Reyrolle High

Speed Trip Relay


Catalog Reyrolle 7PJ15 · Edition 3

siemens.com/reyrolle
2 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Content

Digital Grid Devices and Application 1

Reyrolle High Speed Trip Relay Selection Guide 1.1

Relay (7PJ15) Catalog 7PJ15 High Speed Trip Relay 1.2

System 2

Protection 2.1

Monitoring 2.2

Hardware Construction 2.3

Technical Documentation 3

Connection Diagrams 3.1

Dimension Drawings 3.2

Technical Data 3.3

Ordering Information 3.4

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 3
Devices and Application
Relay Selection Guide

Relay Selection Guide

ANSI Functions

7PJ1521

7PJ1524
1.1

86 Lock out relay, Master trip relay ● ●


Number of contacts 10 6 or 10 or 20
Contact reset arrangement Self Hand and Electrical
Operating coil cut-off Economy Instantaneous
Case size E2 E2 or E4
Flag indications 1 1
Flag reset arrangement Hand Hand

4 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Devices and Application
7PJ15 High Speed Trip Relay

Description
The 7PJ1521 and 7PJ1524 High Speed Trip relay is a
multi-contact attracted armature relay designed to IEC 60255.
High burden relays with immunity to capacitance discharge
currents. They are also suitable for certain applications where 1.2
they are remote from the initiation signal.
A high burden also permits reliable operation of current oper-
ated series repeat relays. TR relays can be provided with an
instantaneous or time-delayed cut-off.

Benefits
The features of the High Speed Trip Relay are:
• High speed, high burden, positive action, and instantaneous
cutoff.
• The 7PJ1524 trip relay can be used with the Trip Circuit Super-
vision relay (7PJ13) to monitor and supervise the integrity of
the trip circuit with coil supervision terminal.
• It is supplied in a draw-out type case.

[7PJ15_FrontView, 1, --_--]

• Tripping of multiple circuit-breakers


• Tripping and lock out application of feeder and transformer
circuit-breakers
• Control signaling and interlocking
• Inter tripping and remote tripping interface for SCADA

[sc_7PJ15_drawout, 1, --_--]

• The relay has a robust design for a long, reliable service life.
Applications
The high speed trip relay type 7PJ15 is mainly used for all types
of control and protection circuits in power stations and indus-
trial applications, where a higher grade of reliability and high
contact rating is stipulated. The 7PJ15 relay acts as a high speed
element and contact multiplication in tripping and signaling
circuits of protective relays.
The high speed trip relay is used in the following applications:

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 5
System
Hardware Construction

Hardware Construction
The device is housed in a draw-out case designed for panel
mounting.
The rear connection comprises of screw type, fixed terminals.

2.3

[sc_7PJ15_E4, 1, en_US]

Figure 2.3/3 Size E4

[sc_7PJ15_drawoutphoto, 1, --_--]

Figure 2.3/1 7PJ15 Including Handles

NOTE

i All other photographs in this document show the


device with handles removed for uninterrupted
views.

[sc_7PJ15 side label, 1, en_US]

Figure 2.3/4 Side Label

Relay Information
The device fascia displays the MLFB order code, serial number,
and device identification reference.
The device terminal label displays the MLFB code, serial number,
relay description, terminal contact details, and safety symbols.

QR code

AC 2 kV insulation test of reset coil, trip


coil, and output contacts
[sc_7PJ15_E2, 1, en_US]
5 kV impulse voltage test (type test) in
Figure 2.3/2 Size E2 compliance with Class III

Electrical Hazard

European CE marking

Refer to device documentation

Waste Electrical and Electronic Equip-


ment Directive (WEEE)

6 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Connection Diagrams

3.1

[lo_7PJ15_10contactswiringdiagram, 1, en_US]

Figure 3.1/1 7PJ1521 (10 Contacts Self Reset Trip Relay) Wiring Diagram

Trip + ve 27
coil - ve 28
supply
Coil supervi- 24
sion
Contact config- Output Contact Pair / Terminal Number
uration 1–3 2–4 5–7 6–8 9– 10– 13– 14– 17– 21–
11 12 15 16 19 23
10M + 0B M M M M M M M M M M
8M + 2B B B M M M M M M M M
6M + 4B B B B B M M M M M M

Table 3.1/1 7PJ1521 (10 Contacts Self Reset Trip Relay) Terminal Details

DC 125 V Relay R1-2X 100R, 12 W


R2-2X 3.9K, 12 W
R3-1X 270R, 6 W
DC 240 V Relay R1-1X 470R, 12 W
R2-1X 2.2K, 12 W
R2-1X 4.7K, 12 W
R3-1X 270R, 6 W [sc_7PJ15_10contactsterminaldiagram1, 1, --_--]

Figure 3.1/2 7PJ1521 (10 Contacts Self Reset Trip Relay) Terminal
Table 3.1/2 7PJ1521 (10 Contacts Self Reset Trip Relay) Resistor Details Diagram

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 7
Technical Documentation
Connection Diagrams

3.1

[lo_7PJ15_6/10contactswiringdiagram, 1, en_US]

Figure 3.1/3 7PJ1524 (6/10 Contacts Hand Reset and Electrical Reset Trip Relay) Wiring Diagram

Trip + ve 27
coil - ve 28
supply
Reset + ve 25
coil - ve 26
supply
Coil supervi- 24
sion
Contact config- Output Contact Pair / Terminal Number
uration 1–3 2–4 5–7 6–8 9– 10– 13– 14– 17– 18–
11 12 15 16 19 20
8M + 2B B B M M M M M M M M
6M + 4B B B B B M M M M M M
4M + 2B B B M M M M – – – –
5M + 1B B – M M M M M – – –
6M + 0B – – M M M M M M – –

Table 3.1/3 7PJ1524 (6/10 Contacts Hand Reset and Electrical Reset Trip
Relay) Terminal Details

DC 125 V Relay R1-2X 100R


DC 240 V Relay R1-1X 470R, 14 W
[sc_7PJ15_610contactsterminaldiagram1, 1, --_--]
R2-1X 470R, 3 W
Figure 3.1/4 7PJ1524 (6/10 Contacts Hand Reset and Electrical Reset
Trip Relay) Terminal Diagram
Table 3.1/4 7PJ1524 (6/10 Contacts Hand Reset and Electrical Reset Trip
Relay) Resistor Details

8 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Connection Diagrams

3.1

[lo_7PJ15_20contactswiringdiagram, 1, en_US]

Figure 3.1/5 7PJ1524 (20 Contacts hand Reset and electrical reset Trip Relay) Wiring Diagram

Trip coil + ve B 27
supply - ve B 28
Reset + ve B 25
coil - ve B 26
supply
Coil supervi- B 24
sion
Contact config- "A" Block Output Contact Pair / Terminal Number
uration 1–3 2–4 5–7 6–8 9– 10– 13– 14– 17– 18–
11 12 15 16 19 20
18M + 2B M B M M M M M M M M
16M + 4B B B M M M M M M M M
Contact config- "B" Block Output Contact Pair / Terminal Number
uration 1–3 2–4 5–7 6–8 9– 10– 13– 14– 17– 18–
11 12 15 16 19 20
18M + 2B M B M M M M M M M M
16M + 4B B B M M M M M M M M

Table 3.1/5 7PJ1524 (20 Contacts Hand Reset and Electrical Reset Trip
Relay) Terminal Details

DC 125 V Relay No resistor [sc_7PJ15_20contactsterminaldiagram1, 1, --_--]


DC 240 V Relay R1&R2 – 470R, 14 W
Figure 3.1/6 7PJ1524 (20 Contacts Hand Reset and Electrical Reset Trip
R3&R4 – 470R, 3 W Relay) Terminal Diagram

Table 3.1/6 7PJ1524 (20 Contacts Hand Reset and Electrical Reset Trip
Relay) Resistor Details

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 9
Technical Documentation
Dimension Drawings

Dimension Drawings
This section displays the different dimensional views of a High
Speed Trip Relay.

3.2

[sc_E2casing, 1, en_US]

Figure 3.2/1 E2 Case

10 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Dimension Drawings

3.2

[sc_E4casing, 1, en_US]

Figure 3.2/2 E4 Case

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 11
Technical Documentation
Technical Data

Technical Data DC 125 V ≤ 50 ≤ 70


For full technical data refer to the Performance Specification DC 240 V ≤ 70 ≤ 150
Chapter of the Technical Manual.
Contact Ratings
Indication of Conformity

Make and carry AC 1250 VA or DC 1250 W within limits of


This product complies with the directive of the
continuously 660 V and 5 A
Council of the European Communities on the harmo-
nization of the laws of the Member States relating to Short time AC 30 A or DC 30 A for 0.5 s
concerning electrical equipment for use within speci- Make and carry for 3 s AC 7500 VA or DC 7500 W within limits of
fied voltage limits (Low Voltage Directive 660 V and 30 A
2014/35/EU) as well as restriction on usage of Limiting making 1000 W within limits of 250 V
hazardous substances in electrical and electronic capacity (L/R ≤ 40 ms)
equipment (RoHS Directive 2011/65/EU).
Limiting breaking
This conformity has been proved by tests conducted capacity
by Siemens AG in accordance of the Council Directive 1250 VA V/I = 250/5
AC resistive
in accordance with the product standard IEC/EN
60255-27 for the low-voltage directive. DC resistive 100 W V/I = 48/2.09;

RoHS directive 2011/65/EU is met using the standard 110/0.91;


EN 50581. The device has been designed and 250/0.4
produced for industrial use. DC inductive (L/R ≤ 40 50 W
V/I = 48/1.042;
ms)
General Technical Data 110/0.454;

3.3 250/0.2
Parameter Value Electrical endurance 10,000 operations
Operating time 10 ms at rated voltage Vrated Switching rate 600 operations per hour
Reset time < 20 ms at rated voltage Vrated (electrical
reset) Mechanical Tests
Drop-off time < 20 ms (self reset)
Rated voltage Vrated Test Reference Requirement
DC 125 V, DC 240 V 1
Vibration IEC 60255-21-1 Response and endurance
Operating range 50 % to 120 % of rated voltage Vrated 2
Class I
Contact reset arrangement Self
(7PJ1521) Shock and bump IEC 60255-21-2 Shock response and with-
stand
Contact reset arrangement Hand and Electrical
(7PJ1524) Class I
Flag reset arrangement Hand Bump Class I
Seismic IEC 60255-21-3 Class I
7PJ1521 Nominal Burden (Self Reset) Degree of protec- IEC 60529 IP50 – Front
tion
IP10 – Rear
Operate Coil Burden (W)
Rated voltage Nominal burden (W) Burden (W) after oper-
to operate ation of economy
circuit
DC 125 V ≤ 150 ≤ 10
DC 240 V ≤ 180 ≤ 10

7PJ1524 Nominal Burden (Hand and Electrical Reset)

Operate Coil Burden (W)


Rated voltage 10 Contacts 20 Contacts
DC 125 V ≤ 150 ≤ 180
DC 240 V ≤ 180 ≤ 180
Reset Coil Burden (W)
Rated voltage 10 Contacts 20 Contacts

1 10 contacts - DC 240 V, 20 contacts - DC 125 V and DC 240 V, product variants are not part of the ENA TS 48-4.
2 Operating coils of self-reset and economy cut-off relays are rated at 120 % of rated voltage. All other operate and rest coils are short time rated well in
excess of the operating time of their cut-off contacts. Self-reset relays will reset at not less than 5 % rated voltage.

12 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Technical Data

Electrical Tests Product Safety Test

Test Standard Test Standard


Insulation resistance IEC 60255-27 3 Clearances and creepage distances IEC 60255-27
Insulation resistance > 100 MΩ at IP rating
DC 500 V Impulse voltage
Between all terminals and earth AC or DC dielectric voltage
Insulation resistance
Between coil terminals and
contacts Protective bonding continuity
Impulse voltage withstand IEC 60255-27 3 Protective bonding resistance

5 kV, 1.2/50 μs, 0.5 J Flammability of insulating mate-


rials, components and fire enclo-
5 +ve, -ve pulses sures
Between all terminals and earth Single fault condition
Between coil terminals and Mechanical resistance to shock and IEC 61010-1
contacts impact
High voltage (Dielectric) IEC 60255-27 3 Protection against electric shock
Protection against the spread of
2 kV, 50 Hz@1 min
fire
Between all terminals and earth Equipment temperature limits and
Between coil terminals and resistance to heat
contacts
3.3
AC 1 kV, 50 Hz @ 1 min across Climatic Environmental Tests
make contacts
Temperature
Thermal withstand continuous 4 IEC 60255-6
IEC 60068-2-1/IEC 60068-2-2/IEC 60068-2-14/IEC 60255-1
1.2 Vrated
Functional performance IEC 60255-1 Ambient operating temperature -10 °C to +55 °C
Maximum allowable temperature IEC 60255-6 Storage temperature (non-opera- -25 °C to +70 °C
Maximum temperature limit tional)
+ 100 °C Change of temperature Cyclic: 3 h at -10 °C to 3 h at +55°C
AC ripple on DC supply IEC 61000-4-17 Number of cycles: 5
Withstand 15 % AC ripple on DC
Power frequency magnetic field IEC 61000-4-8 Level 4, Humidity
30 A/m applied continuously IEC 60068-2-30/IEC 60068-2-78/IEC 60255-1
300 A/m applied for 3 s
Damped oscillatory magnetic field IEC 61000-4-10, Level 5 Damp heat test, cyclic 6 days at +25 °C to +55 °C (12 h +
value 12 h cycle) and 93 % relative
0.1 and 1.0 MHz,100 A/m humidity
Impulse magnetic field immunity IEC 61000-4-9, Level 5 Damp heat steady state test 10 days at +40 °C and 95 %
test humidity
1000 A/m, +/- 5 pulses
Immunity to capacitance discharge ENA TS 48-4 Maximum altitude of operation Up to 2000 m
Issue 4 2010
Installation Category
Refer to General Technical Data1.

Installation category (overvoltage Class III


category)

Pollution

Pollution degree 2

3 All aspect of IEC 60255-5 have been covered under IEC 60255-27.
4 Applicable for self reset type trip relays

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 13
Technical Documentation
Ordering Information

Ordering Information – 7PJ1521

Product Description Order Number


1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
High Speed Trip Relay 7 P J 1 5 2 1 – 2 □ □ 6 0 – 1 A □ 0
High speed trip, high burden with contact type (self reset) and hand reset flag | | | | | | | | | |
| | | | | | | | | |
TR – Tripping | | | | | | | | | |
TR2: High burden, EB2 2 | | | | | | | | |
| | | | | | | | |
Contact Operation | | | | | | | | |
Self reset contacts 1 | | | | | | | |
| | | | | | | |
Operating Coil Cut-Off | | | | | | | |
Economy 2 | | | | | | |
| | | | | | |
Contact Arrangement – Make Contact | | | | | | |
6 Make contact G E | | | | |
8 Make contact J C | | | | |
10 Make contact L A | | | | |
| | | | | |
Contact Arrangement – Break Contact | | | | | |
3.4 0 Break contact A | | | | |
1 Break contact B | | | | |
2 Break contact C | | | | |
4 Break contact E | | | | |
| | | | |
Number of Contacts 5 | | | | |
6/10 6 | | | |
| | | |
Contact Type | | | |
Make contact (standard) / Break contact (standard) 0 | | |
| | |
Type of Flag | | |
Hand reset flag 1 | |
| |
Housing Size | |
Case size E2 (4U high) A |
|
Voltage Rating |
DC 125 V F
DC 240 V H

5 The number of contacts must match the selected contact arrangement.

14 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Technical Documentation
Ordering Information

Ordering Information – 7PJ1524

Product Description Order Number


1 2 3 4 5 6 7 – 8 9 10 11 12 – 13 14 15 16
High Speed Trip Relay 7 P J 1 5 2 4 – 1 □ □ □ 0 – 1 □ □ 0
High speed trip, high burden with contact type (hand reset and electrical reset) and | | | | | | | | | |
hand reset flag
| | | | | | | | | |
TR – Tripping | | | | | | | | | |
TR2: High burden 2 | | | | | | | | |
| | | | | | | | |
Contact Operation | | | | | | | | |
Hand and electrical reset contacts 4 | | | | | | | |
| | | | | | | |
Operating Coil Cut-Off | | | | | | | |
Instantaneous 1 | | | | | | |
| | | | | | |
Contact Arrangement – Make Contact | | | | | | |
4 Make contact E C 6 | | | |
5 Make contact F B 6 | | | |
6 Make contact G A 6 | | | |
6 Make contact G E 6 | | | |
8 Make contact J C 6 | | | | 3.4
16 Make contact S E 8 | | | |
18 Make contact U C 8 | | | |
| | | | | |
Contact Arrangement – Break Contact | | | | | |
0 Break contact A | | | | |
1 Break contact B | | | | |
2 Break contact C | | | | |
4 Break contact E | | | | |
| | | | |
Number of Contacts 6 | | | | |
6/10 6 | | A |
20 8 | | C |
| | | |
Contact Type | | | |
Make contact (standard) / Break contact (standard) 0 | | |
| | |
Type of Flag | | |
Hand reset flag 1 | |
| |
Housing Size | |
Case size E2 (4U high) A |
Case size E4 (4U high) C |
|
Voltage Rating |
DC 125 V F
DC 240 V H

6 The number of contacts must match the selected contact arrangement.

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 15
Technical Documentation
Ordering Information

3.4

16 Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices
Appendix
Legal notice

Indication of conformity Copyright

This product complies with the directive Copyright © Siemens AG 2019. All rights
of the Council of the European reserved. The disclosure, duplication,
Communities on harmonization of the distribution and editing of this document, or
laws of the Member States relating to utilization and communication of the content
concerning electrical equipment for use within are not permitted, unless authorized in
specified voltage limits (Low Voltage Directive writing. All rights, including rights created by
2014/35/EU) as well as restriction on usage of patent grant or registration of a utility model
hazardous substances in electrical and electronic
equipment (RoHS Directive 2011/65/EU). or a design, are reserved.
This conformity has been proved by tests conducted
by Siemens AG in accordance of the Council Directive
in accordance with the product standard IEC/EN
60255-27 for the low-voltage directive.
RoHS directive 2011/65/EU is met using the standard
EN 50581. The device has been designed and
produced for industrial use.

Disclaimer of liability
This document has been subjected to rigorous
technical review before being published. It is revised
at regular intervals, and any modifications and
amendments are included in the subsequent issues.
The content of this document has been compiled for
information purposes only. Although Siemens AG has
made best efforts to keep the document as precise
and up-to-date as possible, Siemens AG shall not
assume any liability for defects and damage which
result through use of the information contained
herein. This content does not form part of a contract
or of business relations; nor does it change these. All
obligations of Siemens AG are stated in the relevant
contractual agreements. Siemens AG reserves the
right to revise this documentation time to time.

Document Edition: 03

Release Status: 08.2019

Version of the products described: V1.00

Digital Grid ⋅ Reyrolle High Speed Trip Relay (7PJ15) Catalog ⋅ Siemens Protection Devices 17
Published by and copyright © 2019 Subject to changes and errors.
Siemens Protection Devices The information given in this document
P.O. Box 8 only contains general descriptions and / or
North Farm Road performance features which may not always
Hebburn specifically reflect those described or which
Tyne & Wear may undergo modification in the course of
NE31 1TZ further development of the products.
United Kingdom
Phone: +44 (0)191 401 7901 The requested performance features are
Fax: +44 (0)191 401 5575 binding only when they are expressly
E-mail: marketing.spdl.gb@siemens.com agreed upon in the concluded contract.

For enquires please contact our Customer Support Center


Phone: +49 180/524 7000 (24hrs)
Fax: +49 180/524 2471
E-mail: support.energy@siemens.com
www.siemens.com/protection

Article No: C53000-X7040-C019-1

You might also like