Miniature Circuit Breakers
Miniature Circuit Breakers
© Siemens AG 2016
3/2 Introduction
3
3/7 5SL6, 6000 A
3/9 5SL4, 10000 A
Additional components
3/36 Electrical components
3/41 Mechanical components
Busbars
3/44 5ST standard busbars
3/53 5ST3 busbars acc. to UL 508
3/57 5ST2 distribution blocks
3/61 SIKclip wiring system
Siemens LV 10 · 2016/2017
© Siemens AG 2016
Introduction
■ Overview
Devices Page Application Standards
3
5SL miniature circuit breakers 3/3 For all 0.3 to 63 A applications with B, C and D tripping EN 60898-1
characteristics with a rated breaking capacity of 4500 A,
6000 A und 10000 A acc. to EN 60898-1.
5SY and 5SP miniature circuit 3/13 For all applications from 0.3 to 125 A with a rated EN 60898-1/-2
breakers breaking capacity of 10000 A and 15000 A acc. to EN 60947-2
EN 60898-1. Applications for universal current from UL 1077
0.3 to 63 A, Version 25 kA, acc. to EN 60947-2. CSA 22.2
GB 10963.1/.2
5SJ6. . .-.KS miniature circuit 3/29 For socket outlet and lighting circuits in all building EN 60898-1
breakers, with plug-in terminals installations.
The plug-in terminals offer easy front connection for
manual insertion of conductors, which considerably
reduces mounting times.
5SY miniature circuit breakers, 3/32 For socket outlet and lighting circuits in all building EN 60898-1
1+N in 1 MW installations where a switchable neutral conductor is
required.
The miniature circuit breaker 1+N saves space in the
distribution board.
Additional components 3/36 Auxiliary switches, fault signal contacts, shunt trips,
undervoltage releases for higher system availability,
RC units for personal safety and remote controlled
mechanisms for remote switching.
Busbars 3/44 Busbars in 10 mm2 and 16 mm2 save space in the UL 508
distribution board and time during mounting. Busbars in
2 2
18 mm and 25 mm acc. to UL 508 and CSA.
5SJ4 . . .-.HG miniature circuit 3/63 Miniature circuit breakers can be used as "branch circuit UL 489
breakers acc. to UL 489 and IEC, protection" and are approved for the connection type
and accessories "same polarity" and "opposite polarity" in the
characteristics B, C and D acc. to UL489,
from 0.3 to 63 A.
SHU 5SP3 main miniature circuit 3/74 Voltage-independent selective main miniature circuit DIN VDE 0641-21
breakers breakers (SHU) in the precounter area support
downstream miniature circuit breakers by providing
better current limitation.
■ Overview
The 5SL miniature circuit breakers are intended for use up to To facilitate cable entry, the devices are equipped with rectangu-
6 kA/10 kA. These devices have system features that are lar terminals for the accommodation of pin busbars with cables
characteristic of all Siemens miniature circuit breakers. up to 35 mm2. The rated current range is between 0.3 A and
63 A. The 5SL miniature circuit breakers are available in
They are also suitable for the quick and easy mounting of
3
characteristics B, C and D.
additional components, such as auxiliary switches and fault
signal contacts. The 5SL4 miniature circuit breakers can also be
combined with shunt trips, undervoltage releases and arc fault
detection devices.
■ Benefits
• Effective touch protection when grasping and manually • Easy-to-mount busbar assembly.
operating the latching slide with latch-down option. • Consistent bus mounting concept throughout the Siemens
miniature circuit breaker range.
• Individual devices can be removed from the bus-mounted • The 5SL4 miniature circuit breakers are suitable for the quick
assembly without the use of tools. and easy mounting of arc fault detection devices, auxiliary
switches, fault signal contacts, shunt trips and undervoltage
releases.
■ Technical specifications
5SL3 5SL6 5SL4
Standards EN 60898-1
Approvals See chapter "Appendix"
3 Tripping characteristic
Rated voltage Un V AC
B, C
230/400
B, C, D
Operational voltage
• Min. V AC/DC 24
per pole
• Max. V AC 250/440
V DC/pole 601) 601)2)
Rated breaking capacity
• Icn acc. to IEC/EN 60898-1 kA AC 4.5 6 10
• Icu acc. to IEC/EN 60947-2 kA AC 4.5 6 10
Insulation coordination
• Rated insulation voltage V AC 250/440
• Pollution degree for overvoltage category 2/III
Rated frequency Hz 50/60
Touch protection Acc. to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection IP20 with connected IP40 IP20
conductors, with connected with connected
IP40 in the area of the conductors conductors
handle with distribution
cover
CFC and silicone-free Yes
Conductor cross-sections
• 1-wire
- Solid ( 10 mm2) / stranded ( 16 mm2) mm2 0.75 ... 35
- Finely stranded with non-insulated end sleeve mm2 0.75 ... 25
- Finely stranded with insulated end sleeve mm2 0.75 ... 25
- Finely stranded without end sleeve mm2 1 ... 35
• 2-wire, same cross-section
- Solid ( 10 mm2) / stranded ( 16 mm2) mm2 0.75 ... 10
- Finely stranded with non-insulated end sleeve mm2 0.75 ... 4
- Finely stranded with insulated end sleeve mm2 0.75 ... 4
- Finely stranded without end sleeve mm2 1 ... 4
• 1-wire + busbar (pin thickness 1.5 mm)
- Solid ( 10 mm2) / stranded ( 16 mm2) mm2 10 ... 25
- Finely stranded with non-insulated end sleeve mm2 6 ... 25
- Finely stranded with insulated end sleeve mm2 6 ... 16
Terminals Screw (Pozidriv) 2
• Terminal tightening torque Nm 2.5 ... 3
Mounting position Any
Service life, on average, with rated load 20000 actuations
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45, occasionally +55, -25 ... +55,
max. 95 % humidity max. 95 % humidity
Resistance to climate Acc. to IEC 60068-2-30 6 cycles
1)
The operational voltage 60 V DC/pole takes into account a battery
charging voltage with a peak value of 72 V.
2)
Exempt: Characteristic C: 0.3 ... 1 A, characteristic D: 0.3 ... 2 A.
■ Overview
The 5SL miniature circuit breakers are particularly suitable for
the demands of 4.5 kA and 6 kA applications in infrastructure,
such as residential buildings and small commercial buildings.
3
M)
A MW1) kg
Miniature circuit breakers 6000 A
1P, 230/400 V AC
0.3 1 -- 5SL6114-7 1 1/120 units 1AC 0.165
0.5 -- 5SL6105-7 1 1/120 units 1AC 0.159
1 -- 5SL6101-7 1 1/120 units 1AC 0.148
1.6 -- 5SL6115-7 1 1/120 units 1AC 0.156
2 -- 5SL6102-7 1 1/120 units 1AC 0.125
3 -- 5SL6103-7 1 1/120 units 1AC 0.132
4 -- 5SL6104-7 1 1/120 units 1AC 0.124
6 5SL6106-6 1AB 5SL6106-7 1 1/120 units 1AC 0.132
8 -- 5SL6108-7 1 1/120 units 1AC 0.133
10 5SL6110-6 1AB 5SL6110-7 1 1/120 units 1AC 0.131
13 5SL6113-6 1AB 5SL6113-7 1 1/120 units 1AC 0.121
16 5SL6116-6 1AB 5SL6116-7 1 1/120 units 1AC 0.121
20 5SL6120-6 1AB 5SL6120-7 1 1/120 units 1AC 0.121
25 5SL6125-6 1AB 5SL6125-7 1 1/120 units 1AC 0.123
32 5SL6132-6 1AB 5SL6132-7 1 1/120 units 1AC 0.151
40 5SL6140-6 1AB 5SL6140-7 1 1/120 units 1AC 0.163
50 5SL6150-6 1AB 5SL6150-7 1 1/120 units 1AC 0.160
63 5SL6163-6 1AB 5SL6163-7 1 1/120 units 1AC 0.160
1P+N, 230 V AC
0.3 2 -- 5SL6514-7 1 1/60 units 1AC 0.287
0.5 -- 5SL6505-7 1 1/60 units 1AC 0.308
1 -- 5SL6501-7 1 1/60 units 1AC 0.280
1.6 -- 5SL6515-7 1 1/60 units 1AC 0.308
2 -- 5SL6502-7 1 1/60 units 1AC 0.234
3 -- 5SL6503-7 1 1/60 units 1AC 0.234
4 -- 5SL6504-7 1 1/60 units 1AC 0.235
6 5SL6506-6 1AB 5SL6506-7 1 1/60 units 1AC 0.226
8 -- 5SL6508-7 1 1/60 units 1AC 0.235
10 5SL6510-6 1AB 5SL6510-7 1 1/60 units 1AC 0.222
13 5SL6513-6 1AB 5SL6513-7 1 1/60 units 1AC 0.221
16 5SL6516-6 1AB 5SL6516-7 1 1/60 units 1AC 0.228
20 5SL6520-6 1AB 5SL6520-7 1 1/60 units 1AC 0.228
25 5SL6525-6 1AB 5SL6525-7 1 1/60 units 1AC 0.251
32 5SL6532-6 1AB 5SL6532-7 1 1/60 units 1AC 0.309
40 5SL6540-6 1AB 5SL6540-7 1 1/60 units 1AC 0.314
50 5SL6550-6 1AB 5SL6550-7 1 1/60 units 1AC 0.325
63 5SL6563-6 1AB 5SL6563-7 1 1/60 units 1AC 0.325
2P, 400 V AC
0.3 2 -- 5SL6214-7 1 1/60 units 1AC 0.309
0.5 -- 5SL6205-7 1 1/60 units 1AC 0.307
1 -- 5SL6201-7 1 1/60 units 1AC 0.307
1.6 -- 5SL6215-7 1 1/60 units 1AC 0.304
2 -- 5SL6202-7 1 1/60 units 1AC 0.248
3 -- 5SL6203-7 1 1/60 units 1AC 0.246
4 -- 5SL6204-7 1 1/60 units 1AC 0.254
6 5SL6206-6 1AB 5SL6206-7 1 1/60 units 1AC 0.246
8 -- 5SL6208-7 1 1/60 units 1AC 0.255
10 5SL6210-6 1AB 5SL6210-7 1 1/60 units 1AC 0.243
13 5SL6213-6 1AB 5SL6213-7 1 1/60 units 1AC 0.249
16 5SL6216-6 1AB 5SL6216-7 1 1/60 units 1AC 0.240
20 5SL6220-6 1AB 5SL6220-7 1 1/60 units 1AC 0.240
25 5SL6225-6 1AB 5SL6225-7 1 1/60 units 1AC 0.246
32 5SL6232-6 1AB 5SL6232-7 1 1/60 units 1AC 0.303
40 5SL6240-6 1AB 5SL6240-7 1 1/60 units 1AC 0.314
50 5SL6250-6 1AB 5SL6250-7 1 1/60 units 1AC 0.328
63 5SL6263-6 1AB 5SL6263-7 1 1/60 units 1AC 0.327
1)
1 MW (modular width) = 18 mm.
3
M)
A MW1) kg
Miniature circuit breakers 10000 A
1P, 230/400 V AC
0.3 1 -- 5SL4114-7 1 1/120 units 1AC 0.165
0.5 -- 5SL4105-7 1 1/120 units 1AC 0.159
1 5SL4101-6 1AB 5SL4101-7 1 1/120 units 1AC 0.150
1.6 -- 5SL4115-7 1 1/120 units 1AC 0.159
2 5SL4102-6 1AB 5SL4102-7 1 1/120 units 1AC 0.153
3 5SL4103-6 1AB 5SL4103-7 1 1/120 units 1AC 0.161
4 5SL4104-6 1AB 5SL4104-7 1 1/120 units 1AC 0.151
6 5SL4106-6 1AB 5SL4106-7 1 1/120 units 1AC 0.152
8 5SL4108-6 1AB 5SL4108-7 1 1/120 units 1AC 0.161
10 } 5SL4110-6 1AB 5SL4110-7 1 1/120 units 1AC 0.152
13 5SL4113-6 1AB 5SL4113-7 1 1/120 units 1AC 0.150
16 } 5SL4116-6 1AB } 5SL4116-7 1 1/120 units 1AC 0.153
20 5SL4120-6 1AB 5SL4120-7 1 1/120 units 1AC 0.161
25 5SL4125-6 1AB 5SL4125-7 1 1/120 units 1AC 0.162
32 5SL4132-6 1AB 5SL4132-7 1 1/120 units 1AC 0.161
40 5SL4140-6 1AB 5SL4140-7 1 1/120 units 1AC 0.165
50 5SL4150-6 1AB 5SL4150-7 1 1/120 units 1AC 0.170
63 5SL4163-6 1AB 5SL4163-7 1 1/120 units 1AC 0.170
1P+N, 230 V AC
0.3 2 -- 5SL4514-7 1 1/60 units 1AC 0.330
0.5 -- 5SL4505-7 1 1/60 units 1AC 0.305
1 5SL4501-6 1AB 5SL4501-7 1 1/60 units 1AC 0.305
1.6 -- 5SL4515-7 1 1/60 units 1AC 0.330
2 5SL4502-6 1AB 5SL4502-7 1 1/60 units 1AC 0.306
3 5SL4503-6 1AB 5SL4503-7 1 1/60 units 1AC 0.306
4 5SL4504-6 1AB 5SL4504-7 1 1/60 units 1AC 0.306
6 5SL4506-6 1AB 5SL4506-7 1 1/60 units 1AC 0.305
8 5SL4508-6 1AB 5SL4508-7 1 1/60 units 1AC 0.330
10 5SL4510-6 1AB } 5SL4510-7 1 1/60 units 1AC 0.307
13 5SL4513-6 1AB 5SL4513-7 1 1/60 units 1AC 0.304
16 5SL4516-6 1AB 5SL4516-7 1 1/60 units 1AC 0.310
20 5SL4520-6 1AB 5SL4520-7 1 1/60 units 1AC 0.312
25 5SL4525-6 1AB 5SL4525-7 1 1/60 units 1AC 0.313
32 5SL4532-6 1AB 5SL4532-7 1 1/60 units 1AC 0.311
40 5SL4540-6 1AB 5SL4540-7 1 1/60 units 1AC 0.313
50 5SL4550-6 1AB 5SL4550-7 1 1/60 units 1AC 0.330
63 5SL4563-6 1AB 5SL4563-7 1 1/60 units 1AC 0.330
2P, 400 V AC
0.3 2 -- 5SL4214-7 1 1/60 units 1AC 0.313
0.5 -- 5SL4205-7 1 1/60 units 1AC 0.308
1 5SL4201-6 1AB 5SL4201-7 1 1/60 units 1AC 0.305
1.6 -- 5SL4215-7 1 1/60 units 1AC 0.307
2 5SL4202-6 1AB 5SL4202-7 1 1/60 units 1AC 0.311
3 5SL4203-6 1AB 5SL4203-7 1 1/60 units 1AC 0.312
4 5SL4204-6 1AB 5SL4204-7 1 1/60 units 1AC 0.310
6 5SL4206-6 1AB 5SL4206-7 1 1/60 units 1AC 0.309
8 5SL4208-6 1AB 5SL4208-7 1 1/60 units 1AC 0.313
10 5SL4210-6 1AB 5SL4210-7 1 1/60 units 1AC 0.311
13 5SL4213-6 1AB 5SL4213-7 1 1/60 units 1AC 0.305
16 5SL4216-6 1AB 5SL4216-7 1 1/60 units 1AC 0.312
20 5SL4220-6 1AB 5SL4220-7 1 1/60 units 1AC 0.312
25 5SL4225-6 1AB 5SL4225-7 1 1/60 units 1AC 0.313
32 5SL4232-6 1AB 5SL4232-7 1 1/60 units 1AC 0.311
40 5SL4240-6 1AB 5SL4240-7 1 1/60 units 1AC 0.315
50 5SL4250-6 1AB 5SL4250-7 1 1/60 units 1AC 0.330
63 5SL4263-6 1AB 5SL4263-7 1 1/60 units 1AC 0.330
1) 1 MW (modular width) = 18 mm.
10000 Characteristic D
3 In Mounting width DT Article No. Price PU PS*/ PG Weight
www.siemens.com/ per PU (UNIT, P. unit per PU
product?Article No. SET, approx.
M)
A MW1) kg
Miniature circuit breakers 10000 A
1P, 230/400 V AC
3
0.3 1 5SL4114-8 1 1/120 units 1AA 0.165
0.5 5SL4105-8 1 1/120 units 1AA 0.165
1 5SL4101-8 1 1/120 units 1AA 0.159
1.6 5SL4115-8 1 1/120 units 1AA 0.165
2 5SL4102-8 1 1/120 units 1AA 0.159
3 5SL4103-8 1 1/120 units 1AA 0.165
4 5SL4104-8 1 1/120 units 1AA 0.160
6 5SL4106-8 1 1/120 units 1AA 0.165
8 5SL4108-8 1 1/120 units 1AA 0.158
10 5SL4110-8 1 1/120 units 1AA 0.157
13 5SL4113-8 1 1/120 units 1AA 0.158
16 5SL4116-8 1 1/120 units 1AA 0.160
20 5SL4120-8 1 1/120 units 1AA 0.160
25 5SL4125-8 1 1/120 units 1AA 0.165
32 5SL4132-8 1 1/120 units 1AA 0.165
40 5SL4140-8 1 1/120 units 1AA 0.165
50 5SL4150-8 1 1/120 units 1AA 0.171
63 5SL4163-8 1 1/120 units 1AA 0.165
1P+N, 230 V AC
0.3 2 5SL4514-8 1 1/60 units 1AA 0.330
0.5 5SL4505-8 1 1/60 units 1AA 0.330
1 5SL4501-8 1 1/60 units 1AA 0.303
1.6 5SL4515-8 1 1/60 units 1AA 0.330
2 5SL4502-8 1 1/60 units 1AA 0.306
3 5SL4503-8 1 1/60 units 1AA 0.305
4 5SL4504-8 1 1/60 units 1AA 0.310
6 5SL4506-8 1 1/60 units 1AA 0.308
8 5SL4508-8 1 1/60 units 1AA 0.303
10 5SL4510-8 1 1/60 units 1AA 0.302
13 5SL4513-8 1 1/60 units 1AA 0.330
16 5SL4516-8 1 1/60 units 1AA 0.312
20 5SL4520-8 1 1/60 units 1AA 0.312
25 5SL4525-8 1 1/60 units 1AA 0.311
32 5SL4532-8 1 1/60 units 1AA 0.313
40 5SL4540-8 1 1/60 units 1AA 0.312
50 5SL4550-8 1 1/60 units 1AA 0.329
63 5SL4563-8 1 1/60 units 1AA 0.330
2P, 400 V AC
0.3 2 5SL4214-8 1 1/60 units 1AA 0.330
0.5 5SL4205-8 1 1/60 units 1AA 0.296
1 5SL4201-8 1 1/60 units 1AA 0.308
1.6 5SL4215-8 1 1/60 units 1AA 0.311
2 5SL4202-8 1 1/60 units 1AA 0.310
3 5SL4203-8 1 1/60 units 1AA 0.303
4 5SL4204-8 1 1/60 units 1AA 0.310
6 5SL4206-8 1 1/60 units 1AA 0.313
8 5SL4208-8 1 1/60 units 1AA 0.305
10 5SL4210-8 1 1/60 units 1AA 0.300
13 5SL4213-8 1 1/60 units 1AA 0.302
16 5SL4216-8 1 1/60 units 1AA 0.309
20 5SL4220-8 1 1/60 units 1AA 0.309
25 5SL4225-8 1 1/60 units 1AA 0.310
32 5SL4232-8 1 1/60 units 1AA 0.313
40 5SL4240-8 1 1/60 units 1AA 0.315
50 5SL4250-8 1 1/60 units 1AA 0.330
63 5SL4263-8 1 1/60 units 1AA 0.330
1)
1 MW (modular width) = 18 mm.
10000 Characteristic D
3 In Mounting width DT Article No. Price PU PS*/ PG Weight
www.siemens.com/ per PU (UNIT, P. unit per PU
product?Article No. SET, approx.
M)
A MW1) kg
■ Overview
Miniature circuit breakers are used to protect systems and The devices are approved for worldwide use according to
installations in buildings and for industrial applications. IEC standards for power supply systems up to 250/440 V AC.
72 V DC per pole is permitted in DC systems.
Used in industrial applications and plant engineering, miniature
circuit breakers can be supplemented with additional compo- For North America, there is an additional approval according to
nents, such as auxiliary switches, fault signal contacts, shunt
trips, undervoltage releases, remote controlled mechanism,
UL 1077 for use as "supplementary protectors" in systems up to
480/277 V AC. For use in ship building, the devices also have 3
RC units, and arc fault detection devices. numerous certifications according to shipping classifications;
BV, DNV, GL and LRS. References to this can be found in
chapter "Appendix", "Standards and approvals".
■ Benefits
• Optional top or bottom infeed as the terminals are identical • Quick and easy manual removal of miniature circuit breakers
• Clear and visible conductor connection in front of the rear from the busbar assembly, for example if connections need to
busbar facilitates controls be changed
• The conductor is easily inserted into the terminal thanks to the • Time-saving replacement of parts as busbars no longer need
large and easily accessible wiring space to be freed from adjacent devices
• Double terminal chambers permit accommodation of 2 wires • The 5SY miniature circuit breakers are ideal for the quick and
of different cross-sections easy mounting of auxiliary switches and fault signal contacts.
Captive metal brackets on the additional components ensure
the quick and easy mounting of devices on the miniature
circuit breakers without the need for tools
■ Technical specifications
5SY6 5SY4 5SY5 5SY7 5SY8 5SP4
Standards EN 60898-1 EN 60898-1 EN 60898-2 EN 60898-1 EN 60947-2 EN 60898-1
Approvals See chapter "Appendix"
Rated voltage Un V AC 230/400 230/400 230/400 230/400 230/400 230/400
3 V DC -- -- 220/440/
8805)
-- -- --
Operational voltage
Min. V AC/DC/pole 24 24 24 24 24 24
Acc. to EN 60898-1/-2 and EN 60947-2 Max. V DC/pole 724) 724) 250 724) 724) 72
Max. V AC 250/440 250/440 250/440 250/440 250/440 250/440
Acc. to UL 1077 and CSA C22.2 No.235 Max. V AC 480/277 480/277 -- 480/277 480/277 480/277
Max. V DC 60 606) -- 606) 606) 60
Breaking capacity1)
• Icn acc. to IEC/EN 60898-1 kA AC 6 10 10 15 -- 10
• Icn acc. to IEC/EN 60898-2 kA DC 10 10 10 15 -- 10
• Icu acc. to IEC/EN 60947-2 kA AC 30 ... 101) 35 ... 101) 35 ... 101) 50 ... 151) 70 ... 201) 10
kA DC 15 15 15 15 15 15
• Acc. to UL1077 and CSA C22.2 No.235 kA AC 5 5 -- 5 5 5
Insulation coordination
• Rated insulation voltage V AC 250/440
V DC/pole -- -- 250 -- -- --
Rated frequency Hz 50/60
Pollution degree for overvoltage category 3/III3)
Touch protection Acc. to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection Acc. to EN 60529 IP20 with connected conductors,
IP40 in the area of the handle with distribution cover
CFC and silicone-free Yes
Mounting
• Snap-on fixing system Yes --
• Standard mounting rail and screw fixing -- Yes
Terminals Screw (Pozidriv) 2
• Tunnel terminals at both ends -- Yes
• Combined terminals at both ends Yes --
• Terminal tightening torque Nm 2.5 ... 3 2.5 ... 3.5
lbs/in. 22 ... 26 22 ... 31
Conductor cross-sections
• Solid and stranded mm2 0.75 ... 35 4 ... 50
• Finely stranded, with end sleeve mm2 0.75 ... 25 1.5 ... 35
• AWG conductors AWG 14 ... 4 14 ... 2
(Cu 60/75 °C In 40 A; 60 °C In > 40 A)
Mains connection
• AC Any
2)
• DC Any Any
Mounting position Any
Endurance Actuations 20000
On average, with rated load Actuations 10000 for 5SY5 at 40 A, 50 A and 63 A
Ambient temperature °C -25 ... +55, max. 95 % humidity
Storage temperature °C -40 ... +75
Resistance to climate Acc. to IEC 60068-2-30 6 cycles
Shock Acc. to IEC 60068-2-27 m/s2 150 at 11 ms half-sine
Resistance to vibrations Acc. to IEC 60068-2-6 m/s2 50 at 25 ... 150 Hz and 60 at 35 Hz (4 s)
3
M)
A MW1) kg
Miniature circuit breakers 6000 A
1P, 230/400 V AC
0.3 1 -- 5SY6114-7 1 1 unit 1AC 0.168
0.5 -- 5SY6105-7 1 1/120 units 1AC 0.157
1 -- 5SY6101-7 1 1/120 units 1AC 0.155
1.6 -- 5SY6115-7 1 1/120 units 1AC 0.162
2 5SY6102-6 1AB } 5SY6102-7 1 1/120 units 1AC 0.161
3 -- 5SY6103-7 1 1/120 units 1AC 0.161
4 5SY6104-6 1AB } 5SY6104-7 1 1/120 units 1AC 0.151
5 -- 5SY6111-7 1 1 unit 1AC 0.161
6 } 5SY6106-6 1AB } 5SY6106-7 1 1/120 units 1AC 0.150
8 -- 5SY6108-7 1 1/120 units 1AC 0.150
10 } 5SY6110-6 1AB } 5SY6110-7 1 1/120 units 1AC 0.150
13 5SY6113-6 1AB 5SY6113-7 1 1/120 units 1AC 0.154
15 -- 5SY6118-7 1 1 unit 1AC 0.158
16 } 5SY6116-6 1AB } 5SY6116-7 1 1/120 units 1AC 0.155
20 5SY6120-6 1AB 5SY6120-7 1 1/120 units 1AC 0.154
25 5SY6125-6 1AB 5SY6125-7 1 1/120 units 1AC 0.153
30 -- 5SY6130-7 1 1 unit 1AC 0.162
32 5SY6132-6 1AB 5SY6132-7 1 1/120 units 1AC 0.154
40 5SY6140-6 1AB 5SY6140-7 1 1/120 units 1AC 0.154
50 5SY6150-6 1AB 5SY6150-7 1 1/120 units 1AC 0.160
63 5SY6163-6 1AB 5SY6163-7 1 1/120 units 1AC 0.164
1P+N, 230 V AC
0.3 2 -- 5SY6514-7 1 1 unit 1AC 0.328
0.5 -- 5SY6505-7 1 1 unit 1AC 0.324
1 -- 5SY6501-7 1 1 unit 1AC 0.319
1.6 -- 5SY6515-7 1 1 unit 1AC 0.311
2 5SY6506-6 1AB 5SY6502-7 1 1/60 units 1AC 0.321
3 -- 5SY6503-7 1 1 unit 1AC 0.320
4 5SY6510-6 1AB 5SY6504-7 1 1 unit 1AC 0.319
6 5SY6513-6 1AB 5SY6506-7 1 1/60 units 1AC 0.302
8 -- 5SY6508-7 1 1 unit 1AC 0.313
10 5SY6510-6 1AB 5SY6510-7 1 1/60 units 1AC 0.302
13 5SY6513-6 1AB 5SY6513-7 1 1/60 units 1AC 0.309
16 5SY6516-6 1AB 5SY6516-7 1 1/60 units 1AC 0.302
20 5SY6520-6 1AB 5SY6520-7 1 1 unit 1AC 0.313
25 5SY6525-6 1AB 5SY6525-7 1 1 unit 1AC 0.314
32 5SY6532-6 1AB 5SY6532-7 1 1 unit 1AC 0.317
40 5SY6540-6 1AB 5SY6540-7 1 1 unit 1AC 0.317
50 5SY6550-6 1AB 5SY6550-7 1 1 unit 1AC 0.329
63 5SY6563-6 1AB 5SY6563-7 1 1 unit 1AC 0.344
2P, 400 V AC
0.3 2 -- 5SY6214-7 1 1 unit 1AC 0.325
0.5 -- 5SY6205-7 1 1/60 units 1AC 0.322
1 -- 5SY6201-7 1 1/60 units 1AC 0.313
1.6 -- 5SY6215-7 1 1 unit 1AC 0.316
2 -- } 5SY6202-7 1 1/60 units 1AC 0.315
3 -- 5SY6203-7 1 1/60 units 1AC 0.305
4 -- } 5SY6204-7 1 1/60 units 1AC 0.304
5 -- 5SY6211-7 1 1 unit 1AC 0.314
6 5SY6206-6 1AB } 5SY6206-7 1 1/60 units 1AC 0.302
8 -- 5SY6208-7 1 1/60 units 1AC 0.309
10 5SY6210-6 1AB } 5SY6210-7 1 1/60 units 1AC 0.309
13 5SY6213-6 1AB 5SY6213-7 1 1 unit 1AC 0.316
15 -- 5SY6218-7 1 1 unit 1AC 0.309
16 5SY6216-6 1AB } 5SY6216-7 1 1/60 units 1AC 0.301
20 5SY6220-6 1AB 5SY6220-7 1 1/60 units 1AC 0.309
25 5SY6225-6 1AB 5SY6225-7 1 1/60 units 1AC 0.309
30 -- 5SY6230-7 1 1 unit 1AC 0.316
32 5SY6232-6 1AB 5SY6232-7 1 1/60 units 1AC 0.310
40 5SY6240-6 1AB 5SY6240-7 1 1 unit 1AC 0.316
50 5SY6250-6 1AB 5SY6250-7 1 1 unit 1AC 0.326
63 5SY6263-6 1AB 5SY6263-7 1 1 unit 1AC 0.337
1)
1 MW (modular width) = 18 mm.
3
M)
A MW1) kg
Miniature circuit breakers 10000 A
1P, 230/400 V AC
0.5 1 5SY4105-5 1AA --
1 5SY4101-5 1AA --
1.6 5SY4115-5 1AA --
2 5SY4102-5 1AA 5SY4102-6 1 1 unit 1AB 0.170
3 5SY4103-5 1AA --
4 5SY4104-5 1AA 5SY4104-6 1 1 unit 1AB 0.171
6 5SY4106-5 1AA } 5SY4106-6 1 1/120 units 1AB 0.156
8 5SY4108-5 1AA --
10 5SY4110-5 1AA } 5SY4110-6 1 1/120 units 1AB 0.151
13 5SY4113-5 1AA 5SY4113-6 1 1/120 units 1AB 0.152
16 5SY4116-5 1AA } 5SY4116-6 1 1/120 units 1AB 0.153
20 5SY4120-5 1AA 5SY4120-6 1 1/120 units 1AB 0.165
25 5SY4125-5 1AA 5SY4125-6 1 1/120 units 1AB 0.163
32 5SY4132-5 1AA 5SY4132-6 1 1/120 units 1AB 0.170
40 5SY4140-5 1AA 5SY4140-6 1 1/120 units 1AB 0.167
50 5SY4150-5 1AA 5SY4150-6 1 1 unit 1AB 0.168
63 5SY4163-5 1AA 5SY4163-6 1 1 unit 1AB 0.175
80 -- 5SY4180-6 1 1 unit 1AB 0.175
1P+N, 230 V AC
1 2 5SY4501-5 1AA --
1.6 5SY4515-5 1AA --
2 5SY4502-5 1AA --
3 5SY4503-5 1AA --
4 5SY4504-5 1AA --
6 5SY4506-5 1AA 5SY4506-6 1 1 unit 1AB 0.313
8 5SY4508-5 1AA --
10 5SY4510-5 1AA 5SY4510-6 1 1/60 units 1AB 0.317
13 5SY4513-5 1AA 5SY4513-6 1 1/6 units 1AB 0.307
16 5SY4516-5 1AA 5SY4516-6 1 1/60 units 1AB 0.311
20 5SY4520-5 1AA 5SY4520-6 1 1 unit 1AB 0.310
25 5SY4525-5 1AA 5SY4525-6 1 1 unit 1AB 0.320
32 5SY4532-5 1AA 5SY4532-6 1 1 unit 1AB 0.322
40 5SY4540-5 1AA 5SY4540-6 1 1 unit 1AB 0.321
50 5SY4550-5 1AA 5SY4550-6 1 1 unit 1AB 0.319
63 5SY4563-5 1AA 5SY4563-6 1 1 unit 1AB 0.330
2P, 400 V AC
0.5 2 5SY4205-5 1AA --
1 5SY4201-5 1AA --
1.6 5SY4215-5 1AA --
2 5SY4202-5 1AA --
3 5SY4203-5 1AA --
4 5SY4204-5 1AA --
6 5SY4206-5 1AA 5SY4206-6 1 1/60 units 1AB 0.312
8 5SY4208-5 1AA --
10 5SY4210-5 1AA 5SY4210-6 1 1/60 units 1AB 0.304
13 5SY4213-5 1AA 5SY4213-6 1 1 unit 1AB 0.321
16 5SY4216-5 1AA 5SY4216-6 1 1/60 units 1AB 0.309
20 5SY4220-5 1AA 5SY4220-6 1 1 unit 1AB 0.317
25 5SY4225-5 1AA 5SY4225-6 1 1 unit 1AB 0.323
32 5SY4232-5 1AA 5SY4232-6 1 1 unit 1AB 0.322
40 5SY4240-5 1AA 5SY4240-6 1 1 unit 1AB 0.321
50 5SY4250-5 1AA 5SY4250-6 1 1 unit 1AB 0.328
63 5SY4263-5 1AA 5SY4263-6 1 1 unit 1AB 0.339
80 -- 5SY4280-6 1 1 unit 1AB 0.311
1)
1 MW (modular width) = 18 mm.
3
1P, 230/400 V AC
0.3 1 5SY4114-7 1AC 5SY4114-8 1 1 unit 1AA 0.166
0.5 5SY4105-7 1AC 5SY4105-8 1 1 unit 1AA 0.166
1 5SY4101-7 1AC 5SY4101-8 1 1/120 units 1AA 0.172
1.6 5SY4115-7 1AC 5SY4115-8 1 1 unit 1AA 0.164
2 } 5SY4102-7 1AC 5SY4102-8 1 1/120 units 1AA 0.155
3 5SY4103-7 1AC 5SY4103-8 1 1/120 units 1AA 0.161
4 } 5SY4104-7 1AC 5SY4104-8 1 1/120 units 1AA 0.150
5 5SY4111-7 1AC --
6 } 5SY4106-7 1AC 5SY4106-8 1 1/120 units 1AA 0.165
8 5SY4108-7 1AC 5SY4108-8 1 1 unit 1AA 0.155
10 } 5SY4110-7 1AC 5SY4110-8 1 1/120 units 1AA 0.147
13 5SY4113-7 1AC 5SY4113-8 1 1 unit 1AA 0.157
15 5SY4118-7 1AC --
16 } 5SY4116-7 1AC 5SY4116-8 1 1/120 units 1AA 0.157
20 5SY4120-7 1AC 5SY4120-8 1 1 unit 1AA 0.162
25 5SY4125-7 1AC 5SY4125-8 1 1 unit 1AA 0.160
30 5SY4130-7 1AC --
32 5SY4132-7 1AC 5SY4132-8 1 1 unit 1AA 0.167
35 5SY4135-7 1AC --
40 5SY4140-7 1AC 5SY4140-8 1 1 unit 1AA 0.166
45 5SY4145-7 1AC --
50 5SY4150-7 1AC 5SY4150-8 1 1 unit 1AA 0.164
60 5SY4160-7 1AC --
63 5SY4163-7 1AC 5SY4163-8 1 1 unit 1AA 0.167
80 5SY4180-7 1AC --
1P+N, 230 V AC
0.3 2 5SY4514-7 1AC 5SY4514-8 1 1 unit 1AA 0.324
0.5 5SY4505-7 1AC 5SY4505-8 1 1 unit 1AA 0.323
1 5SY4501-7 1AC 5SY4501-8 1 1 unit 1AA 0.320
1.6 5SY4515-7 1AC 5SY4515-8 1 1 unit 1AA 0.321
2 5SY4502-7 1AC 5SY4502-8 1 1 unit 1AA 0.317
3 5SY4503-7 1AC 5SY4503-8 1 1 unit 1AA 0.315
4 5SY4504-7 1AC 5SY4504-8 1 1 unit 1AA 0.308
6 5SY4506-7 1AC 5SY4506-8 1 1 unit 1AA 0.311
8 5SY4508-7 1AC 5SY4508-8 1 1 unit 1AA 0.307
10 5SY4510-7 1AC 5SY4510-8 1 1 unit 1AA 0.324
13 5SY4513-7 1AC 5SY4513-8 1 1 unit 1AA 0.301
16 5SY4516-7 1AC 5SY4516-8 1 1 unit 1AA 0.303
20 5SY4520-7 1AC 5SY4520-8 1 1 unit 1AA 0.317
25 5SY4525-7 1AC 5SY4525-8 1 1 unit 1AA 0.313
32 5SY4532-7 1AC 5SY4532-8 1 1 unit 1AA 0.323
40 5SY4540-7 1AC 5SY4540-8 1 1 unit 1AA 0.326
50 5SY4550-7 1AC 5SY4550-8 1 1 unit 1AA 0.322
63 5SY4563-7 1AC 5SY4563-8 1 1 unit 1AA 0.324
80 5SY4580-7 1AC --
2P, 400 V AC
0.3 2 5SY4214-7 1AC 5SY4214-8 1 1 unit 1AA 0.322
0.5 5SY4205-7 1AC 5SY4205-8 1 1 unit 1AA 0.326
1 5SY4201-7 1AC 5SY4201-8 1 1/60 units 1AA 0.328
1.6 5SY4215-7 1AC 5SY4215-8 1 1 unit 1AA 0.316
2 } 5SY4202-7 1AC 5SY4202-8 1 1/60 units 1AA 0.319
3 5SY4203-7 1AC 5SY4203-8 1 1/60 units 1AA 0.323
4 5SY4204-7 1AC 5SY4204-8 1 1/60 units 1AA 0.309
5 5SY4211-7 1AC --
6 } 5SY4206-7 1AC 5SY4206-8 1 1/60 units 1AA 0.317
8 5SY4208-7 1AC 5SY4208-8 1 1 unit 1AA 0.310
10 } 5SY4210-7 1AC 5SY4210-8 1 1/60 units 1AA 0.303
13 5SY4213-7 1AC 5SY4213-8 1 1 unit 1AA 0.304
15 5SY4218-7 1AC --
16 } 5SY4216-7 1AC 5SY4216-8 1 1/60 units 1AA 0.311
20 5SY4220-7 1AC 5SY4220-8 1 1 unit 1AA 0.315
25 5SY4225-7 1AC 5SY4225-8 1 1 unit 1AA 0.323
30 5SY4230-7 1AC --
32 5SY4232-7 1AC 5SY4232-8 1 1 unit 1AA 0.329
35 5SY4235-7 1AC --
40 5SY4240-7 1AC 5SY4240-8 1 1 unit 1AA 0.321
45 5SY4245-7 1AC --
50 5SY4250-7 1AC 5SY4250-8 1 1 unit 1AA 0.328
60 5SY4260-7 1AC --
63 5SY4263-7 1AC 5SY4263-8 1 1 unit 1AA 0.325
80 5SY4280-7 1AC --
* You can order this quantity or a multiple thereof.
Siemens LV 10 · 2016/2017 3/19
© Siemens AG 2016
3
M)
A MW1) kg
Miniature circuit breakers 10000 A, high-current
1P, 230/400 V AC
80 1.5 5SP4180-6 1 1 unit 1AB 0.271
100 5SP4191-6 1 1 unit 1AB 0.269
125 5SP4192-6 1 1 unit 1AB 0.248
2P, 400 V AC
80 3 5SP4280-6 1 1 unit 1AB 0.533
100 5SP4291-6 1 1 unit 1AB 0.529
125 5SP4292-6 1 1 unit 1AB 0.516
3P, 400 V AC
80 4.5 5SP4380-6 1 1 unit 1AB 0.785
100 5SP4391-6 1 1 unit 1AB 0.789
125 5SP4392-6 1 1 unit 1AB 0.795
4P, 400 V AC
80 6 5SP4480-6 1 1 unit 1AB 1.032
100 5SP4491-6 1 1 unit 1AB 1.034
125 5SP4492-6 1 1 unit 1AB 1.066
2P, 400 V AC
80 3 5SP4280-7 1AC 5SP4280-8 1 1 unit 1AA 0.526
100 5SP4291-7 1AC 5SP4291-8 1 1 unit 1AA 0.523
125 5SP4292-7 1AC --
3P, 400 V AC
80 4.5 } 5SP4380-7 1AC 5SP4380-8 1 1 unit 1AA 0.772
100 } 5SP4391-7 1AC 5SP4391-8 1 1 unit 1AA 0.771
125 5SP4392-7 1AC --
4P, 400 V AC
80 6 5SP4480-7 1AC 5SP4480-8 1 1 unit 1AA 1.031
100 5SP4491-7 1AC 5SP4491-8 1 1 unit 1AA 1.026
125 5SP4492-7 1AC --
1)
1 MW (modular width) = 18 mm.
3
M)
A MW1) kg
Miniature circuit breakers 10000 A, universal current
1P, 230/400 V AC,
220 V DC
0.3 1 -- 5SY5114-7 1 1 unit 1AC 0.174
0.5 -- 5SY5105-7 1 1 unit 1AC 0.171
1 -- 5SY5101-7 1 1/120 units 1AC 0.169
1.6 -- 5SY5115-7 1 1 unit 1AC 0.167
2 5SY5102-6 1AB 5SY5102-7 1 1/120 units 1AC 0.170
3 -- 5SY5103-7 1 1/120 units 1AC 0.165
4 5SY5104-6 1AB 5SY5104-7 1 1/120 units 1AC 0.164
6 5SY5106-6 1AB 5SY5106-7 1 1/120 units 1AC 0.166
8 -- 5SY5108-7 1 1 unit 1AC 0.163
10 5SY5110-6 1AB 5SY5110-7 1 1/120 units 1AC 0.164
13 5SY5113-6 1AB 5SY5113-7 1 1 unit 1AC 0.168
16 5SY5116-6 1AB 5SY5116-7 1 1/120 units 1AC 0.164
20 5SY5120-6 1AB 5SY5120-7 1 1 unit 1AC 0.167
25 5SY5125-6 1AB 5SY5125-7 1 1 unit 1AC 0.167
32 5SY5132-6 1AB 5SY5132-7 1 1 unit 1AC 0.168
40 5SY5140-6 1AB 5SY5140-7 1 1 unit 1AC 0.173
50 5SY5150-6 1AB 5SY5150-7 1 1 unit 1AC 0.172
63 5SY5163-6 1AB 5SY5163-7 1 1 unit 1AC 0.176
2P, 400 V AC, 440 V DC
0.3 2 -- 5SY5214-7 1 1 unit 1AC 0.330
0.5 -- 5SY5205-7 1 1 unit 1AC 0.329
1 -- 5SY5201-7 1 1 unit 1AC 0.325
1.6 -- 5SY5215-7 1 1 unit 1AC 0.324
2 -- 5SY5202-7 1 1/60 units 1AC 0.330
3 -- 5SY5203-7 1 1/60 units 1AC 0.319
4 -- 5SY5204-7 1 1/60 units 1AC 0.319
6 5SY5206-6 1AB } 5SY5206-7 1 1/60 units 1AC 0.309
8 -- 5SY5208-7 1 1 unit 1AC 0.314
10 5SY5210-6 1AB 5SY5210-7 1 1/60 units 1AC 0.315
13 5SY5213-6 1AB 5SY5213-7 1 1/60 units 1AC 0.322
16 5SY5216-6 1AB 5SY5216-7 1 1/60 units 1AC 0.314
20 5SY5220-6 1AB 5SY5220-7 1 1 unit 1AC 0.321
25 5SY5225-6 1AB 5SY5225-7 1 1/60 units 1AC 0.320
32 5SY5232-6 1AB 5SY5232-7 1 1 unit 1AC 0.323
40 5SY5240-6 1AB 5SY5240-7 1 1 unit 1AC 0.322
50 5SY5250-6 1AB 5SY5250-7 1 1 unit 1AC 0.337
63 5SY5263-6 1AB 5SY5263-7 1 1/60 units 1AC 0.343
1) 1 MW (modular width) = 18 mm.
For application examples, see Configuration Manual "Miniature
Circuit Breakers" at: www.siemens.com/lowvoltage/manuals.
3
M)
A MW1) kg
Miniature circuit breakers 15000 A
1P, 230/400 V AC
6 1 5SY7106-6 1 1 unit 1AB 0.161
10 5SY7110-6 1 1 unit 1AB 0.160
13 5SY7113-6 1 1 unit 1AB 0.162
16 5SY7116-6 1 1 unit 1AB 0.167
20 5SY7120-6 1 1 unit 1AB 0.161
25 5SY7125-6 1 1 unit 1AB 0.163
32 5SY7132-6 1 1 unit 1AB 0.165
40 5SY7140-6 1 1 unit 1AB 0.165
50 5SY7150-6 1 1 unit 1AB 0.170
63 5SY7163-6 1 1 unit 1AB 0.173
1P+N, 230 V AC
6 2 5SY7506-6 1 1 unit 1AB 0.314
10 5SY7510-6 1 1 unit 1AB 0.313
13 5SY7513-6 1 1 unit 1AB 0.318
16 5SY7516-6 1 1 unit 1AB 0.315
20 5SY7520-6 1 1 unit 1AB 0.311
25 5SY7525-6 1 1 unit 1AB 0.309
32 5SY7532-6 1 1 unit 1AB 0.321
40 5SY7540-6 1 1 unit 1AB 0.322
50 5SY7550-6 1 1 unit 1AB 0.330
63 5SY7563-6 1 1 unit 1AB 0.340
2P, 400 V AC
6 2 5SY7206-6 1 1 unit 1AB 0.320
10 5SY7210-6 1 1 unit 1AB 0.310
13 5SY7213-6 1 1 unit 1AB 0.296
16 5SY7216-6 1 1 unit 1AB 0.317
20 5SY7220-6 1 1 unit 1AB 0.311
25 5SY7225-6 1 1 unit 1AB 0.317
32 5SY7232-6 1 1 unit 1AB 0.322
40 5SY7240-6 1 1 unit 1AB 0.324
50 5SY7250-6 1 1 unit 1AB 0.328
63 5SY7263-6 1 1 unit 1AB 0.339
3P, 400 V AC
6 3 5SY7306-6 1 1 unit 1AB 0.463
10 5SY7310-6 1 1 unit 1AB 0.458
13 5SY7313-6 1 1 unit 1AB 0.467
16 5SY7316-6 1 1 unit 1AB 0.474
20 5SY7320-6 1 1 unit 1AB 0.470
25 5SY7325-6 1 1 unit 1AB 0.474
32 5SY7332-6 1 1 unit 1AB 0.476
40 5SY7340-6 1 1 unit 1AB 0.474
50 5SY7350-6 1 1 unit 1AB 0.486
63 5SY7363-6 1 1 unit 1AB 0.506
3P+N, 400 V AC
6 4 5SY7606-6 1 1 unit 1AB 0.632
10 5SY7610-6 1 1 unit 1AB 0.591
13 5SY7613-6 1 1 unit 1AB 0.622
16 5SY7616-6 1 1 unit 1AB 0.624
20 5SY7620-6 1 1 unit 1AB 0.614
25 5SY7625-6 1 1 unit 1AB 0.617
32 5SY7632-6 1 1 unit 1AB 0.634
40 5SY7640-6 1 1 unit 1AB 0.637
50 5SY7650-6 1 1 unit 1AB 0.648
63 5SY7663-6 1 1 unit 1AB 0.660
4P, 400 V AC
6 4 5SY7406-6 1 1 unit 1AB 0.621
10 5SY7410-6 1 1 unit 1AB 0.610
13 5SY7413-6 1 1 unit 1AB 0.633
16 5SY7416-6 1 1 unit 1AB 0.620
20 5SY7420-6 1 1 unit 1AB 0.613
25 5SY7425-6 1 1 unit 1AB 0.630
32 5SY7432-6 1 1 unit 1AB 0.633
40 5SY7440-6 1 1 unit 1AB 0.635
50 5SY7450-6 1 1 unit 1AB 0.647
63 5SY7463-6 1 1 unit 1AB 0.671
1)
1 MW (modular width) = 18 mm.
3
M)
A MW1) kg
Miniature circuit breakers 25000 A
1P, 230/400 V AC
0.3 1 5SY8114-7 1AC 5SY8114-8 1 1 unit 1AA 0.165
0.5 5SY8105-7 1AC 5SY8105-8 1 1 unit 1AA 0.165
1 5SY8101-7 1AC 5SY8101-8 1 1 unit 1AA 0.172
1.6 5SY8115-7 1AC 5SY8115-8 1 1 unit 1AA 0.162
2 5SY8102-7 1AC 5SY8102-8 1 1 unit 1AA 0.162
3 5SY8103-7 1AC 5SY8103-8 1 1 unit 1AA 0.161
4 5SY8104-7 1AC 5SY8104-8 1 1 unit 1AA 0.158
6 5SY8106-7 1AC 5SY8106-8 1 1 unit 1AA 0.160
8 5SY8108-7 1AC 5SY8108-8 1 1 unit 1AA 0.156
10 5SY8110-7 1AC 5SY8110-8 1 1 unit 1AA 0.157
13 5SY8113-7 1AC 5SY8113-8 1 1 unit 1AA 0.154
16 5SY8116-7 1AC 5SY8116-8 1 1 unit 1AA 0.157
20 5SY8120-7 1AC 5SY8120-8 1 1 unit 1AA 0.165
25 5SY8125-7 1AC 5SY8125-8 1 1 unit 1AA 0.162
32 5SY8132-7 1AC 5SY8132-8 1 1 unit 1AA 0.165
40 5SY8140-7 1AC 5SY8140-8 1 1 unit 1AA 0.169
50 5SY8150-7 1AC 5SY8150-8 1 1 unit 1AA 0.170
63 5SY8163-7 1AC 5SY8163-8 1 1 unit 1AA 0.160
1P+N, 230 V AC
0.3 2 5SY8514-7 1AC 5SY8514-8 1 1 unit 1AA 0.322
0.5 5SY8505-7 1AC 5SY8505-8 1 1 unit 1AA 0.323
1 5SY8501-7 1AC 5SY8501-8 1 1 unit 1AA 0.330
1.6 5SY8515-7 1AC 5SY8515-8 1 1 unit 1AA 0.324
2 5SY8502-7 1AC 5SY8502-8 1 1 unit 1AA 0.317
3 5SY8503-7 1AC 5SY8503-8 1 1 unit 1AA 0.318
4 5SY8504-7 1AC 5SY8504-8 1 1 unit 1AA 0.307
6 5SY8506-7 1AC 5SY8506-8 1 1 unit 1AA 0.319
8 5SY8508-7 1AC 5SY8508-8 1 1 unit 1AA 0.313
10 5SY8510-7 1AC 5SY8510-8 1 1 unit 1AA 0.304
13 5SY8513-7 1AC 5SY8513-8 1 1 unit 1AA 0.305
16 5SY8516-7 1AC 5SY8516-8 1 1 unit 1AA 0.303
20 5SY8520-7 1AC 5SY8520-8 1 1 unit 1AA 0.313
25 5SY8525-7 1AC 5SY8525-8 1 1 unit 1AA 0.312
32 5SY8532-7 1AC 5SY8532-8 1 1 unit 1AA 0.323
40 5SY8540-7 1AC 5SY8540-8 1 1 unit 1AA 0.325
50 5SY8550-7 1AC 5SY8550-8 1 1 unit 1AA 0.326
63 5SY8563-7 1AC 5SY8563-8 1 1 unit 1AA 0.336
2P, 400 V AC
0.3 2 5SY8214-7 1AC 5SY8214-8 1 1 unit 1AA 0.330
0.5 5SY8205-7 1AC 5SY8205-8 1 1 unit 1AA 0.325
1 5SY8201-7 1AC 5SY8201-8 1 1 unit 1AA 0.322
1.6 5SY8215-7 1AC 5SY8215-8 1 1 unit 1AA 0.316
2 5SY8202-7 1AC 5SY8202-8 1 1 unit 1AA 0.318
3 5SY8203-7 1AC 5SY8203-8 1 1 unit 1AA 0.314
4 5SY8204-7 1AC 5SY8204-8 1 1 unit 1AA 0.310
6 5SY8206-7 1AC 5SY8206-8 1 1 unit 1AA 0.309
8 5SY8208-7 1AC 5SY8208-8 1 1 unit 1AA 0.306
10 5SY8210-7 1AC 5SY8210-8 1 1 unit 1AA 0.301
13 5SY8213-7 1AC 5SY8213-8 1 1 unit 1AA 0.305
16 5SY8216-7 1AC 5SY8216-8 1 1 unit 1AA 0.304
20 5SY8220-7 1AC 5SY8220-8 1 1 unit 1AA 0.305
25 5SY8225-7 1AC 5SY8225-8 1 1 unit 1AA 0.315
32 5SY8232-7 1AC 5SY8232-8 1 1 unit 1AA 0.340
40 5SY8240-7 1AC 5SY8240-8 1 1 unit 1AA 0.332
50 5SY8250-7 1AC 5SY8250-8 1 1 unit 1AA 0.330
63 5SY8263-7 1AC 5SY8263-8 1 1 unit 1AA 0.330
1)
1 MW (modular width) = 18 mm.
Characteristic C Characteristic D
In Mount- DT Article No. Price PG DT Article No. Price PU PS*/ PG Weight
ing www.siemens.com/ per PU www.siemens.com/ per PU (UNIT, P. unit per PU
width product?Article No. product?Article No. SET, approx.
M)
A MW1) kg
■ Overview
Miniature circuit breakers with plug-in terminals are used for the
protection of socket outlets and lighting circuits with the most
common rated currents of 10 to 20 A.
■ Benefits
3
• Double, self-contained, screwless outgoing terminals for fast • Removal of individual conductors requires no tools and
connection of conductors. ensures high operating reliability.
• No end sleeves required for finely stranded conductors. This
saves mounting time.
■ Technical specifications
5SJ6. . .-.KS
Standards EN 60898-1
Approvals See chapter "Appendix"
Rated voltage Un V AC 230/400
3 Operational voltage
• Min. V 24
AC/DC/pole
• Max. V AC 250/440
V DC/pole 601)
Rated breaking capacity Acc. to EN 60898-1 kA AC 6
Insulation coordination
• Rated insulation voltage V AC 250/440
• Pollution degree for overvoltage category 2/III
Rated frequency Hz 50/60
Touch protection Acc. to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection Acc. to EN 60529 IP20 with connected conductors,
IP40 in the area of the handle with distribution cover
CFC and silicone-free Yes
Terminals Screwless terminals on the outgoing terminals for 1.5 ... 4 mm2
Conductor cross-sections
• Top, plug-in terminals
- Solid, stranded and finely stranded, without end sleeve mm2 1.5 ... 4
- Finely stranded, with end sleeve mm2 1.5 ... 2.5
• Bottom, tunnel terminal Screw (Pozidriv) 2
- Solid, stranded or finely stranded, with end sleeve mm2 0.75 ... 25
Mounting position Any
Service life
On average, with rated load 20000 actuations
Ambient temperature °C -25 ... +45, occasionally +55, max. 95 % humidity
Storage temperature °C -40 ... +75
Resistance to climate Acc. to IEC 60068-2-30 6 cycles
1)
The operational voltage 60 V DC/pole takes into account a battery
charging voltage with a peak value of 72 V.
3
M)
A MW1) kg
Miniature circuit breakers with plug-in terminal
1P
10 1 5SJ6110-6KS 1AB 5SJ6110-7KS 1 1 unit 1AC 0.115
13 5SJ6113-6KS 1AB 5SJ6113-7KS 1 1 unit 1AC 0.124
16 5SJ6116-6KS 1AB 5SJ6116-7KS 1 1/12 units 1AC 0.113
20 5SJ6120-6KS 1AB 5SJ6120-7KS 1 1 unit 1AC 0.122
1P+N
10 2 5SJ6510-6KS 1AB 5SJ6510-7KS 1 1 unit 1AC 0.220
13 5SJ6513-6KS 1AB 5SJ6513-7KS 1 1 unit 1AC 0.221
16 5SJ6516-6KS 1AB 5SJ6516-7KS 1 1 unit 1AC 0.218
20 5SJ6520-6KS 1AB 5SJ6520-7KS 1 1 unit 1AC 0.218
2P
10 2 5SJ6210-6KS 1AB 5SJ6210-7KS 1 1 unit 1AC 0.239
13 5SJ6213-6KS 1AB 5SJ6213-7KS 1 1 unit 1AC 0.239
16 5SJ6216-6KS 1AB 5SJ6216-7KS 1 1 unit 1AC 0.239
20 5SJ6220-6KS 1AB 5SJ6220-7KS 1 1 unit 1AC 0.239
3P
10 3 5SJ6310-6KS 1AB 5SJ6310-7KS 1 1/4 units 1AC 0.356
13 5SJ6313-6KS 1AB 5SJ6313-7KS 1 1/4 units 1AC 0.353
16 5SJ6316-6KS 1AB 5SJ6316-7KS 1 1/4 units 1AC 0.351
20 5SJ6320-6KS 1AB 5SJ6320-7KS 1 1/4 units 1AC 0.350
1)
1 MW (modular width) = 18 mm.
■ Overview
These miniature circuit breakers are used for the protection of Compact busbars facilitate installation in space-saving
systems and installations with switched neutral conductors in distribution boards.
distribution boards with little space. They are just a single
modular width.
3 ■ Benefits
• Auxiliary switches and fault signal contacts from the high- • The infeed can be implemented either from the top or the
capacity range can be freely mounted on these miniature bottom. Additional terminals with lateral cable entry facilitate
circuit breakers. This increases availability and cuts down on mounting when using large conductor cross-sections.
logistics.
■ Technical specifications
5SY30.. 5SY60..
Standards EN 60898-1
Approvals See chapter "Appendix"
Rated voltage Un V AC 230
Operational voltage
• Min. V AC/DC 24
• Max. V AC 250
V 72
DC/pole
Rated making and breaking capacity Icn kA AC 4.5 6
Insulation coordination
• Rated insulation voltage V AC 250
• Pollution degree for overvoltage category 2/III
Rated frequency Hz 50/60
Touch protection Acc. to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection Acc. to EN 60259 IP20 with connected conductors,
IP40 in the area of the handle with distribution cover
CFC and silicone-free Yes
Terminals Screw (Pozidriv) 2
• Solid and stranded, mm2 0.75 ... 16
top and bottom terminal
• Finely stranded, with end sleeve, mm2 0.75 ... 10
top and bottom terminal
• Terminal tightening torque Nm 2.0 ... 2.5
Mounting position Any
Service life
On average, with rated load 20000 actuations
at 2 A/4 A and 40 A: 8000 actuations
Ambient temperature °C -25 ... +45, occasionally +55, max. 95 % humidity
Storage temperature °C -40 ... +75
Resistance to climate Acc. to IEC 60068-2-30 6 cycles
Resistance to vibrations Acc. to IEC 60068-2-6 m/s2 50 at 25 ... 150 Hz and 60 at 35 Hz (4 sec)
3
M)
A MW1) kg
Miniature circuit breakers, compact, 1+N (1P+N), 230 V AC
N pole, right
2 1 -- 5SY6002-7 1 1 unit 1AC 0.120
4 -- 5SY6004-7 1 1 unit 1AC 0.120
6 5SY6006-6 1AB 5SY6006-7 1 1/120 units 1AC 0.108
8 -- 5SY6008-7 1 1 unit 1AC 0.120
10 5SY6010-6 1AB 5SY6010-7 1 1/120 units 1AC 0.109
13 5SY6013-6 1AB 5SY6013-7 1 1 unit 1AC 0.109
16 5SY6016-6 1AB 5SY6016-7 1 1/120 units 1AC 0.108
20 5SY6020-6 1AB 5SY6020-7 1 1/120 units 1AC 0.110
25 5SY6025-6 1AB 5SY6025-7 1 1 unit 1AC 0.117
32 5SY6032-6 1AB 5SY6032-7 1 1 unit 1AC 0.126
40 5SY6040-6 1AB 5SY6040-7 1 1 unit 1AC 0.127
N pole, left
2 1 -- 5SY6002-7KL 1 1 unit 1AC 0.101
4 -- 5SY6004-7KL 1 1 unit 1AC 0.122
6 5SY6006-6KL 1AB 5SY6006-7KL 1 1 unit 1AC 0.126
8 -- 5SY6008-7KL 1 1 unit 1AC 0.122
10 5SY6010-6KL 1AB 5SY6010-7KL 1 1 unit 1AC 0.118
13 5SY6013-6KL 1AB 5SY6013-7KL 1 1 unit 1AC 0.111
16 5SY6016-6KL 1AB 5SY6016-7KL 1 1 unit 1AC 0.103
20 5SY6020-6KL 1AB 5SY6020-7KL 1 1 unit 1AC 0.122
25 5SY6025-6KL 1AB 5SY6025-7KL 1 1 unit 1AC 0.126
32 5SY6032-6KL 1AB 5SY6032-7KL 1 1 unit 1AC 0.133
40 5SY6040-6KL 1AB 5SY6040-7KL 1 1 unit 1AC 0.100
Single-phase
For MCBs 1+N, gray 1 1016 5ST3764 1 10 units 1AD 0.134
1)
1 MW (modular width) = 18 mm.
■ Dimensional drawings
5ST36 5ST37
Pin spacing in MW Pin spacing in MW
Dimensions of side view in mm (approx.). Dimensions of side view in mm (approx.).
1 1 1 1
I201_13680
I201_13984
I201_13681
15,2
10
L1 L2 L3
10
5,6
9,2 5,6
5ST3613 5ST3762 5ST3763
5ST3614 5ST3764 5ST3765
5ST3615
■ Technical specifications
Auxiliary switches (AS) Fault signal contacts (FC)
5ST3010, 5ST3010-2 5ST30131), 5ST3013-22) 5ST3020, 5ST3020-2
5ST3011, 5ST3011-2 5ST30141), 5ST3014-22) 5ST3021, 5ST3021-2
5ST3012, 5ST3012-2 1)
5ST3015 , 5ST3015-2 2) 5ST3022, 5ST3022-2
3
Standards EN 62019; IEC/EN 60947-5-1; UL 1077; CSA C22.2 No. 235
Approvals See chapter "Appendix"
Short-circuit protection Miniature circuit breaker or gG 6 A fuse
Contact load
• Min. 50 mA, 24 V 1 mA/5 V DC 50 mA, 24 V
1)
• Max. -- = 100 mA/30 V DC --
2)
= 50 mA/30 V DC
• 400 V AC, AC-14, NO A 2 -- 2
• 230 V AC, AC-14, NO A 6 -- 6
• 400 V AC, AC-13, NC A 2 -- 2
• 230 V AC, AC-13, NC A 6 -- 6
• 220 V DC, DC-13, NO+NC A 1 -- 1
• 110 V DC, DC-13, NO+NC A 1 -- 1
• 60 V DC, DC-13, NO+NC A 3 -- 3
• 24 V DC, DC-13, NO+NC A 6 -- 6
Service life, on average, with rated load 20000 actuations 20000 actuations 20000 actuations
Conductor cross-sections mm2 0.5 ... 2.5 0.5 ... 2.5 0.5 ... 2.5
AWG 22 ... 14 22 ... 14 22 ... 14
Terminals
• Terminal tightening torque Nm 0.5 0.5 0.5
lbs/in. 4.5 4.5 4.5
Rated frequency Hz 50/60
Mounting position Any Any Any
Ambient temperature °C -25 ... +55 -25 ... +55 -25 ... +55
Storage temperature °C -40 ... +75 -40 ... +75 -40 ... +75
Resistance to climate Acc. to IEC 60068-2-30 Cycles 28
Shock Acc. to IEC 60068-2-27 m/s 50 at 11 ms half-sine
Resistance to vibrations Acc. to IEC 60068-2-6 m/s2 50 at 10 ... 150 Hz
Rated residual Rated current Mount- DT Article No. Price PU PS*/ PG Weight
current ing www.siemens.com/ per PU (UNIT, P. unit per PU
width product?Article No. SET, approx.
M)
In In
mA A MW1) kg
RC units, type A, instantaneous tripping
For 5SY miniature circuit breakers,
3
but not for 5SY5, 5SY8, 5SY60. . and 5SL miniature
circuit breakers
2P, 230 ... 400 V AC, 50 ... 60 Hz
10 0.3 ... 16 2 5SM2121-6 1 1 unit 1AH 0.203
30 0.3 ... 40 } 5SM2322-6 1 1/24 units 1AH 0.201
300 5SM2622-6 1 1/24 units 1AH 0.194
30 0.3 ... 63 5SM2325-6 1 1 unit 1AH 0.212
100 5SM2425-6 1 1 unit 1AH 0.207
300 5SM2625-6 1 1 unit 1AH 0.194
500 5SM2725-6 1 1 unit 1AH 0.194
For 5SY miniature circuit breakers,
but not for 5SY5, 5SY8, 5SY60. . and 5SL miniature
circuit breakers
3P; 230 ... 400 V AC; 50 ... 60 Hz
30 0.3 ... 40 3 5SM2332-6 1 1 unit 1AH 0.300
300 5SM2632-6 1 1 unit 1AH 0.288
30 0.3 ... 63 5SM2335-6 1 1 unit 1AH 0.338
100 5SM2435-6 1 1 unit 1AH 0.312
300 5SM2635-6 1 1 unit 1AH 0.289
500 5SM2735-6 1 1 unit 1AH 0.294
For 5SY miniature circuit breakers,
but not for 5SY5, 5SY8, 5SY60. . and 5SL miniature
circuit breakers
4P, 230 ... 400 V AC, 50 ... 60 Hz
30 0.3 ... 40 3 } 5SM2342-6 1 1 unit 1AH 0.327
300 } 5SM2642-6 1 1 unit 1AH 0.322
30 0.3 ... 63 5SM2345-6 1 1 unit 1AH 0.375
100 5SM2445-6 1 1 unit 1AH 0.338
300 5SM2645-6 1 1 unit 1AH 0.319
500 5SM2745-6 1 1 unit 1AH 0.319
For 5SP4 miniature circuit breakers
(B and C characteristics)
2P, 125 ... 230 V AC, 50 ... 60 Hz
30 80 ... 100 3.5 5SM2327-6 1 1 unit 1AH 0.516
300 5SM2627-6 1 1 unit 1AH 0.467
Rated residual Rated current Mount- DT Article No. Price PU PS*/ PG Weight
current ing www.siemens.com/ per PU (UNIT, P. unit per PU
width product?Article No. SET, approx.
M)
In In
mA A MW1) kg
1)
1 MW (modular width) = 18 mm.
For 5SL, 5SV, 5TL1 miniature circuit breakers 5ST3806 1 5 units 1AD 0.004
For padlock with 3 ... 6 mm shackle
Padlocks
For 5ST3801 and 5ST3806 handle locking device 5ST3802 1 1 unit 1AD 0.033
Locking devices
For 5SP and 5SY miniature circuit breakers 5ST3803 1 1 set 1AD 0.044
comprising 5ST3801 handle locking device
and 5ST3802 padlock
Locking devices
For 5SL, 5SV, 5TL1 miniature circuit breakers, 5ST3807 1 1 set 1AD 0.024
comprising 5ST3806 handle locking device
and 5ST3802 padlock
Spacers
Can be placed on either side of the standard 0.5 5TG8240 1 2 units 1BK 0.017
mounting rail. Two spacers allow for
convenient cable routing
Fixing parts
Made of plastic, for use on a mounting plate 5ST2201 1 1 unit 1AD 0.012
Device labels
Adhesive, for modular installation devices, e.g.
5SY, 5SL, 5TL1, etc.
Versions
• 15 mm x 6 mm, white (WIN 098) 8WH8210-0AA35 100 3740 units 1BT 0.010
• 15 mm x 6 mm, yellow (WIN 099) 8WH8210-0AA36 100 3740 units 1BT 0.010
Covers
Can be assembled as mini distribution board, suitable
for all devices, cover parts prepared for rail mounting
of conventional label caps, comprising:
• End plates (for snapping onto standard mounting } 5ST2134 1 10 units 1AD 0.026
rail)
• Angled profile (approx. 1 m long) 5ST2135 1 5 units 1AD 0.288
• Alternative flat profiles 5ST2136 1 5 units 1AD 0.239
(as a cover between the rows of devices length
approx. 1 m)
Holders for front panel installation
Universal use for devices from 1 to 6 MW
Cutout dimensions:
Height 45+0.5 mm
Width: 23, 41, 59, 77, 95 or 113 mm 7LF9006 1 1 unit 1BK 0.070
■ More information
The Siemens mounting concept supports the combination of all
5ST3 additional components with miniature circuit breakers of
the 5SY and 5SP series and RCBOs of the 5SU1 series.
5SL and 5SY60.. miniature circuit breakers are suitable for
mounting auxiliary switches and fault signal contacts. Auxiliary
switches can also be mounted on 5TE8 flush-mounting circuit 3
breakers and 5SG71 MINIZED switch disconnectors. In the case
of the 5SY6 miniature circuit breaker and in the case of the
RCBO, the arc fault detection device can be mounted on the
left-hand side.
For further information on the mounting concept for RCBOs, see chapter "Residual Current Protective Devices / Arc Fault Detection
Devices (AFDDs)".
■ Overview
The busbar system with pin-type connections can be used for all No further need for time-consuming tasks, such as cutting,
5SL6 and 5SJ6 miniature circuit breakers . . .-.KS and 5SY cutting to length, deburring, cleaning of cut surfaces and
miniature circuit breakers with or without mounted auxiliary mounting of end caps.
switch (AS) or fault signal contact (FC).
Any free pins on the busbars can be made safe by covering with
3 Busbars in 10 mm2 and 16 mm2 versions are available.
With bars that can be cut to length, the 5ST37 busbar system
touch protection.
For further information on the bus-mounting of miniature circuit
can be tailored to any requirements. breakers with residual current operated circuit breakers, please
refer to the chapter "Residual Current Protective Devices/
The extremely flexible 5ST36 busbar system with fixed lengths Arc Fault Detection Devices (AFDDs)".
also enables installation in any length as the busbars can be
overlapped.
■ Benefits
• Between the rows of devices, the busbar, that is located at the • The ability to overlap when mounting the busbars enables a
bottom and behind the conductor, provides an optimum wiring cross-section enlargement of up to 32 mm2 using the
space with easy view of the inserted conductor. This enables respective components, 10 mm2 and 16 mm2
easy control of connections.
• By overlapping the busbars with fixed lengths, it is possible to • The fact that the connection of the conductor is always clearly
achieve device combinations with any number of devices visible facilitates cable entry of all pole types and
considerably reduces mounting times
■ Technical specifications
5ST3
Standards EN 60439-1 (VDE 0660-500): 2005-01
Busbar material SF-Cu F 24
Partition material Plastic, Cycoloy 3600
heat-resistant over 90 °C
flame-retardant and
self-extinguishing,
3
dioxin and halogen-free
Rated operational voltage Uc V AC 400
Rated current In
• Cross-section 10 mm2 A 63
• Cross-section 16 mm2 A 80
Rated impulse withstand voltage Uimp kV 4
Test pulse voltage (1.2/50) kV 6.2
Rated conditional short-circuit current Icc kA 25
Resistance to climate
• Constant atmosphere Acc. to DIN 50015 23/83; 40/92; 55/20
• Humid heat Acc. to IEC 60068-2-30 28 cycles
Insulation coordination
• Overvoltage category III
• Pollution degree 2
Maximum busbar current IS/phase
• Infeed at the start of the busbar
- Cross-section 10 mm2 A 63
- Cross-section 16 mm2 A 80
• Infeed at the center of the busbar
- Cross-section 10 mm2 A 100
- Cross-section 16 mm2 A 130
Infeed at the start or end of the busbar Infeed along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755
I201_13754a
S
S1 S2
The sum of the outgoing current per branch (1, 2, 3 ... n) must not be greater
than the max. busbar current IS/phase.
Single-phase,
for MCBs with AS or FC
For 2 MCBs 1P 1.5 40 5ST3633 1 10 units 1AD 0.011
For 6 MCBs 1P 156.5 5ST3634 1 10 units 1AD 0.036
For 9 MCBs 1P 237 5ST3635 1 10 units 1AD 0.055
Two-phase
For 2 MCBs 2P 1 75.5 5ST3636 1 10 units 1AD 0.026
For 3 MCBs 2P 105 5ST3637 1 10 units 1AD 0.042
For 6 MCBs 2P 210 5ST3638 1 10 units 1AD 0.089
Two-phase
For MCBs with AS or FC
For 2 MCBs 2P 1 + 1.5 75.5 5ST3640 1 10 units 1AD 0.029
For 3 MCBs 2P 120.5 5ST3641 1 10 units 1AD 0.048
For 5 MCBs 2P 210 5ST3642 1 10 units 1AD 0.086
1) 1 MW (modular width) = 18 mm.
1)
1 MW (modular width) = 18 mm.
■ Dimensional drawings
5ST36
Pin spacing in MW (modular width; 1 MW = 18 mm)
Dimensions of side view in mm (approx.)
1 1 1,5 1,5
I201_13663
14
3,4
5ST3600 5ST3601 5ST3603 5ST3604
5ST3630 5ST3602 5ST3633 5ST3605
5ST3631 5ST3634
5ST3632 5ST3635
1 1 1 1,5
I201_13666
I201_13664
15,2
L1 L2
19
L1 L2 L1 L2
6,6 7,3
5ST3606 5ST3636 5ST3640
5ST3607 5ST3637 5ST3641
5ST3608 5ST3638 5ST3642
15,2
L1 L2 L3 L1 L2 L3 L1 L2 L3
9,2
5ST3613 5ST3616 5ST3618
5ST3614 5ST3617 5ST3620
5ST3615
5ST3667
19
L1 L2 L3 L1 L2 L3 L1 L2 L3
10,3
5ST3643 5ST3646 5ST3648
5ST3644 5ST3647 5ST3650
5ST3645
5ST3668
1 1 1 1 1 1 1 1
1,5
I201_13670
15,2
L1 L2 L3 N L1 N L2 N L3 N
11,8
5ST3621 5ST3623
5ST3622
1 1 1 1 1 1 1 1
1,5
I201_13671
L1 L2 L3 N L1 N L2 N L3 N
19
13,3
5ST3651 5ST3653
5ST3652
5ST36
Pin spacing in MW (modular width; 1 MW = 18 mm)
Dimensions of side view in mm (approx.)
1 1 2 1 1 1 1 1 1 1
1,5
I201_13672
3
15,2
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2
9,2
5ST3624
1 1 2 1 1 1 1 1 1 1
1,5
I201_13673
L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2
19
10,3
5ST3654
5ST37
Pin spacing in MW (modular width; 1 MW = 18 mm)
Dimensions of side view in mm (approx.)
1 1,5 1 1 1,5
I201_13674
3,5
I201_13675
15
L1 L2 L1 L2
13
18
5ST3700 5ST3702 5ST3704 5ST3706
5ST3701 5ST3703 5ST3705 5ST3707
5ST3730 5ST3732 5ST3734 5ST3736
5ST3731 5ST3733 5ST3735 5ST3737
Single-phase Single-phase Two-phase Two-phase
15
L1 L2 L3 L1 L2 L3 L1 L2 L3
18
5ST3708 5ST3711 5ST3713
5ST3710 5ST3712 5ST3714
5ST3738 5ST3741 5ST3743
5ST3740 5ST3742 5ST3744
I201_19174
18
17
L1 L2 L3 N L1 N L2 N L3 N
20 20
5ST3715 5ST3746-2
5ST3716
5ST3745
5ST3746
2 2 2
I201_19201
17
L1 L2 L1 L2
14
5ST3735-2
5ST37
Pin spacing in MW (modular width; 1 MW = 18 mm)
Dimensions of side view in mm (approx.)
1
3
L1 N L2 N N L2 N L1
L1 N L3 N N L3 N L1
I201_18187
5ST3770-2
1,5
L1 N L2 N N L2 N L1
L1 N L3 N N L3 N L1
I201_18188
5ST3770-3
1 1 1 1 1 1
1
11,9
30,2
30,2
L1 L2 L3 N L2 N L3 N
I202_01456 18,3
22,1
5ST3770-4
1 1 1 1 1 1
1,5
11,9
30,2
30,2
L1 L2 L3 N L2 N L3 N
18,3
I202_01458
22,1
5ST3770-5
1 1
I201_13680
I201_13681
10
10
5,6
5,6
5ST3762 5ST3763
5ST3764 5ST3765
■ Overview
Products according to UL standards are used in North America, The busbars are available in single-, two- and three-phase
but also in several other countries. This is important in particular versions with different pin spacings and with two cross-sections
for exporting machines or electrical switchboard assemblies 18 mm² and 25 mm². Infeed can be directly into the terminals of
and equipment to the USA. Acceptance and delivery are possi- the miniature circuit breaker or through connection terminals.
3
ble only if the relevant UL standards are satisfied.
The connection terminals are available in two versions – for
The 5ST37 busbar system according to UL 508 and CSA is direct infeed at the busbar or for infeed directly at the miniature
suitable for both universal use worldwide with all 5SY and circuit breaker/fuse holder. Pins that are not required can be
5SP miniature circuit breakers for "Supplementary Protection" covered with touch protection covers.
certified according to UL 1077 and for 3NW and 3NC fuse
holders certified according to UL 512. Not approved for use in
feeder circuits.
■ Benefits
• Busbar with infeed through a connection terminal directly on • Infeed directly on the miniature circuit breaker up to a cross-
the miniature circuit breaker up to a conductor cross-section section of 35 mm² and connection terminal for connection di-
of 35 mm² rectly on the busbar up to conductor cross-sections of 50 mm²
• Suitable for universal use according to both IEC and
UL standards
• Can be used for 5SY, 5SP miniature circuit breakers and for
Class CC, SITOR cylindrical and semiconductor fuse holders
• UL-tested combination – device and busbar
• Different cross-sections 18 mm² and 25 mm²
■ Technical specifications
5ST37. .-0HG 5ST37. .-2HG 5ST3770-0HG 5ST3770-1HG
Standards UL 508, CSA C22.2 No. 14-M 95 / IEC 60999
Approvals UL 508 File No. E328403
CSA
3 Operational voltage
• Acc. to IEC V AC 690
• Acc. to UL 508 V AC 600
Rated conditional short-circuit current kA 10
• Dielectric strength kV/mm 25
• Surge strength kV > 9.5
Max.current UL A -- -- 115
IEC A -- -- 160
Maximum busbar current IS/phase
• Infeed at the start of the busbar A 80 100 -- --
• Infeed at the center of the busbar A 160 200 -- --
Insulation coordination
• Overvoltage category III
• Pollution degree 2
Short-circuit current load capability 10000 A RMS sym. 600 V for three connections
18 mm2 100000 A RMS sym. for protection with Class J 175 A
25 mm2 100000 A RMS sym. for protection with Class J 200 A
Busbar cross-section mm2 Cu 18 25 -- --
Infeed Any
Conductor cross-sections Solid AWG -- -- 10 ... 1/0 10 ... 1
mm2 -- -- 6 ... 35 (Cu 60 °C) 6 ... 50 (Cu 75 °C)
Stranded AWG -- -- 10 ... 2
mm2 -- -- 6 ... 35
Terminals Screw (Pozidriv) -- -- 2 2
• Terminal tightening torque Nm -- -- 5 3.5
lbs/in. -- -- 50 35
Infeed at the start or end of the busbar Infeed along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755
I201_13754a
S
S1 S2
The sum of the outgoing current per branch (1, 2, 3 ... n) must not be greater
than the max. busbar current IS/phase.
Infeed to busbar
50 mm2 5ST3770-1HG 1 10 units 1AE 0.032
■ Dimensional drawings
5ST37 busbars
Pin spacing in MW (modular width; 1 MW = 18 mm)
Dimensions of side view in mm (approx.)
1 1,5 2 1 1 1,5 1,5
3
I202_02123
I202_02124
5
23
L1 L2 L1 L2
15
21
I202_02122
23
L1 L2 L3 L1 L2 L3 L1 L2 L3
21
5ST3710-0HG 5ST3712-0HG 5ST3714-0HG
I202_02105
5
23
L1 L2
15
21
5ST3701-2HG 5ST3705-2HG
1,5 1,5 2
I202_02106
I202_02108
24
23
L1 L2 L3
21 22 9,5
5ST3710-2HG 5ST3750-0HG
1 16 28,5
I202_02110
30
I202_02111
I202_02107
60
14
18,5
5 9,5 8 3 40 18
5ST3748-0HG 5ST3770-0HG 5ST3770-1HG
14 3,8
0,
R
24
5,7
23,8
71,2
17,8
I202_02109
5ST3655-0HG
■ Overview
Distribution blocks for standard rail mounting The distribution blocks are made of thermoplastic with electrical
and mechanical components, which enables their use under
Using distribution blocks it is possible to implement one, two, high thermal and mechanical load acc. to IEC 60947-7-1.
three and four-phase systems with a rated current of up to 400 A.
This allows supply terminals to be divided into several load
circuits with different cable cross-sections.
3
■ Technical specifications
5ST2501 5ST2502 5ST2503
Standards, IEC 60947-7-1
certifications
Degree of protection IP 20
Poles 4
Approved cable Copper
Conductor cross-section
• Inputs per pole
- Solid/stranded conductor mm² 1 x 2.5 … 16 1 x 6 … 35 1 x 10 … 35
acc. to IEC Neutral mm² -- 1 x 6 … 35 --
conductor
- Finely stranded with end sleeve mm² 1 x 2.5 … 10 1 x 6 … 25 1 x 10 … 25
Neutral mm² -- 1 x 6 … 25 --
conductor
• Outputs per pole
- Solid/stranded conductor Large mm² 8 x 1.5 … 10 2 x 4 … 16 3 x 6 … 25
acc. to IEC Small mm² -- 5 x 1.5 … 6 8 x 2.5 … 16
Neutral Large mm² -- 6 x 4 … 16 --
conductor Small mm² -- 4 x 1.5 … 10 --
- Finely stranded with end sleeve Large mm² 8 x 1.5 … 10 2 x 4 … 10 3 x 6 … 16
Small -- 5 x 1.5 ... 6 8 x 2.5 ... 10
Neutral Large mm² -- 6 x 4 … 10 --
conductor Small -- 4 x 1.5 ... 6 --
Tightening torque
• Inputs lbs/in. 13.5 13.5 3.5 ... 5
Nm 1.5 1.5 2
Plug-in connection PZ2 PZ2 PZ2
• Outputs Large lbs/in. 13.5 13.5 13.5
Nm 1.5 1.5 1.5
Plug-in connection PZ1 PZ2 PZ2
Small lbs/in. -- 7.2 13.5
Nm -- 0.8 1.5
Plug-in connection -- PZ1 PZ2
Operational voltage
• IEC, max. V 690 690 1000 V AC
1500 V DC
Overcurrent protection
• Max. rated current A 80 125 175
• Rated peak withstand current (Ipk) kA 21.6 24 20
• Rated short-time withstand current (Icw 1 s) kA 3 4.2 6.2
Block dimensions (D x H x W) mm 88 x 49 x 85 75 x 45 x 98 102 x 47 x 87
3 Poles
Approved cable
1
Copper
Wiring type Factory and field wiring
• Front/back Pressure wire connector
Conductor cross-section
• Inputs
- Solid and stranded conductor Large AWG 1 x 14 … 4 1x8…2 1x8…2/0 1x2…4/0 1x3/
acc. to UL 0 … 350 MCM
- Solid and stranded acc. to IEC mm² 2.5 … 16 10 … 35 10 … 70 35 … 120 95 … 185
- Solid and stranded conductor Small AWG -- 1 x 14 ... 6 --
acc. to UL
- Solid and stranded acc. to IEC mm² -- 6 ... 16 --
- Finely stranded with end sleeve Large AWG 1 x 14 … 4 1x8…2 1x8…1 1x2…3/0 3/0…5/0
acc. to UL
- Finely stranded with end sleeve mm² 2.5 … 16 10 … 35 10 … 50 35 … 95 95 … 150
acc. to IEC
- Finely stranded with end sleeve Small AWG -- 1 x 14 ... 6 --
acc. to UL
- Finely stranded with end sleeve mm² -- 6 ... 16 --
acc. to IEC
• Outputs
- Solid and stranded conductor Top AWG 4 x 14 … 10 6 x 14 … 6 6 x 14 … 6 4 x 16 … 8 --
acc. to UL
- Solid and stranded acc. to IEC mm² 2.5 … 6 2.5 … 16 2.5 … 16 1.5 … 10 --
- Solid and stranded conductor Medium AWG -- 5 x 16 … 6
acc. to UL
- Solid and stranded acc. to IEC mm² -- 1.5 … 16
- Solid and stranded conductor Bottom AWG 2 x 14 … 6 -- 2 x 14 … 2
acc. to UL
- Solid and stranded acc. to IEC mm² 2.5 … 16 -- 2 x 2.5 … 35
- Finely stranded with end sleeve Top AWG 4 x 14 … 10 6 x 14 … 6 6 x 14 … 6 2 x 14 … 4
acc. to UL
- Finely stranded with end sleeve mm² 2.5 … 6 2.5 … 16 2.5 … 16 2 x 2.5 ... 25
acc. to IEC
- Finely stranded with end sleeve Bottom AWG 2 x 14 … 6 -- 2 x 14 … 4 --
acc. to UL
- Finely stranded with end sleeve mm² 2.5 … 16 -- 2 x 2.5 … 25 --
acc. to IEC
Tightening torque
• Inputs lbs/in. 13.2 ... 26.5 31 ... 44 44 ... 53 170 ... 186 222
Nm 1.5 ... 3 3.5 ... 5 5 ... 6 19 ... 21 25
Plug-in connection Allen key (4 mm) Allen key (5 mm) Allen key (6 mm) Allen key (8 mm)
• Outputs Large lbs/in. 13.2 ... 26.5 17.7 ... 26.5 13.2 ... 26.5 31 ... 62
Nm 1.5 ... 3 2 ... 3 1.5 ... 3 3.5 ... 7
Plug-in connection PZ2 Standard screwdriver
Small lbs/in. 7 ... 13.2 -- 18 ... 27
Nm 0.8 ... 1.5 -- 2 ... 3
Plug-in connection PZ1 -- Standard screwdriver
Ampere per pole, max. (UL/IEC) A 80/80 115/125 160/160 230/250 310/400
Operational voltage
• UL, max. (AC) V 600
• IEC, max. (AC/DC) V 1000/1500
Overcurrent protection
• Required Class J
• Max. rated current (UL/IEC) A 80/80 115/125 160/160 230/250 310/400
• SCCR RMS Sym A kA 100
• Rated peak withstand current (Ipk) kA 2.7 30 51
• Rated short-time withstand current (Icw 1 s) kA 1.9 4.2 11 21
Clearance
• Air inches 3 / 8 (9.5)
(mm)
• Creepage distance inches 1 / 2 (12.7)
(mm)
Fire class UL 94V-0
Block dimensions (D x H x W) mm 66 x 47 x 27 74 x 47 x 27 92 x 49 x 35 96 x 49 x 45 96 x 49 x 45
Connections With cable up to With connector or Lateral incoming -- --
16 mm² cable up to feeder for paral-
16 mm² 1) lel connection
with copper bar
(max. 16 x 5 mm)
1)
Copper jumper is tested for a rated current of 100 A
3
A V MW kg
Distribution blocks
1-pole UL 1059 / UL 486E / 80 600 1.5 5ST2504 1 1 unit 1AD 0.076
IEC 60947-7-1 125 600 1.5 5ST2505 1 1 unit 1AD 0.149
UL File No. E80027 / XCFR2 160 600 2 } 5ST2507 1 1 unit 1AD 0.259
C22.2 No158 -1987 / XCFR8
UL 486E / IEC 60947-7-1 250 600 2.5 } 5ST2508 1 1 unit 1AD 0.430
UL File No. E80027 / XCFR2 350 600 2.5 } 5ST2511 1 1 unit 1AD 0.407
5ST2504
4-pole IEC 60947-7-1 80 500 5 5ST2501 1 1 unit 1AD 0.224
5ST2501
IEC 60947-7-1 125 690 5.5 5ST2502 1 1 unit 1AD 0.337
5ST2502
IEC 60947-7-1 160 500 9 5ST2503 1 1 unit 1AD 0.716
5ST2503
Accessories
Connector for 5ST2505 distribution -- -- -- 5ST2506 1 10 units 1AD 0.015
board
• With touch protection
• 20 mm2
• Single-phase
• 32 mm
5ST2506
Terminal lug ring terminal end for
distribution block
Versions
• For 5ST2508 distribution block 5ST2510 1 10 units 1AD 0.057
• For 5ST2511 distribution block 5ST2512 1 10 units 1AD 0.086
■ Dimensional drawings
27 4 43 27 4 43
3
66
74
I201_18405
I201_18406
5ST2504 5ST2505
35 5 44 45 5 44
92
96
I201_18407
I201_18408
5ST2507 5ST2508
45 5 44 85 5 49
88
96
I201_18402
I201_18409
5ST2511 5ST2501
98 5 41 162 50
87
75
I201_18404
I201_18403
5ST2502 5ST2503
■ Overview
SIKclip is a fast wiring system that simplifies the connection of High degree of protection because each contact is locked
control switches: individually.
• For mounting directly on the rear vertical CU busbar system SIKclip is made of thermoplastic acc. to IEC 60439-3 and is
• Mounting using brackets on the rear of the DIN rail. suitable for high thermal loads.
The 4-pole busbar can handle loads of up to 250 A, each 3
individual contact up to 63 A.
■ Technical specifications
5ST25..
Test specifications EN 60947-1, EN 61439-1
Degree of protection IP20
Max. rated current In A 250 at 40 °C ambient temperature
Max. rated output current In A 63 at 40 °C ambient temperature
Rated operational voltage Un V AC 400
Rated insulation voltage V AC 660
Test voltage kV 2.5, 50 Hz
Connecting cables 40 A (6 mm2), 63 A (10 mm2)
Connecting cable type H07VK
Ambient temperature °C -5 ... +60
Note:
To install the SIKclip wiring system in the ALPHA AS, the busbars
must be installed in a vertical rear position, but not recessed. If
the busbars are in a recessed position the cables will not reach
the circuit breakers.
* You can order this quantity or a multiple thereof.
Siemens LV 10 · 2016/2017 3/61
© Siemens AG 2016
■ Dimensional drawings
436,5
3 F
mounting bracket
50 25 25 50
647,5
I201_18489
mounting bracket
50 25 25 50
17
58,3 (L1)
50,8 (L2)
65
40,3 (L3)
29,8 (N)
12,5
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
■ Overview
UL standards are used in North America as well as in several The key difference between the three device series is their
other countries. This is of particular importance to European application in different power supply systems.
exporters of electrical switchboard assemblies and equipment • 5SJ4…-.HG40: 240/120 V AC, 1-pole, "same polarity only",
for machines who export to the USA, as their products will only • 5SJ4…-.HG41: 240 V AC, 1-, 2- and 3-pole,
3
be accepted if they meet the relevant UL standards. • 5SJ4…-.HG42: 480Y/277 V AC, 1-, 2- and 3-pole.
A wide range of low-voltage circuit protection devices from The terminals are suitable for "field wiring". This means that the
Siemens comply with UL standards and are therefore suitable for devices can be installed not only in factory-built distribution
implementation worldwide in both IEC/EN and UL applications boards and control cabinets, but also on-site in a customer
within the framework of their specified use. system.
Miniature circuit breakers certified to UL 489 permit use as an Using this mounting concept, all additional 5ST3. . .-.HG com-
all-round solution for protection tasks in distribution boards, ponents can be combined with miniature circuit breakers of the
control cabinets and control systems to UL 508A as "branch 5SJ4…-.HG range. The auxiliary switch (AS) signals the contact
protectors". In particular, they are also approved for the protec- position. In the event of a fault, the fault signal contact (FC)
tion of electrical circuits in heating, ventilating and cooling sys- signals the automatic tripping of the miniature circuit breaker as
tems (HVAC), as well as for DC applications up to 60 V/125 V. well as the contact position. Shunt trips (ST) are used for remote
This covers a wide range of protection tasks, in residential and tripping of miniature circuit breakers. Captive metal brackets on
non-residential buildings, as well as in industry. The tripping the additional components ensure fast mounting on the devices.
characteristics B, C and D to EN/IEC 60898-1 have been Single, two and three-phase busbars in 3 lengths with 6, 12 or
adapted so that they fall in the permissible tripping range 18 pins are available as accessories for all device series for "field
according to UL 489, as well as for applications at 25 °C and wiring". The infeed is via connection terminals, which are avail-
40 °C. able in two versions, for direct infeed at either the busbar or the
This means that the devices are approved for use according to miniature circuit breakers. Pins that are not required can be
both standards. The enclosure dimensions of the devices corre- covered with touch protection covers.
spond to DIN format. This means that the device series are
suitable for universal use worldwide according to IEC or
UL standards.
■ Benefits
• Can be used globally for all applications in residential,
non-residential and industrial buildings. This facilitates the
planning of installations and enhances export opportunities
• The devices can be used according to IEC/EN 60898-1 and
UL 489, which means these devices can be installed any-
where in the world
• Miniature circuit breakers with 480Y/277 V up to 40 A, with
240/120 V and 240 V up to 63 A
• Can be used for both AC voltage and DC voltage up to 125 V
• Rated making and breaking capacity up to 14 kA in acc. with
UL 489 and up to 15 kA in acc. with IEC 60947-2
• Fast mounting with busbars up to 115 A and feeder terminals
up to 50 mm2.
• Bus mounting with central infeed directly on the busbar up to • Accessories: Auxiliary switches, fault signal contacts and
conductor cross-section of 50 mm2 shunt trips up to 480 V can be easily mounted onto the
miniature circuit breaker
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
■ Technical specifications
5SJ4. . .-.HG40 5SJ4. . .-.HG41 5SJ4. . .-.HG42
Standards EN 60947-2;
UL 489 (UL File E243414); UL 489A (UL File E332105); CSA C22.2 No. 5-02
Approvals See chapter "Appendix"
3 Tripping characteristic
Rated voltage
B, C, D C, D
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
Additional components Auxiliary switches (AS) Fault signal contacts Shunt trips (ST)
(FC)
5ST3010-0HG 5ST3020-0HG 5ST3030-0HG 5ST3031-0HG
5ST3011-0HG 5ST3021-0HG
5ST3012-0HG 5ST3022-0HG
3
Standards UL 489, UL File E321559; CSA 22.2 No. 5-02
IEC/EN 62019, IEC/EN 60947-5-1 IEC/EN 60947-1
Operational voltage/operational current (load)
• Acc. to IEC V AC 400 230 110 ... 415 24 ... 60
A AC 2 6 (NC: 13 AC, S: AC14) -- --
V DC 220 110 60 24 -- 24 ... 60
A DC 1 1 3 6 (DC13) -- --
• Acc. to UL V AC 480 277 240 120 110 ... 480 24 ... 60
A AC 1.5 3 4 6 -- --
V DC 125 60 -- 24 ... 60
A DC 1 3 -- --
Rated frequency Hz 50/60
Short-circuit protection Miniature circuit breaker or 6 A fuse
Minimum contact load 50 mA, 24 V
Tripping operations -- -- max. 2000
Service life, on average, with rated load 12000 actuations
Primary operating range x Un -- 0.7 ... 1.1
Conductor cross-sections AWG 22 ... 14 22 ... 14
mm2 0.5 ... 2.5 0.5 ... 2.5
Terminals Screw (Pozidriv) 1 1 1
• Terminal tightening torque Nm 0.5 0.8
lbs/in. 4.5 6.8
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
3
M)
A MW1) kg
Miniature circuit breakers
"same polarity only"
1P, 240 V AC
6 1 5SJ4106-6HG40 1 1 unit 1AE 0.160
10 5SJ4110-6HG40 1 1 unit 1AE 0.166
13 5SJ4113-6HG40 1 1 unit 1AE 0.163
15 5SJ4118-6HG40 1 1 unit 1AE 0.168
16 5SJ4116-6HG40 1 1 unit 1AE 0.168
20 5SJ4120-6HG40 1 1 unit 1AE 0.164
25 5SJ4125-6HG40 1 1 unit 1AE 0.166
30 5SJ4130-6HG40 1 1 unit 1AE 0.166
32 5SJ4132-6HG40 1 1 unit 1AE 0.164
35 5SJ4135-6HG40 1 1 unit 1AE 0.164
40 5SJ4140-6HG40 1 1 unit 1AE 0.167
45 5SJ4145-6HG40 1 1 unit 1AE 0.190
50 5SJ4150-6HG40 1 1 unit 1AE 0.170
60 5SJ4160-6HG40 1 1 unit 1AE 0.175
63 5SJ4163-6HG40 1 1 unit 1AE 0.175
1) 1 MW (modular width) = 18 mm.
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
Characteristic C Characteristic D
In Mounting DT Article No. Price PG DT Article No. Price PU PS*/ PG Weight
width www.siemens.com/ per PU www.siemens.com/ per PU (UNIT, P. unit per PU
product?Article No. product?Article No. SET, approx.
M)
A MW1) kg
Miniature circuit
breakers
"same polarity only"
3
1P, 240 V AC
0.3 1 5SJ4114-7HG40 1AE 5SJ4114-8HG40 1 1 unit 1AE 0.168
0.5 5SJ4105-7HG40 1AE 5SJ4105-8HG40 1 1 unit 1AE 0.168
1 5SJ4101-7HG40 1AE 5SJ4101-8HG40 1 1 unit 1AE 0.165
1.6 5SJ4115-7HG40 1AE 5SJ4115-8HG40 1 1 unit 1AE 0.162
2 5SJ4102-7HG40 1AE 5SJ4102-8HG40 1 1 unit 1AE 0.163
3 5SJ4103-7HG40 1AE 5SJ4103-8HG40 1 1 unit 1AE 0.162
4 5SJ4104-7HG40 1AE 5SJ4104-8HG40 1 1 unit 1AE 0.163
5 5SJ4111-7HG40 1AE 5SJ4111-8HG40 1 1 unit 1AE 0.161
6 5SJ4106-7HG40 1AE 5SJ4106-8HG40 1 1 unit 1AE 0.161
8 5SJ4108-7HG40 1AE 5SJ4108-8HG40 1 1 unit 1AE 0.164
10 5SJ4110-7HG40 1AE 5SJ4110-8HG40 1 1 unit 1AE 0.163
13 5SJ4113-7HG40 1AE 5SJ4113-8HG40 1 1 unit 1AE 0.163
15 5SJ4118-7HG40 1AE 5SJ4118-8HG40 1 1 unit 1AE 0.163
16 5SJ4116-7HG40 1AE 5SJ4116-8HG40 1 1 unit 1AE 0.159
20 5SJ4120-7HG40 1AE 5SJ4120-8HG40 1 1 unit 1AE 0.165
25 5SJ4125-7HG40 1AE 5SJ4125-8HG40 1 1 unit 1AE 0.161
30 5SJ4130-7HG40 1AE 5SJ4130-8HG40 1 1 unit 1AE 0.170
32 5SJ4132-7HG40 1AE 5SJ4132-8HG40 1 1 unit 1AE 0.168
35 5SJ4135-7HG40 1AE 5SJ4135-8HG40 1 1 unit 1AE 0.161
40 5SJ4140-7HG40 1AE 5SJ4140-8HG40 1 1 unit 1AE 0.165
45 5SJ4145-7HG40 1AE 5SJ4145-8HG40 1 1 unit 1AE 0.159
50 5SJ4150-7HG40 1AE 5SJ4150-8HG40 1 1 unit 1AE 0.171
60 5SJ4160-7HG40 1AE 5SJ4160-8HG40 1 1 unit 1AE 0.170
63 5SJ4163-7HG40 1AE 5SJ4163-8HG40 1 1 unit 1AE 0.169
Miniature circuit
breakers
1P, 240 V AC
0.3 1 5SJ4114-7HG41 1AE 5SJ4114-8HG41 1 1 unit 1AE 0.177
0.5 5SJ4105-7HG41 1AE 5SJ4105-8HG41 1 1 unit 1AE 0.175
1 5SJ4101-7HG41 1AE 5SJ4101-8HG41 1 1 unit 1AE 0.173
1.6 5SJ4115-7HG41 1AE 5SJ4115-8HG41 1 1 unit 1AE 0.169
2 5SJ4102-7HG41 1AE 5SJ4102-8HG41 1 1 unit 1AE 0.171
3 5SJ4103-7HG41 1AE 5SJ4103-8HG41 1 1 unit 1AE 0.171
4 5SJ4104-7HG41 1AE 5SJ4104-8HG41 1 1 unit 1AE 0.169
5 5SJ4111-7HG41 1AE 5SJ4111-8HG41 1 1 unit 1AE 0.169
6 5SJ4106-7HG41 1AE 5SJ4106-8HG41 1 1 unit 1AE 0.169
8 5SJ4108-7HG41 1AE 5SJ4108-8HG41 1 1 unit 1AE 0.166
10 5SJ4110-7HG41 1AE 5SJ4110-8HG41 1 1 unit 1AE 0.171
13 5SJ4113-7HG41 1AE 5SJ4113-8HG41 1 1 unit 1AE 0.174
15 5SJ4118-7HG41 1AE 5SJ4118-8HG41 1 1 unit 1AE 0.170
16 5SJ4116-7HG41 1AE 5SJ4116-8HG41 1 1 unit 1AE 0.175
20 5SJ4120-7HG41 1AE 5SJ4120-8HG41 1 1 unit 1AE 0.172
25 5SJ4125-7HG41 1AE 5SJ4125-8HG41 1 1 unit 1AE 0.170
30 5SJ4130-7HG41 1AE 5SJ4130-8HG41 1 1 unit 1AE 0.177
32 5SJ4132-7HG41 1AE 5SJ4132-8HG41 1 1 unit 1AE 0.177
35 5SJ4135-7HG41 1AE 5SJ4135-8HG41 1 1 unit 1AE 0.155
40 5SJ4140-7HG41 1AE 5SJ4140-8HG41 1 1 unit 1AE 0.175
45 5SJ4145-7HG41 1AE 5SJ4145-8HG41 1 1 unit 1AE 0.155
50 5SJ4150-7HG41 1AE 5SJ4150-8HG41 1 1 unit 1AE 0.177
60 5SJ4160-7HG41 1AE 5SJ4160-8HG41 1 1 unit 1AE 0.177
63 5SJ4163-7HG41 1AE 5SJ4163-8HG41 1 1 unit 1AE 0.177
1)
1 MW (modular width) = 18 mm.
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
Characteristic C Characteristic D
In Mount- DT Article No. Price PG DT Article No. Price PU PS*/ PG Weight
ing www.siemens.com/ per PU www.siemens.com/ per PU (UNIT, P. unit per PU
width product?Article No. product?Article No. SET, approx.
M)
A MW1) kg
3 Miniature circuit
breakers
2P, 240 V AC
0.3 2 5SJ4214-7HG41 1AE 5SJ4214-8HG41 1 1 unit 1AE 0.310
0.5 5SJ4205-7HG41 1AE 5SJ4205-8HG41 1 1 unit 1AE 0.341
1 5SJ4201-7HG41 1AE 5SJ4201-8HG41 1 1 unit 1AE 0.332
1.6 5SJ4215-7HG41 1AE 5SJ4215-8HG41 1 1 unit 1AE 0.310
2 5SJ4202-7HG41 1AE 5SJ4202-8HG41 1 1 unit 1AE 0.326
3 5SJ4203-7HG41 1AE 5SJ4203-8HG41 1 1 unit 1AE 0.328
4 5SJ4204-7HG41 1AE 5SJ4204-8HG41 1 1 unit 1AE 0.322
5 5SJ4211-7HG41 1AE 5SJ4211-8HG41 1 1 unit 1AE 0.325
6 5SJ4206-7HG41 1AE 5SJ4206-8HG41 1 1 unit 1AE 0.325
8 5SJ4208-7HG41 1AE 5SJ4208-8HG41 1 1 unit 1AE 0.333
10 5SJ4210-7HG41 1AE 5SJ4210-8HG41 1 1 unit 1AE 0.330
13 5SJ4213-7HG41 1AE 5SJ4213-8HG41 1 1 unit 1AE 0.329
15 5SJ4218-7HG41 1AE 5SJ4218-8HG41 1 1 unit 1AE 0.328
16 5SJ4216-7HG41 1AE 5SJ4216-8HG41 1 1 unit 1AE 0.329
20 5SJ4220-7HG41 1AE 5SJ4220-8HG41 1 1 unit 1AE 0.332
25 5SJ4225-7HG41 1AE 5SJ4225-8HG41 1 1 unit 1AE 0.334
30 5SJ4230-7HG41 1AE 5SJ4230-8HG41 1 1 unit 1AE 0.345
32 5SJ4232-7HG41 1AE 5SJ4232-8HG41 1 1 unit 1AE 0.340
35 5SJ4235-7HG41 1AE 5SJ4235-8HG41 1 1 unit 1AE 0.310
40 5SJ4240-7HG41 1AE 5SJ4240-8HG41 1 1 unit 1AE 0.343
45 5SJ4245-7HG41 1AE 5SJ4245-8HG41 1 1 unit 1AE 0.342
50 5SJ4250-7HG41 1AE 5SJ4250-8HG41 1 1 unit 1AE 0.340
60 5SJ4260-7HG41 1AE 5SJ4260-8HG41 1 1 unit 1AE 0.343
63 5SJ4263-7HG41 1AE 5SJ4263-8HG41 1 1 unit 1AE 0.339
Miniature circuit
breakers
3P, 240 V AC
0.3 3 5SJ4314-7HG41 1AE 5SJ4314-8HG41 1 1 unit 1AE 0.499
0.5 5SJ4305-7HG41 1AE 5SJ4305-8HG41 1 1 unit 1AE 0.465
1 5SJ4301-7HG41 1AE 5SJ4301-8HG41 1 1 unit 1AE 0.489
1.6 5SJ4315-7HG41 1AE 5SJ4315-8HG41 1 1 unit 1AE 0.482
2 5SJ4302-7HG41 1AE 5SJ4302-8HG41 1 1 unit 1AE 0.479
3 5SJ4303-7HG41 1AE 5SJ4303-8HG41 1 1 unit 1AE 0.487
4 5SJ4304-7HG41 1AE 5SJ4304-8HG41 1 1 unit 1AE 0.465
5 5SJ4311-7HG41 1AE 5SJ4311-8HG41 1 1 unit 1AE 0.484
6 5SJ4306-7HG41 1AE 5SJ4306-8HG41 1 1 unit 1AE 0.485
8 5SJ4308-7HG41 1AE 5SJ4308-8HG41 1 1 unit 1AE 0.491
10 5SJ4310-7HG41 1AE 5SJ4310-8HG41 1 1 unit 1AE 0.491
13 5SJ4313-7HG41 1AE 5SJ4313-8HG41 1 1 unit 1AE 0.487
15 5SJ4318-7HG41 1AE 5SJ4318-8HG41 1 1 unit 1AE 0.488
16 5SJ4316-7HG41 1AE 5SJ4316-8HG41 1 1 unit 1AE 0.490
20 5SJ4320-7HG41 1AE 5SJ4320-8HG41 1 1 unit 1AE 0.484
25 5SJ4325-7HG41 1AE 5SJ4325-8HG41 1 1 unit 1AE 0.491
30 5SJ4330-7HG41 1AE 5SJ4330-8HG41 1 1 unit 1AE 0.506
32 5SJ4332-7HG41 1AE 5SJ4332-8HG41 1 1 unit 1AE 0.510
35 5SJ4335-7HG41 1AE 5SJ4335-8HG41 1 1 unit 1AE 0.507
40 5SJ4340-7HG41 1AE 5SJ4340-8HG41 1 1 unit 1AE 0.498
45 5SJ4345-7HG41 1AE 5SJ4345-8HG41 1 1 unit 1AE 0.500
50 5SJ4350-7HG41 1AE 5SJ4350-8HG41 1 1 unit 1AE 0.523
60 5SJ4360-7HG41 1AE 5SJ4360-8HG41 1 1 unit 1AE 0.506
63 5SJ4363-7HG41 1AE 5SJ4363-8HG41 1 1 unit 1AE 0.504
1)
1 MW (modular width) = 18 mm.
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
Characteristic C Characteristic D
In Mount- DT Article No. Price PG DT Article No. Price PU PS*/ PG Weight
ing www.siemens.com/ per PU www.siemens.com/ per PU (UNIT, P. unit per PU
width product?Article No. product?Article No. SET, approx.
M)
A MW1) kg
Miniature circuit
breakers
1P, 480Y/277 V AC
3
0.3 1 5SJ4114-7HG42 1AE 5SJ4114-8HG42 1 1 unit 1AE 0.155
0.5 5SJ4105-7HG42 1AE 5SJ4105-8HG42 1 1 unit 1AE 0.179
1 5SJ4101-7HG42 1AE 5SJ4101-8HG42 1 1 unit 1AE 0.179
1.6 5SJ4115-7HG42 1AE 5SJ4115-8HG42 1 1 unit 1AE 0.174
2 5SJ4102-7HG42 1AE 5SJ4102-8HG42 1 1 unit 1AE 0.175
3 5SJ4103-7HG42 1AE 5SJ4103-8HG42 1 1 unit 1AE 0.173
4 5SJ4104-7HG42 1AE 5SJ4104-8HG42 1 1 unit 1AE 0.175
5 5SJ4111-7HG42 1AE 5SJ4111-8HG42 1 1 unit 1AE 0.171
6 5SJ4106-7HG42 1AE 5SJ4106-8HG42 1 1 unit 1AE 0.175
8 5SJ4108-7HG42 1AE 5SJ4108-8HG42 1 1 unit 1AE 0.175
10 5SJ4110-7HG42 1AE 5SJ4110-8HG42 1 1 unit 1AE 0.175
13 5SJ4113-7HG42 1AE 5SJ4113-8HG42 1 1 unit 1AE 0.175
15 5SJ4118-7HG42 1AE 5SJ4118-8HG42 1 1 unit 1AE 0.175
16 5SJ4116-7HG42 1AE 5SJ4116-8HG42 1 1 unit 1AE 0.173
20 5SJ4120-7HG42 1AE 5SJ4120-8HG42 1 1 unit 1AE 0.174
25 5SJ4125-7HG42 1AE 5SJ4125-8HG42 1 1 unit 1AE 0.174
30 5SJ4130-7HG42 1AE 5SJ4130-8HG42 1 1 unit 1AE 0.182
32 5SJ4132-7HG42 1AE 5SJ4132-8HG42 1 1 unit 1AE 0.155
35 5SJ4135-7HG42 1AE --
40 5SJ4140-7HG42 1AE --
Miniature circuit
breakers
2P, 480Y/277 V AC
0.3 2 5SJ4214-7HG42 1AE 5SJ4214-8HG42 1 1 unit 1AE 0.346
0.5 5SJ4205-7HG42 1AE 5SJ4205-8HG42 1 1 unit 1AE 0.342
1 5SJ4201-7HG42 1AE 5SJ4201-8HG42 1 1 unit 1AE 0.338
1.6 5SJ4215-7HG42 1AE 5SJ4215-8HG42 1 1 unit 1AE 0.335
2 5SJ4202-7HG42 1AE 5SJ4202-8HG42 1 1 unit 1AE 0.335
3 5SJ4203-7HG42 1AE 5SJ4203-8HG42 1 1 unit 1AE 0.330
4 5SJ4204-7HG42 1AE 5SJ4204-8HG42 1 1 unit 1AE 0.335
5 5SJ4211-7HG42 1AE 5SJ4211-8HG42 1 1 unit 1AE 0.330
6 5SJ4206-7HG42 1AE 5SJ4206-8HG42 1 1 unit 1AE 0.334
8 5SJ4208-7HG42 1AE 5SJ4208-8HG42 1 1 unit 1AE 0.339
10 5SJ4210-7HG42 1AE 5SJ4210-8HG42 1 1 unit 1AE 0.338
13 5SJ4213-7HG42 1AE 5SJ4213-8HG42 1 1 unit 1AE 0.334
15 5SJ4218-7HG42 1AE 5SJ4218-8HG42 1 1 unit 1AE 0.337
16 5SJ4216-7HG42 1AE 5SJ4216-8HG42 1 1 unit 1AE 0.334
20 5SJ4220-7HG42 1AE 5SJ4220-8HG42 1 1 unit 1AE 0.342
25 5SJ4225-7HG42 1AE 5SJ4225-8HG42 1 1 unit 1AE 0.338
30 5SJ4230-7HG42 1AE 5SJ4230-8HG42 1 1 unit 1AE 0.342
32 5SJ4232-7HG42 1AE 5SJ4232-8HG42 1 1 unit 1AE 0.350
35 5SJ4235-7HG42 1AE --
40 5SJ4240-7HG42 1AE --
1)
1 MW (modular width) = 18 mm.
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
Characteristic C Characteristic D
In Mount- DT Article No. Price PG DT Article No. Price PU PS*/ PG Weight
ing www.siemens.com/ per PU www.siemens.com/ per PU (UNIT, P. unit per PU
width product?Article No. product?Article No. SET, approx.
M)
A MW1) kg
3 Miniature circuit
breakers
3P, 480Y/277 V AC
0.3 3 5SJ4314-7HG42 1AE 5SJ4314-8HG42 1 1 unit 1AE 0.510
0.5 5SJ4305-7HG42 1AE 5SJ4305-8HG42 1 1 unit 1AE 0.529
1 5SJ4301-7HG42 1AE 5SJ4301-8HG42 1 1 unit 1AE 0.507
1.6 5SJ4315-7HG42 1AE 5SJ4315-8HG42 1 1 unit 1AE 0.495
2 5SJ4302-7HG42 1AE 5SJ4302-8HG42 1 1 unit 1AE 0.495
3 5SJ4303-7HG42 1AE 5SJ4303-8HG42 1 1 unit 1AE 0.492
4 5SJ4304-7HG42 1AE 5SJ4304-8HG42 1 1 unit 1AE 0.488
5 5SJ4311-7HG42 1AE 5SJ4311-8HG42 1 1 unit 1AE 0.485
6 5SJ4306-7HG42 1AE 5SJ4306-8HG42 1 1 unit 1AE 0.491
8 5SJ4308-7HG42 1AE 5SJ4308-8HG42 1 1 unit 1AE 0.500
10 5SJ4310-7HG42 1AE 5SJ4310-8HG42 1 1 unit 1AE 0.497
13 5SJ4313-7HG42 1AE 5SJ4313-8HG42 1 1 unit 1AE 0.500
15 5SJ4318-7HG42 1AE 5SJ4318-8HG42 1 1 unit 1AE 0.496
16 5SJ4316-7HG42 1AE 5SJ4316-8HG42 1 1 unit 1AE 0.497
20 5SJ4320-7HG42 1AE 5SJ4320-8HG42 1 1 unit 1AE 0.498
25 5SJ4325-7HG42 1AE 5SJ4325-8HG42 1 1 unit 1AE 0.502
30 5SJ4330-7HG42 1AE 5SJ4330-8HG42 1 1 unit 1AE 0.514
32 5SJ4332-7HG42 1AE 5SJ4332-8HG42 1 1 unit 1AE 0.511
35 5SJ4335-7HG42 1AE --
40 5SJ4340-7HG42 1AE --
1)
1 MW (modular width) = 18 mm.
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
■ Accessories
Pin spacing Length DT Article No. Price PU PS*/ PG Weight
www.siemens.com/ per PU (UNIT, P. unit per PU
product?Article No. SET, approx.
M)
MW1)
3
mm kg
Busbars acc. to UL 489 specially for 5SJ4…-.HG.. miniature circuit
breakers, fixed lengths, cannot be cut2), UL File E321559
Single-phase
For 6 MCBs 1P 1 100 5ST3663-0HG 1 10 units 1AE 0.058
For 12 MCBs 1P 205 5ST3663-1HG 1 10 units 1AE 0.115
For 18 MCBs 1P 310 5ST3663-2HG 1 10 units 1AE 0.173
Two-phase
For 3 MCBs 2P 1 100 5ST3664-0HG 1 10 units 1AE 0.067
For 6 MCBs 2P 205 5ST3664-1HG 1 10 units 1AE 0.138
For 9 MCBs 2P 310 5ST3664-2HG 1 10 units 1AE 0.212
Three-phase
For 2 MCBs 3P 1 100 5ST3665-0HG 1 10 units 1AE 0.069
For 4 MCBs 3P 205 5ST3665-1HG 1 10 units 1AE 0.156
For 6 MCBs 3P 310 5ST3665-2HG 1 10 units 1AE 0.249
Busbars acc. to UL 489 specially for 5SJ4…-.HG.. miniature circuit
breakers, can be cut, UL File E315616
Single-phase
For MCBs 1P 1 1016 5ST3701-3HG 1 1 unit 1AE 0.820
For MCBs 1P with AS or FC 1016 5ST3703-3HG 1 1 unit 1AE 0.710
Two-phase
For MCBs 2P 1 1016 5ST3705-3HG 1 1 unit 1AE 1.010
For MCBs 2P with AS or FC 1016 5ST3707-3HG 1 1 unit 1AE 0.990
Three-phase
For MCBs 3P 1 1016 5ST3710-3HG 1 1 unit 1AE 1.230
For MCBs 3P with AS or FC 1+1+1.5 1016 5ST3712-3HG 1 1 unit 1AE 1.170
For MCBs 3x 1016 5ST3714-3HG 1 1 unit 1AE 1.160
(1P with AS or FC)
Note
For the UL 489 busbars that can be cut, use only the
associated separate infeed, end cap and touch protection
cover.
Terminals according to UL 489
Infeed at the miniature circuit breaker
• Specially for 5SJ4...-.HG.. miniature circuit breakers 5ST3666-0HG 1 10 units 1AE 0.036
• Max. 35 mm2
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
Padlocks
For 5ST3801 handle locking device 5ST3802 1 1 unit 1AD 0.033
1)
1 MW (modular width) = 18 mm.
5SJ4 . . . - . HG miniature circuit breakers acc. to UL 489 and IEC, and accessories
■ More information
Mounting concept for mounting 5ST30. .-0HG accessories on
5SJ4. . .-.HG miniature circuit breakers
The diagram shows which additional components can be
mounted on the right.
3
2 auxiliary switches (AS) or fault signal contacts (FC) can
be mounted to the right of the miniature circuit breaker
(MCB) in any combination
5ST30.
5SJ4 ...-.HG.. or or or
AS FC AS AS AS FC
FC FC FC AS
I201_18121
MCB
or or or
ST AS FC AS AS AS FC
FC FC FC AS
Max. 1 shunt trip (ST) can be mounted on the right of the
miniature circuit breaker (MCB). 2 auxiliary switches (AS)
or fault signal contacts (FC) can also be mounted to the
right of the ST in any combination
■ Overview ■ Benefits
The selective main miniature circuit breaker is used as a circuit • Quick and easy installation on busbar and standard mounting
breaker on meter panels. rail
Characteristic E is adapted to the special application require- • Reliable and high selectivity
ments for cascade circuits between melting fuses and miniature • Optimum availability of the consumer load
3 circuit breakers in distributor circuits.
Used in conjunction with downstream miniature circuit breakers,
• The SHU 5SP3 main miniature circuit breaker operates on a
voltage-independent basis
SHU 5SP3 main miniature circuit breakers ensure effective • High and safe selectivity between sub-distribution and meter
protection and optimum availability of the plant. panel ensures the continued supply of the unaffected circuits
in the event of a fault, thus improving system availability
• In the event of a fault, the SHU 5SP3 main miniature circuit
breaker prevents an existing short-circuit from being recon-
nected until the cause of the fault has been eliminated
• The SHU 5SP3 selective main miniature circuit breaker
ensures fast and safe disconnection and reconnection of
loads
• It complies with all the requirements of TAB 2007 and can
therefore be used in metering systems
■ Technical specifications
5SP37. ., 5SP37. .-1 5SP37. .-2, 5SP38. .-2
5SP37. .-2KK0.
Standards DIN VDE 0645 DIN VDE 0641-21
Rated voltage Un
• 1-pole V AC 230/400 --
• 3 x 1-pole V AC 400 -- 400
Operational voltage Min. V AC 110
Max. V AC 440
Rated frequency Hz 50 ... 60
Rated current In A 16 ... 100 16 ... 63
Rated insulation voltage Ui V AC 690
Rated making and breaking capacity Icn A 25000
Insulation coordination
• Overvoltage category IV
• Pollution degree 3
Surge strength Uimp kV 6
Impact resistance 30 g, at least 3 impacts, impact duration 11 ms
Resistance to vibrations 2 g, 20 frequency cycles 5 ... 150 ... 15 Hz
Switching position indication OFF = green, ON = red
Main switch characteristics Acc. to EN 60204-1 Yes
Handle end position, sealable Yes
Cutoff ON/OFF -- Locking slide with lock, additional wire seal, cable
ties and Antilux
Device depth mm 92
Degree of protection IP20 with connected conductors
Mains connection Any
Mounting position Any
Mounting On standard mounting rail Direct tool-free mounting on the busbar system
or interface adapter
Service life, on average, with rated load Actuations 20000
Wire connections Saddle terminals at both
ends
• Top Screwless spring terminal for flexible cables,
in particular for meter connecting cables acc. to
DIN 43870-3
• Bottom Box terminal, also for infeed to the busbar system,
up to 100 A infeed current
Conductor cross-sections
• Top and bottom, solid and stranded mm2 2.5 ... 70 --
• Top and bottom, finely stranded mm2 2.5 ... 50 --
• Top, finely stranded mm2 -- 2.5 ... 16
• Bottom, solid, stranded and finely stranded, with end sleeve mm2 -- 2.5 ... 50
Storage temperature °C -40 ... +70
Ambient temperature °C -25 ... +55
1)
1 MW (modular width) = 18 mm.
Mounting plates
For mounting on standard mounting rails according to
EN 50022
For 1 or 2 standard mounting rails, universal application, } 5ST1322 1 10 units 1AE 0.030
tier spacing 125 mm
1)
1 MW (modular width) = 18 mm.
Notes