Minimum Clearance in Substation:
Voltage        Highest        Lighting          Switching        Minimum Clearance         Safety           Ground
                  Voltage        Impulse           Impulse                                    Clearance(Mt)    Clearance(Mt)
                                 Level             Level
                                 (Kvp)             (Kvp)            Phase-         Phase-
                                                                    Earth          Phase
   11KV           12KV           70                                 0.178          0.229      2.600            3.700
   33KV           36KV           170                                0.320          0.320      2.800            3.700
   132KV          145KV          550                                1.100          1.100      3.700            4.600
                                 650                                1.100          1.100      2.700            4.600
   220KV          245KV          950                                1.900          1.900      4.300            5.500
                                 1050                               1.900          1.900      4.300            5.500
   400KV          420KV          1425              1050(P-E)        3.400          4.200      6.400            8.000 
 Electrical Clearance in Substation:
   Voltage          Height of          Height of        Bay Width            Phase-         BetweenEquipment        Earth
                    I Bay              II Bay           (Mt)                 Phase                                  Wire
                    From               From                                  (Mt)                                   From
                    Ground             Ground                                                                       Ground
                    (Mt)               (Mt)
   132KV            8.0                –                11.0                 3.0            3.0                     10.5
   (Single)
   220KV            12.5               –                18                   4.5            4.5                     15.5
   (Single)
   220KV            18.5               25               25                   4.5            4.5                     28.5
   (Double)
   400KV            15.6               22               22.0                 7.0            >6.0                    30.0
Standard Bay Widths in Meters:
   Voltage                                                     Bay Width (Meter)
   11KV                                               4.7 Meter
   33KV                                               4.7 Meter
   66KV                                               7.6 Meter
   132KV                                              12.2 Meter
   220KV                                              17 Meter
   400KV                                              27 Meter
 Standard Bus and Equipment Elevation
   Voltage                Equipment live Terminal     Main Bus                  Take of Elevation
                          Elevation (Meter)                                     (Meter)
                                                      Low          High
   11 KV/33KV             2.8To 4                     5.5  To6.5   9            6.5To8.5
   66KV                   2.8To 4                     6To8         9To 10.5     9.5
   132KV                  3.7To5                      8To9.5       13.5To14.5   12To12.5
   220KV                  4.9To5.5                    9To13        18.5         15To18.5
   400KV                  8.0                         15.5         –            23
 Phase spacing for strung Bus:
   Voltage                                          Clearance
   11KV                                             1300 mm
   33KV                                             1300 mm
   66KV                                             2200 mm
   132KV                                            3000 mm
   220KV                                            4500 mm
   400KV                                            7000 mm
 Minimum Clearance of Live Parts from Ground:
   Voltage              Minimum Clearance to Ground (Mt)          Section Clearance (Mt)
   11KV                 3.700                                     2.600
   33KV                 3.700                                     2.800
   66KV                 4.600                                     3.000
   132KV                4.600                                     3.500
   220KV                5.500                                     4.300
   400KV                8.000                                     7.000
 Insulator String:
    Voltage              No of Suspension        Length (mm)           No of Disc for Tension   Length in (mm)
                         String                                        String
   66KV                  5                       965                   6                        1070
   132KV                 9                       1255                  10                       1820
   220KV                 14                      1915                  15                       2915
   400KV                 23                      3850                  2 X 23                   5450
 Nominal Span:
   Voltage                                       Normal Span (Meter)
   66KV                                          240-250-275
   132KV                                         315-325-335
   220KV                                         315-325-335
   400KV                                         315-325-335
 Minimum Ground Clearance:
   Voltage                                       Ground (Meter)
   66KV                                          5.5
   132KV                                         6.1
   220KV                                         7.0
   400KV                                                 8.0
   800KV                                                 12.4
 Indoor Substation Minimum Clearances
    Distance                   Descriptions
   0.9 Meter                  Horizontally between any item of equipment and thesubstation wall
   0.6 Meter                  Horizontally between any Two items of equipment
   1.2 Meter                  Horizontally in front of any HV switchgear
 Clearance of Conductor on Tower
   Voltage                    Tower Type        Vertical Space        Horizontal         Total Height From Ground(Mt)
                                                (Mt)                  Space(Mt)
   66KV                       A                 1.03                  4.0                15.91
                              B                 1.03                  4.27               15.42
                              C                 1.22                  4.88               16.24
   132KV                      A                 7.140                 2.17               23.14
                              B                 4.2                   6.29               22.06
                              C                 4.2                   7.15               22.68
                              D                 4.2                   8.8                24.06
   220KV                      A                 5.2                   8.5                28.55
                              B                 5.25                  10.5               29.08
                              C                 6.7                   12.6               31.68
                              D                                                           
 NORMS OF PROTECTION FOR EHV CLASS POWER TRANSFORMERS
   Voltage ratio & capacity           HV Side                    LV Side             Common relays
    132/33/11KV up to 8             3 O/L relays + 1 E/L     2 O/L relays + 1 E/L         Buchholz, OLTC Buchholz, OT, WT
   MVA                              relay                    relay
    132/33/11KV above 8             3 O/L relays + 1 dir.    3 O/L relays + 1 E/L         Differential, Buchholz,
   MVA and below 31.5               E/L relay                relay                        OLTCBuchholz, OT, WT
   MVA  
    132/33KV, 31.5 MVA &            3 O/L relays + 1 dir.    3 O/L relays + 1 E/L         Differential, Over flux,Buchholz,
   above                            E/L relay                relay                        OLTC PRV, OT, WT
    220/33 KV, 31.5MVA &            3 O/L relays + 1 dir.    3 O/L relays + 1 dir.        Differential, Over flux,Buchholz,
   50MVA 220/132KV, 100             E/L relay                relay                        OLTC PRV, OT, WT
   MVA 
    400/220KV 315MVA                3 directional O/L        3 directional O/L            Differential, Over flux,Buchholz,
                                    relays (with dir.        relays (with dir.            OLTC PRV, OT, WT and overload
                                    High set) +1             High set)+1                  (alarm) relay
                                    directional E/L          directional E/L
                                    relays. Restricted       relays. Restricted
                                    E/F relay + 3            E/F relay
                                    Directional O/L
                                    relays for action
 The bottom most portion of any insulator or bushing in service should be at a minimum height of 2500 mm above ground level.
 Location of L.A (From T.C Bushing):
   Voltage                 BIL KV Peak                                     Distance (Mt)
   11KV                    75                                              12
   33KV                    200                                             15
   66KV                    325                                             24
   132KV                   550                                             35
   220KV                   900 To 1050                                     Close To T.C
   400KV                   1425 To 1550