Data sheet                                                                                                                    5SY4216-7
Miniature circuit breaker 400 V 10kA, 2-pole, C, 16A, D=70 mm
Model
 product brand name                                            SENTRON
 product designation                                           Miniature circuit breaker
General technical data
 number of poles                                               2
 design of pole                                                2P
 tripping characteristic class                                 C
 mechanical service life (operating cycles) typical            10 000
 overvoltage category                                          3
 degree of pollution                                           3
Voltage
 type of voltage of the operating voltage                      AC
 insulation voltage (Ui)
     ● with single-phase operation at AC rated value           440 V
     ● with multi-phase operation at AC rated value            440 V
 supply voltage with single-phase operation at AC rated        230 V
 value
     ● operational current
          — at 40 °C rated value                               15.02 A
          — at 50 °C rated value                               13.98 A
          — at 55 °C rated value                               13.44 A
          — at 60 °C rated value                               12.86 A
     ● operational current at AC rated value                   16 A
Supply voltage
 supply voltage
     ● at AC                                                   400 V
     ● at DC rated value                                       60 V
 value range of the supply voltage frequency                   50/60 Hz
 operating voltage at DC rated value maximum                   72 V
Protection class
 protection class IP                                           IP20, with connected conductors
Breaking Capacity
 switching capacity current
     ● at DC according to IEC 60947-2 rated value              15 kA
     ● according to EN 60898 rated value                       10 kA
     ● according to IEC 60947-2 rated value                    20 kA
 energy limitation class                                       3
Dissipation
 power loss [W] for rated value of the current at AC in hot    1.6 W
5SY42167                                                                                                Subject to change without notice
                                                              8/21/2025
Page 1/6                                                                                                           © Copyright Siemens
 operating state per pole
 suitability for operation                                     Infrastructure / Industry
Product details
 product feature touch protection                              Yes
 product component
      ● combined terminal top                                  Yes
      ● combined terminal bottom                               Yes
      ● neutral conductor switching                            No
 product feature properties for main switches in accordance    Yes
 with EN 60204-1
 product feature halogen-free                                  Yes
 product feature sealable                                      Yes
 product feature silicon-free                                  Yes
 product extension installable supplementary devices           Yes
Product function
 set values setting current (Ii) for I-tripping                8
 reference value setting current (Ii) for I-tripping           x In
Short circuit
 short-circuit current breaking capacity (Icn)
      ● at AC according to UL 1077 and CSA C22.2 No.235        5 kA
Connections
 connectable conductor cross-section solid
      ● minimum                                                0.75 mm²
      ● maximum                                                35 mm²
 connectable conductor cross-section stranded
      ● minimum                                                0.75 mm²
      ● maximum                                                35 mm²
 connectable conductor cross-section finely stranded with
 core end processing
      ● minimum                                                0.75 mm²
      ● maximum                                                25 mm²
 AWG number as coded connectable conductor cross
 section
      ● minimum                                                18
      ● maximum                                                4
 tightening torque [lbf·in] with screw-type terminals
      ● minimum                                                22 lbf·in
      ● maximum                                                31 lbf·in
 tightening torque with screw-type terminals
      ● minimum                                                2.5 N·m
      ● maximum                                                3.5 N·m
 position of power supply cord                                 Any
Mechanical Design
 height                                                        90 mm
 width                                                         36 mm
 depth                                                         76 mm
 installation depth                                            70 mm
 fastening method                                              DIN rail
 mounting position                                             any
 Net Weight                                                    298 g
Environmental conditions
 influence of the surrounding temperature                      max. 95% RH up to 55°C, max. 55% RH up to 70°C, max. 35% RH up to 75°C
 standard                                                      IEC / EN 60898-1, IEC / EN 60947-2 / UL1077
 vibration resistance according to IEC 60068-2-6               ±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz
 ambient temperature during operation
      ● minimum                                                -40 °C
      ● maximum                                                70 °C
 ambient temperature during storage
      ● minimum                                                -40 °C
      ● maximum                                                75 °C
 number of test cycles for environmental testing according     6
 to IEC 60068-2-30
5SY42167                                                                                              Subject to change without notice
                                                              8/21/2025
Page 2/6                                                                                                         © Copyright Siemens
Environmental footprint
 Environmental Product Declaration(EPD)                                  Yes
 global warming potential [CO2 eq] total                                 16.8 kg
 global warming potential [CO2 eq] during manufacturing                  1.13 kg
 global warming potential [CO2 eq] during operation                      15.7 kg
 global warming potential [CO2 eq] after end of life                     -0.00046 kg
Approvals Certificates
  General Product Approval
  General Product Approval                                                                         EMV                 Test Certificates
     Miscellaneous                  KC                                                                                 Special Test Certific-
                                                                                                                                ate
  Test Certificates        Maritime application
     Miscellaneous
  other                                                Railway                                     Environment
                               Confirmation            Special Test Certific-       Confirmation                       Environmental Con-
                                                                ate                                                         firmations
  Environment
  Environmental Con-
       firmations
Further information
 Information on the packaging
 https://support.industry.siemens.com/cs/ww/en/view/109813875
 Information- and Downloadcenter (Catalogs, Brochures,…)
 http://www.siemens.com/lowvoltage/catalogs
 Industry Mall (Online ordering system)
 https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=5SY4216-7
 Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
 https://support.industry.siemens.com/cs/ww/en/ps/5SY4216-7
 Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
 http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=5SY4216-7
 CAx-Online-Generator
 http://www.siemens.com/cax
 Tender specifications
 http://www.siemens.com/specifications
5SY42167                                                                                                  Subject to change without notice
                                                                        8/21/2025
Page 3/6                                                                                                             © Copyright Siemens
       89,8   35,2                  6,2       69,8
                     -F
                          2
5SY42167                                      Subject to change without notice
                              8/21/2025
Page 4/6                                                 © Copyright Siemens
           CB
                 1                          2
                 3                          4
last modified:       8/6/2025
5SY42167                         Subject to change without notice
                     8/21/2025
Page 5/6                                    © Copyright Siemens
5SY42167               Subject to change without notice
           8/21/2025
Page 6/6                          © Copyright Siemens