Sebelum maintenance closing
mea
s closing time (ms) closing time max (ms) closing sync (ms) assessment
R 105,90 normal
S 105,50 105,90 2,30 normal
T 103,60 normal
Sesudah maintenance closing
mea
s closing time (ms) closing time max (ms) closing sync (ms) assessment
R 104,30 normal
S 102,50 104,30 1,80 normal
T 103,80 normal
Sebelum maintening opening
mea
s open time (ms) open time max (ms) open sync (ms) assessment
R 32,80 normal
S 32,40 32,80 0,40 normal
T 32,70 normal
Sesudah maintening opening
mea opening time opening time max
s (ms) (ms) opening sync (ms) assessment
R 32,50 normal
S 32,70 32,70 0,20 normal
T 32,70 normal
Sebelum maintenance nilai resistansi
meas I DC I AC R assessment
R 100,29 A 10,557 mV 19,9 µΩ abnormal
S 99,71 A 14,935 mV 9,7 µΩ abnormal
T 99,82 A 8,540 mV 12,1 µΩ abnormal
Sesudah maintenance nilai resistansi
meas I DC I AC R assessment
R 99,79 A 12,805 mV 4,7 µΩ abnormal
S 110,25 A 13,012 mV 3,8 µΩ abnormal
T 99,68 A 11,263 mV 4,1 µΩ abnormal
Sebelum maintenance tahanan isolasi
CB in OPEN position Voltage : 5000 VDC > 1GΩ
Terminals
Duratio
Guar Temp (°C) Pole A Pole B Pole C
Tested Grounded n
d
TRAFO SIDE GEN SIDE 30 60 sec 20,10 GΩ 10,65 GΩ 16,90 GΩ
CB in CLOSE position Voltage : 5000 VDC > 1GΩ
Terminals
Duratio
Guar Temp (°C) Pole A Pole B Pole C
Tested Grounded n
d
TRAFO SIDE GEN SIDE 30 60 sec 11,71 GΩ 96,00 GΩ 83,30 GΩ
sesudah maintenance tahanan isolasi
CB in OPEN position Voltage : 5000 VDC > 1GΩ
Terminals
Duratio
Grounde Guar Temp(°C) Pole A Pole B Pole C
Tested n
d d
TRAFO SIDE GEN SIDE 30 60 sec 28,43 GΩ 13,72 GΩ 19,73 GΩ
CB in CLOSE position Voltage : 5000 VDC > 1GΩ
Terminals
Duratio
Grounde Guar Temp(°C) Pole A Pole B Pole C
Tested n
d d
TRAFO SIDE GEN SIDE 30 60 sec 20,80 GΩ 109,51 GΩ 100,30 GΩ