New Multi-Unit Controller
MULTI ROLLER EX
                           Product Reference
                    Hitachi Industrial Equipment Systems Co., Ltd.
                     Air Compressor Systems Business Division
17 February 2006                                                     1
Concept
                                               Conventional model in Japan:
Higher Function, Advanced Extensibility,       3 types of unit-controller
Improved User-Friendliness                     (STEPROLLER II in global market)
- Touch panel + color LCD monitoring display
- Easy pressure control for inverter
- Easy connection with peripheral equipment 
and additional unit
- Weekly timer is equipped as standard
                                                                Integrated Function
                                                       MULTI ROLLER EX
                                                       (hereinafter called “MEX”)
                                                                                      2
Details of Concept
New Multi-Unit Control Method
 -Effective energy-saving: Capacity control method is changed from full-speed to I-type
 -Advanced extensibility: Each unit is connected by RS486 cable for future extension
 -Improved user-friendliness: Touch panel with interactive type 5.7 inch color LCD screen
 -Sophisticated function: Pressure predictive control, PID control (2-loop method) exclusively
                 for V-type, Second pressure setting, Weekly timer, PE connection
  (Future option: Remote monitoring by PC)
 Unit Details
 -Model: Hitachi air compressor (OSP, DSP) 
  [Confirmation required for non-Hitachi constant speed model compressors]
 -Combined with V-type unit (Single-V, Multi-V)
 -Unit construction:Master (PCB main body) + Slave (each unit)
 -External connection: Easy remote control, Flow indication (option)
 -Maximum connectable quantity: 26 units
                  (max. 12 compressors + max. 12 dryers + max. 2 cooling pumps)
                                                                                                 3
New Multi-Unit Controller
    Model
                    MULTI ROLLER EX
                   “EX” stands for “Expansion”
  Description          MR26-_E (E: English version) 
                                          Compressor unit qty. (4, 8 or 12 units)
                Controllable compressor unit qty. : 3 to 12 units
                                                                                    4
Standard Specification
               MR26-4E   MR26-8E   MR26-12E
                                              5
System Construction (1) 
                                   -Connect point connection (input, output) between compressor and MEX
                                   -Analog signal is used for PID control to connect (V-type operation)
                                    Additional modification for shifting pressure control while operating as solo
                                   -No additional valve is required for oil-cooled type
                                     Modification is not necessary for new HISCREW/DSP (constant speed)
Master PCB                         ←Pressure Detecting
                 Pressure Sensor     (from collecting pipe)
    Slave Unit
                                                                                             Run・Stop・
    Slave Unit
                                                                                            Load/Unload
    Slave Unit
                                                                                             (AC200V)
    Slave Unit                                                    Same as the
                                                                 conventional    Operation
         MR26-4E                                                 wiring method Answer・Failure
                                                                                  (DC24V)
                         OSP-37S                  OSP-37S                 OSP-37EII                   OSP-37U
                                                                                                                    6
System Construction (2) 
                                     -Up to 12 compressors installation is available
                                      In the future, when more compressors are to be installed, it can be easily
                                     done by changing the MEX setting, installing the slave unit in the compressor,
                                     and wiring.
                                       (separate setting required)
Master PCB                         ← Pressure Detection
                 Pressure Sensor      (from collecting pipe)                              Additional
    Slave Unit
                                                                                          Installation
    Slave Unit
                                                                                   PID        RS-485 Multi
    Slave Unit
                                                                Run・Stop・         Control      Drop Cable
    Slave Unit
                                                               Load/Unload         Signal
          MR26-4                                                (AC200V)
                                              Operation
                                                                                           Slave Unit      Slave Unit
  Same as                                     Answer・
  conventional                                  Failure
  wiring                                       (DC24V)
                  OSP-37S          OSP-37S         OSP-37EII        OSP-37U           OSP-37VII         OSP-37SI
                                                                                                                7
Function 1: Improved User-Friendliness
 Color LCD Touch Panel is applied
     -Operation and setting by touch panel enables advanced user-friendliness.
       Power save function: Turns off the backlight automatically after 10 minutes
                                                                                 The panel
                                                                                 control enables
                                                                                 to cancel
                                                                                 function and
                                                                                 change setting
                                                                                                   8
Function 2: Advanced 2-Loop Control
Control 2 loops: Constant speed loop and V-type loop
  Various combinations available:
  Constant speed + V-type, Single-V: Loop 1 and Loop2
  Multi-V: Loop2                  (Can equalize operating hours and speed for V-type )  
                  Loop 1                                             Loop 2
      Control constant speed unit                           e.g. : Multi-V control
               Rotary Operation                                Rotary Operation
  *Turn back control is only available by Loop 1       * Loop 2 is exclusive for V-type control
                                                                                                  9
Function 3: Weekly Timer and 2nd Pressure Setting
  Built-in Weekly Timer           -Sets weekly scheduled operation by multi-unit control
                                  -Weekly schedule can be operated also by 2nd
2nd   press. setting & schedule
                                  pressure setting
                                                                                      10
Function 4: PID Control
PID control function exclusive for V-type
 -MEX performs PID control directly to V-type compressors(variable speed control).
 -MEX gives all controlling commands which enables various combination with
 constant speed units.
 -Easy to change target pressure setting by MEX touch panel.
                                                                               Frequency
          MULTI ROLLER EX                                                     command is
                                                                                 added
         Pressure                    Loop 1            Run・Stop          Loop 2
          Sensor                                       (AC200V)
                    Run・Stop・Load/Unload (AC200V)
                                                    Operation
                         Operation Answer・Failure   Answer・          V-type        V-type
                                 (DC24V)            Failure(DC24V)
                                                                                           11
Function 5: Pressure Predictive Control
Pressure Predictive Control                    (*Patented)
  -The peak point is predicted by pressure drop slope calculation.
  Enables earlier start-up timing and also prevents pressure drop.
                    Conventional pressure control                                Pressure predictive control
                                                                                        Discharge
                                                                 Pressure →
                               Discharge
       Pressure →
                               Pressure                                                 Pressure
                                                                                   Δt
                                                                                      ΔP
                                                               Lower limit                        Prevents press. drop
       Lower limit
                                                                 press.
         press.
                                                   Time→       Comp. start-up                                     Time →
                                           Press. drop                                          Start load operation
                                                             Start-up unload
      Comp. start-up
                                      Start load operation                    Sample the pressure slope and
                    Start-up                                                  predict pressure after start-up
                    unload                                                              unloading
                                                                               Protect pressure drop to be less
                                                                                 than the lower limit pressure
      * Pressure predictive control is only valid for constant speed unit combination.
                                                                                                                           12
Function 6: Dryer and Pump Control
   Auxiliary Equipment Control
       -Air dryer and cooling water pump can be operated by MEX.
                                                        -MEX controls air dryer and
Run・Stop・Load/Unload
      (AC200V)                                          cooling water pump to Run/Stop.
 Operation Answer・                                      -Pre-start operation control is
       Failure                                          equipped as standard
      (DC24V)                                           -Max. 12 units of dryer and max. 2
                                                        units of cooling water pump can
                                                        be controlled.
           Compressor
                                                        -Separate Solo operation is also
                                                        available
                              Air Dryer
           Compressor
                                               Air
                              Air Dryer      Receiver
                                                   Run・Stop
                                                   (AC200V)
           Compressor
                                                  Operation Answer
                                                  ・Failure (DC24V)
                              Air Dryer
                                                                                         13
Function 7: Others
 IPI-Blackout Auto Restart Function
-IPI between 20ms to 350ms [AC200V]
  →The operating unit judges as abnormal stop and starts up the stopped unit and
continue auto operation
-IPI longer than 350ms [AC200V]      
    →Selectable to restart auto operation or not                  
-Can be combined with built-in IPI auto restart function compressor
Solo Operation
 -Switchable Auto/Solo operation
    HISCREW: Constant speed unit for modulation control,
               V-type for variable speed control + On-Off line control
    DSP: Constant speed unit for modulation control,
               V-type for variable speed control + On-Off line control
                (Motor On-Off control is available for DSP.)
Remote Monitoring System (Optional – to be released soon)
  -Efficient maintenance by PC remote monitoring function
         Install specific software into PC side and change the master PCB for
             communication.
                                                                                   14
Remote Monitoring Function (Optional)                                                             (Available soon)
  (1) Facility control and preventive maintenance by IT
  (2) Total Control                             System (PC, special software, master PCB for communication, LAN cable)
                                                Construction            (Flow and electricity can be monitored, but sensor
                                                                         must be prepared separately)
 1.1.Real
      Realtime
           timemonitor
                monitor
 2.2.Data
      Data record(operation
          record  (operationand
                              anduse
                                   use                                                              Pressure
    amounts)
     amounts)
 3.3.Comp.                                                                                            Flow
      Comp.maintenance
             maintenancesupport
                            support(list)
                                     (list)
 4.4.Charge
      Charge by electricity and flowamount
             by electricity and flow                           Ethernet
 5.5.Daily/monthly  report
                                       amount                                                     Electricity
      Daily/monthly report
 Real time monitor                              Use special software
 Settings of Run, Stop,                         (Installed in PC)
                                                                 Stored operation data           PE           Comp.
 Shutdown history, etc.
 Screen Examples
                                      Operation                   Control Constant
            Menu                      Monitoring                      Number                        Pressure Trend
                                                                                                                         15
Energy-Saving
   Improved control method                                       1   Multi-unit control
     (modulation control)
                                                                      (inc. V-type)
      2                                   400
          New multi-unit control
           (On-Off line control)
  3                                       300
      Parallel operation
                                   Power consumption
       by conventional
        suction valve
           control                        200
                                          (%)
                                          100
                                                       0   100      200 240 300           400
                                                                     210 270
                                                                 Capacity (%)
                                                                                           16
Precautions on System
[Compressor Operation]
-HISCREW 2000 V-type
 MEX executes PID control during auto operation. For solo operation, additional
 shift circuit of pressure control is required. (Additional modification for specific
 circuit is required.)
 PQ WIDEMODE must be OFF for V-plus unit.
-Cautions for maintenance
 In order for MEX to restart automatically after sudden blackout, make sure to set
 compressor as solo and keep the breaker off.
[Controlled unit quantity]
-Slave unit must be installed for each compressor, separate air dryer, and cooling
 water pump.
-The max. controllable quantity is 26 units. (Max. 12 units of compressors,
 max. 12 units of separate air dryers, and max. 2 units of cooling water pumps.)
[Others]
-Consult with your nearest Hitachi distributors for non-Hitachi compressors.
                                                                                     17
Precautions on System
[Electricity]
-Combination with DSP V-type
 Power system must be the same as compressor.
 (Both must be set to OFF when IPI occurs)
-Cautions on wiring (wiring and earthing)
  Wire separate shielded line for AC200V system wiring and DC24V
   system wiring.
  Each earth must be grounded firmly into the ground.
  V-type must be grounded separately.
[Power capacity]    100V    200V   Master PCB Fuse
  ・ For 4 units      38VA    48VA        3A
  ・ For 8 units      44VA    61VA       3A
  ・ For 12 units     (50VA)   (74VA)     3A  
                                                                   18