +         T3
                                                        T3            T2                                    incoming T2 surge
                                                                                                            arrester
                               Types 2 and 3 surge arrester   Types 2, 1 and 3 surge arrester
    * LPS (Lightning Protection System) = lightning rod, meshed cage on buildings)
    ** After 30m (between the surge arrester and the loads) lightning wave reflection phenomena appear
    in the cables.
   Schneider Electric – Surge Protection – 03/2010                                                                            7
  In practice: distance of equipments >30
  metres
Case No.1                 T2
(the most                                          Distance under than 30 metres
common)
                          Mainboard
                       T2 = type 2 surge arrester
                          T2
Case No.2                                          Distance of more than 30
                                                   metres
                          Mainboard
                       T2 = type 2 surge arrester
                                                                          T3
                         T2                                             Floor
                                                                        switchboard
                                                                        Install the surge arrester
                         Mainboard                                      as close as possible to the
                                                                        sensitive equipment
   * T2 = type 2 surge arrester, T3 = type 3 surge arrester.
 Schneider Electric – Surge Protection – 03/2010                                                      8
 To summarise
Schneider Electric – Surge Protection – 03/2010   9
                                 Install surge arrester
Schneider Electric – Surge Protection – 03/2010           10
 Location in the switchboard: in parallel
                                                      Incoming
                                                      circuit-
                                                      circuit-breaker
 Lightning                                        *
  current
                                                           Sensitive equipments
 * SPD = Surge Protection Device.
Schneider Electric – Surge Protection – 03/2010                                   11
 Lifetime of the surge arrester
 ●The surge arrester has the same lifetime as the switchboard.
 ●At the end of its life, a thermal protector integrated into the surge
  arrester:
   ●isolate the surge arrester from the rest of the installation.
   ●activates the red end-of-life warning light, indicating that the surge
      arrester needs to be changed.
Schneider Electric – Surge Protection – 03/2010                              12
 The upstream protection of the surge
 arrester
 ●The role of the surge arrester is to drive the lightning current to the
  earth in a very short time (< 350 microseconds).
 ●However, the surge arrester is not intended
                                   to be
     exposed to a permanent overvoltage
     (phase/neutral inversion, or neutral rupture). In this case, it would be
     short-circuited and may damage the switchboard.
 ●A device protecting the surge arrester against short circuits is
  therefore required to ensure the safety of the electrical installation.
                      The surge arrester must be protected
                      upstream by a disconnection               SPD
                      circuit breaker.
Schneider Electric – Surge Protection – 03/2010                                 13
          Choose the best upstream
         protection for a surge arrester
Schneider Electric – Surge Protection – 03/2010   14
 2 aspects must be taken into account
 ● When making your choice, take into account:
         ● lightning current withstand capacity (to avoid nuisance trpping),
         ● short-circuit withstand capacity of the installation (Isc).
     Isc
    25kA                                C60L      C60L   NG125N   NG125N
   15kA                                 C60H      C60H    C60H     C60H
     6kA                                C60N      C60N    C60N     C60N
                                        8kA       20kA     40kA      65kA   Lightning current
 ● E.g. the best disconnection circuit breaker for a breaking capacity of 15kA
   and Imax of 40kA is a C60H.
                      The surge arrester/protection device coordination table is
                      supplied by Schneider              Electric.
Schneider Electric – Surge Protection – 03/2010                                                 15
 Example of Schneider Electric coordination table
Schneider Electric – Surge Protection – 03/2010     16
 Schneider Electric innovates for safe
 coordination and easy installation
 ●Quick PF and Quick PRD include both an upstream circuit breaker
  and a surge arrester, thus ensuring:
   ●no risk of coordination error,
   ●continuity of service.
              Safe
            Efficient
         Easy selection
    Quick PF and Quick PRD
Schneider Electric – Surge Protection – 03/2010                     17
                                            Installation rules
                                The surge arrester is effective
                                only if it is properly installed!
Schneider Electric – Surge Protection – 03/2010                     18
 Installing a surge arrester
 ● Lightning is a phenomenon that generates a high frequency voltage:
         ● The length                         of the cables must be taken into account in cases of high
           frequency
         ● 1 metre of cable crossed by a lightning current generates an overvoltage of 1,000V.
              1000V
                                                                        500V
               U spd                              Load                U spd            Load
              1000V                                  Uload =                              Uload =
                                                     USPD + 2000V                         USPD + 500kV
                      For an effective surge protection, shorten the length of cables.
Schneider Electric – Surge Protection – 03/2010                                                           19
 In practice: consider the intermediate earth
 terminal to shorten cables length
            L1                                                                L1
                                                                  L ≤ 50cm
              L2                                                              L2
                                                                              L3
             L3                                               Intermediate
                                                  Main earth earth terminal
                                                  bar                                     Main earth
        L > 50cm                                                                          bar
                      Mandatory in Standard IEC 60364-5-534:                          L = L1 + L2 + L3
                      ● L (length of cables) < 50cm,
                      ● cable cross-section S < 4mm²(Type 2) and S< 16mm² (Type 1).
Schneider Electric – Surge Protection – 03/2010                                                        20
 Installation in a plastic enclosure
 (e.g. Pragma)
                                                    L1 ~ 12cm
                                                                L1+L2+L3 < 50 cm
                                                  L2 ~ 0cm
                                                  L3 ~ 5cm
  Main incoming earth via the bottom
 (main earth bar and intermediate earth terminal).
Schneider Electric – Surge Protection – 03/2010                                    21
 Installation in a plastic enclosure
 (e.g. Pragma)
                                        L1 ~ 12cm
                                                    L2 ~ 0cm    L1+L2+L3 < 50 cm
                                                    L3 ~ 15cm
 Incoming earth cable via the top
(main earth bar and intermediate earth terminal).
Schneider Electric – Surge Protection – 03/2010                                    22
 Installation in a metal enclosure
 (e.g. Prisma Plus)
 ●Directly on "metal chassis".
 ●Use a lock washer to connect the
  cable to the chassis to give a good
  electrical contact.
                      The installation is possible
                      only if the enclosure complies
                      with standard
                      IEC 60439-1.
Schneider Electric – Surge Protection – 03/2010        23
                            ELECTRICAL DISTRIBUTION PROTECTION
       Protection of people                        Circuit           Protection of sensitive
                                                  protection               equipment
                  Against permanent failure (due to                  Against temporary
                  overcurrent, overload, earth fault)          failure (overvoltage, lightning)
                     In the low-voltage system, the surge arrester is essential to
                     ensure complete protection.
Schneider Electric – Surge Protection – 03/2010                                                   24