Impact of Distributed Generation On The Electric Protection System
Impact of Distributed Generation On The Electric Protection System
protection system
by
Thesis submitted in partial fulfilment of the requirements for the Cape Peninsula
University of Technology Master of Technology Degree
Supervisor: Dr Raji
Bellville Campus
July 2019
I, Rufaro Mavis Mutambudzi, declare that the contents of this thesis represent my own unaided
work, and that the thesis has not previously been submitted for academic examination towards
any qualification. Furthermore, it represents my own opinions and not necessarily those of the
Cape Peninsula University of Technology.
08/07/2019
Signed Date
ii
ABSTRACT
This document provides a study of the impact of distributed generation (particularly Solar and
wind energy) on the electric protection system. Due to energy poverty, most countries globally
have been opened up to use of DG such as wind and solar powered generators, South Africa
being one of them. There has been a prediction of the exhaustion of fossil fuels in the past
decades, leaving economies with the need to find sustainable energy options. The contribution
of fossil fuels to greenhouse gases has also been a global concern. This has increased the
use of DG for sustainable energy systems as well as to curb the level of carbon emissions.
While DG may increase energy sustainability, they have various impacts on the electric grid. It
is uncertain how DG may affect the protection system of the power grid henceforth the thesis
analyses the impact of DG on the electric protection. A comprehensive literature review is
carried out on distributed generation and electrical protection. DigSilent PowerFactory software
is used to simulate a network pre-and post-connection of the DG according to the South African
grid code requirements to reflect the power flow and fault levels. Furthermore, the software is
used to populate protection devices for the system. The results include a DigSilent network
diagram with simulation results, fault levels pre-and post-connection of the distributed
generators and protection coordination of the Distance and Overcurrent Relays.
iii
ACKNOWLEDGEMENTS
I would like to extend my greatest appreciation to my supervisor Dr Raji for taking me under
supervision and for the advice throughout my research. To the Department of Electrical,
Electronic and Computer Engineering at CPUT for providing the facilities to carry out the
project, Mr Sikelela Mkhabela and rest of the Eskom team for helping me gather information
and providing me the facilities to design my network diagram. I would also like to thank my
supervisor from Smart Energy SA, Mr John Chirwa for his technical guidance and moral
support.
To my friends and family, Tariro Mudarikwa, Eunice Jani, Linda Tekere and my father, Dr
Mutambudzi, thank you for the constant encouragement throughout the project, love and
infinite support.
iv
DEDICATION
To my father, Dr A. Mutambudzi thank you for your unconditional love and support
throughout my whole life.
v
Table of Contents
vi
3.1 Introduction ........................................................................................................ 29
3.2 Requirements of a Protection System ................................................................ 29
3.3 Potential problems to protection ......................................................................... 30
3.4 Distance Protection ............................................................................................ 31
3.4.1 Setting Distance Protection Relays in transmission lines. ............................... 32
3.4.2 Integration of DG in Distance Protection network ............................................ 33
3.4.3 Distance Protection relay characteristic curves............................................. 34
3.4.4 Potential Distance Protection Coordination Problems ..................................... 35
3.5 Overcurrent Protection ....................................................................................... 38
3.5 Time Grading ..................................................................................................... 40
3.5.1 Definite Operating Time Relays ...................................................................... 40
3.5.2 Definite Current Relays ................................................................................... 41
3.5.3 Inverse Time/ Current characteristic Relays ................................................... 41
3.6 The impact of DG interconnection to the traditional distribution protection.......... 42
3.7 Impact of DG on the protection of the power system .......................................... 43
3.7.1 Short Circuit levels of the Network .................................................................. 44
3.7.2 False tripping of feeder ................................................................................... 44
3.7.3 Nuisance tripping of feeder ............................................................................. 44
3.7.4 Protection Coordination .................................................................................. 44
3.7.5 Islanding ......................................................................................................... 47
3.7.6 Protection Blinding .......................................................................................... 49
3.8 Solutions adopted to curb the impact of DG on the protection system ................ 49
CHAPTER FOUR ................................................................................................................ 51
MODELLING AND SIMULATION ..................................................................................... 51
4.4 Introduction ........................................................................................................ 51
4.2 Modelling of the network .................................................................................... 51
4.2.1 Busbars .......................................................................................................... 51
4.2.2 Circuit Breakers and Terminal Nodes ............................................................. 53
4.2.3 Voltage Sources .......................................................................................... 53
4.2.4 Line Modelling ............................................................................................. 54
4.2.5 Transformers............................................................................................... 55
4.2.6 NECR modelling ......................................................................................... 57
4.2.7 Wind Generator Modelling........................................................................... 58
4.2.8 Solar Photovoltaic ....................................................................................... 59
4.2.9 General Loads ............................................................................................ 60
4.3 Single Line Diagram ........................................................................................... 61
4.4 Protection system modelling............................................................................... 62
4.4.1 Current Transformers ..................................................................................... 62
vii
4.4.2 Relays ......................................................................................................... 63
CHAPTER 5 ........................................................................................................................ 64
RESULTS ......................................................................................................................... 64
5.1 Introduction ........................................................................................................ 64
5.2 Case Study 1: Fault Levels................................................................................. 64
5.3 Case study 2: Overcurrent Protection (MV & LV Networks) ................................ 68
5.4 Case study 3: Distance Protection Relays .......................................................... 71
CHAPTER 6 ........................................................................................................................ 73
DISCUSSION, CONCLUSION AND RECOMMENDATIONS............................................ 73
6.1 Introduction ........................................................................................................ 73
6.2 General Discussion ............................................................................................ 73
6.3 Conclusion ......................................................................................................... 74
6.4 Recommendations ............................................................................................. 74
Bibliography ......................................................................................................................... 75
List of Figures
viii
Figure 3.2: Fault in a transmission line (Distance Protection) ............................................... 31
Figure 3.3: Time Grading in Distance Protection .................................................................. 32
Figure 3.4: Integration of DG in Distance Protection network .............................................. 33
Figure 3.5: Operating characteristic for one distance protection relay .................................. 34
Figure 3.6: Distance relay characteristic curve with arc resistance coverage and load
encroachment ..................................................................................................................... 35
Figure 3.7: Under-reaching of Relays .................................................................................. 36
Figure 3.8: Example of Cascade tripping in distance relays ................................................. 38
Figure 3.9: Multiple sources radial system ........................................................................... 39
Figure 3.10: Upstream and downstream relays for f1 fault ................................................... 39
Figure 3.11: Definite Time Relays ........................................................................................ 40
Figure 3.12: Definite current relay characteristic curve......................................................... 41
Figure 3.13: Inverse Time/Current Characteristic Relays ..................................................... 42
Figure 3.14: Example of the impact of DG on the distribution network ................................. 43
Figure 3.15: Time Based Relay Coordination ....................................................................... 45
Figure 3.16: Logic Coordination ........................................................................................... 46
Figure 3.17: Loss of protection coordination ........................................................................ 46
Figure 3.18: Relay R7-R8 Inverse Time Relay Characteristic Curves .................................. 47
Figure 3.19: Islanding operation ........................................................................................... 48
Figure 3.20: The impact of islanding on Operation of Relays ............................................... 48
Figure 3.21: Protection Blinding in a protection system ........................................................ 49
Figure 4.1: West Coast Overview modelled in DigSilent Software........................................ 52
Figure 4.2: Busbar Modelling ............................................................................................... 52
Figure 4.3: Circuit Breaker and Terminal Nodes Modelling .................................................. 53
Figure 4.4: Voltage Sources Modelling ................................................................................ 53
Figure 4.5: Line Modelling (a) .............................................................................................. 54
Figure 4.6: Line Modelling (b) .............................................................................................. 55
Figure 4.7: Two winding transformer connected as an auto-transformer .............................. 55
Figure 4.8: Auto-Transformer Modelling ............................................................................... 56
Figure 4.9: Two winding Transformer Modelling................................................................... 56
Figure 4.10: Three winding Transformer Modelling .............................................................. 57
Figure 4.11: NECR Modelling .............................................................................................. 57
Figure 4.12: Wind Farm Modelling ....................................................................................... 58
Figure 4.13: Operational Limits of the Wind Farm ................................................................ 58
Figure 4.14: Single line diagram of the Wind Farm .............................................................. 59
Figure 4.15: Solar PV Modelling .......................................................................................... 60
Figure 4.16: Capability Curve of the Solar PV Generator ..................................................... 60
Figure 4.17: General Load Modelling ................................................................................... 61
ix
Figure 4.18: West Coast Network (Single line diagram) ....................................................... 61
Figure 4.19: Current Transformer Modelling (a) ................................................................... 62
Figure 4.20: Current Transformer Modelling (b) ................................................................... 62
Figure 4.21: Distance Relay Modelling ................................................................................. 63
Figure 4.22: Overcurrent Protection Relay Modelling ........................................................... 63
Figure 5.1: Single-phase to Ground Fault on transmission line ............................................ 65
Figure 5.2: IDMT Relay Curve before connection of DG ...................................................... 68
Figure 5.3: IDMT Relay characteristic after connection of DG .............................................. 69
Figure 5.4: Time-Grading of the IDMT Relays ...................................................................... 70
Figure 5.5: Single-Phase to Ground Fault on 0% of Skaapvlei line ...................................... 71
Figure 5.6: Distance Relays characteristic curves ................................................................ 71
Figure 5.7: Single-phase to ground fault on 100% of Skaapvlei line ..................................... 72
Figure 5.8: Distance Relays characteristic curve after Skaapvlei fault at 100% of the line ... 72
List of Tables
List of Appendices
x
List of Abbreviations
AC Alternating Current
DC Direct Current
CB Circuit Breaker
CT Current Transformer
DG Distributed Generation
FC Fuel Cell
HV High Voltage
LV Low Voltage
MV Medium Voltage
MW Mega-Watt
xi
POC Point of Connection
PV Photo-Voltaic
RE Renewable Energy
TW Terra-Watt
WT Wind Turbine
Definition of Terms
Alternating This is bi-directional electrical current, which reverses its direction many
Current times in regular time intervals typically in power supplies.
DC/DC Power electronics devices used to convert direct current from one voltage
Converter level to another
xii
Distributed This is decentralized energy generating electricity close to the loads and
Generation is usually in small scale.
Electrical Load A section of an electrical circuit that consumes active power or energy.
Generation The process of generating primary energy source such as coal, wind,
source natural gas into electrical power.
The extent of load which can flow through the line without exceeding its
Loadability
limitations.
Is a local energy grid which may or may not be connected to the utility
Microgrid
grid with its own generation sources and energy storage.
Are small combustion turbines which produce both electricity and heat
Micro-turbine
in a small scale.
xiii
Overcurrent This is defence against extreme current which is over the rated current
Protection of equipment for example short-circuit protection.
Photovoltaic The production of electricity from light mostly relating to the sun.
Renewable Refers to energy from sources that are naturally replenishing or virtually
Source inexhaustible in duration for example wind, solar etc.
Three-winding This is a transformer with three windings, the primary, secondary and
Transformer third winding called the “tertiary winding.”
xiv
CHAPTER ONE
INTRODUCTION
The study on the impact of distributed generation (DG) on the electric protection arose from
most governments in the world opening to the exploitation and use of DG. Taking South Africa
for instance, it is intensely dependent on fossil fuels and are currently implementing ways to
diversify its energy generating capacity by using RE which involves independent power
producers (IPPs). The South African Integrated Resource plan of 2010 projects an amount of
17 800MW from renewables by 2030, which will represent 21% of the countries’ total energy
output (Department of Energy, 2011). Wind and Solar will dominate the renewable energy mix
with these energy sources projected to grow at an anticipated rate of 800MW per annum. The
advent of these generators into the traditional power system brings about several important
subjects which include reliability, stability and power quality which makes it important to provide
proper protection to the power system.
According (P Manditereza, 2015), studies have discovered sites viable for the installation of
wind and solar energy in SA. These studies have placed the massive potential of wind and
solar capacity in the country. Wind potential is approximated to be 76.6GW, while solar energy
is vast in the country and having a potential of about 886GW. The traditional power system is
vertically integrated consisting of large generating power stations with steady power outputs.
The penetration of DG is usually at the LV to MV networks with large windfarms integrated at
sub-transmission and transmission level (HV). There is need to investigate the impact of these
generators on the protection scheme in a power system considering their variable nature.
1
The study which will be presented in this project, will use DigSilent (PowerFactory) Software
to simulate a network to reflect the impact of distributed generators (particularly solar and wind)
on the electric protection.
i. Conduct a literature review on distributed generation and their impact on the electric
protection system.
ii. Use DigSilent PowerFactory software to model and simulate a network diagram with
and without DG connected to the grid.
iii. Use of DigSilent to populate HV, MV and LV protection systems;
• Overcurrent Protection LV & part of the MV Networks and
• Distance Protection in MV and HV Networks
iv. Perform short-circuit calculations on DigSilent with and without the connection of DG.
v. Provide results and a conclusion on the impact of DG on the electric protection system.
2
1.4 Hypothesis
There is no question that DG will play a large role in most electric grids globally and for some
countries like Germany, DG is already playing a vital role. The question then becomes what
the high penetration degree of distributed generation can do to the grid particularly the electric
protection system. Nowadays the ability to create a sustainable and resilient power system
has become very important and it is highly crucial to integrate DG.
Solar and wind already play a vital role in the modern power system, but how much work needs
to be put into the connection of these generation sources to create a reliable and effective
protection scheme? They most likely affect the load flow, but is there any need to change
protection equipment? How much does DG affect the electric protection system? Can modern
simulation tools like DigSilent Powerfactory be used to model different scenarios in order to
determine the impact?
It becomes important to discuss strategies for enhancing the connection and protection of the
DG. By simulating a network diagram, performing load flow calculations through DigSilent one
can be able to conclude how much DG can impact the electric protections system of a grid.
Case study 1- The first scenario to be analysed will be the variation in fault current levels
before and after connection of DG. The main types of faults to be analysed are the three-phase
faults on Busbars and single-phase to ground faults on transmission lines. A comparison will
be done to determine the percentage change in fault levels pre and post connection of DG.
The results will be outlined in form of tables and discussed.
Case study 2- This study considers the impact of DG on Overcurrent relays and their
protection coordination/settings. The investigation of the behaviour of the Overcurrent relays
before and after connection of DG particularly on Time Grading.
Case study 3- This study reflects the impact of DG on Distance relays including how the relay
coordination is affected in a power network.
3
1.6 Outcome of the Research
The main outcome of the research is to provide a simulated model that will highlights the effects
of Distributed Generation on the electric protection system in High, Medium and Low Voltage
networks.
Chapter Two- This chapter covers an in-depth Literature review on Distributed Generation
starting with a comparison between the traditional power system versus the new concept of
power systems which include DG. A summary of South Africa’s energy mix is given including
their future projections outlined in the Integrated Resource Plan of 2010. In addition to this, the
chapter covers the South African Grid code, clearly indicating the requirements of any external
Generation source when connected to the grid. Different types of DG sources are explained,
a brief study of electrical faults is outlined and summary of DigSilent software provided.
Chapter Three- A discussion on the impact of DG on the electric protection system is carried
out, mostly based on previous studies. It begins by clearly defining the requirements of a
protection system. Distance protection and the behaviour of distance relays is analysed. The
chapter further highlights the impact of DG on overcurrent protection. Other power system
protection problems associated with the connection of DG to the grid are also discussed and
ends with solutions that can be adopted to curb these problems. The study is mostly based on
previously published research.
4
Chapter Four- This chapter explains how the modelling was done in DigSilent software
including the modelling of the protection relays.
Chapter Five- Results obtained from the modelled network are outlined.
Chapter six- This chapter provides a brief discussion on the research and the results obtained.
A conclusion is drawn, and some recommendations provided at the end of the chapter.
5
CHAPTER TWO
LITERATURE REVIEW
2.1 Introduction
Increasing concerns about energy costs, security, and greenhouse gas emissions are inspiring
the power industries to integrate more Distributed Generation (DG) and flexible AC
transmission system (FACTS) elements into their traditional power systems.The continued
depletion of traditional energy sources and the continued emphasis on climate change has left
the world resorting to the move towards DG, which are cleaner, vast and seem to be the
solution to solving the global energy problems. These sources promise to generate high
efficiency and low pollution electricity over the years. Their ranges going from as small as 5kW
to 100MW. These energy sources like solar PV and fuel cells are advantageous as they require
low maintenance.
Some utilities have introduced the idea of DG for competition purposes to rule out utilities
acting as monopolies and exploiting consumers. Some of the need for these energy sources
has come from customers demanding customized power supplies to better suit their needs
(Chiradeja, 2005). The Department of Energy (DOE) and Eskom, South Africa’s major energy
supplier embarked on changing the energy policy which included financial metrics of energy
performance in the country, by slowly lessening coal’s contribution in the energy mix and
combining less carbon-intensive conventional sources together with other DG sources (Krupa
& Burch, 2011).
According to (Zhang et al., 2009), the introduction of DG can have an impact on the structure
as well as the operation of networks, reliability, power flow and short circuit current. Much
emphasis is now being put on DG research and their integration with the traditional power
system. This chapter outlines a thorough literature review on what distributed generation is,
the electric protection system, electric faults and the basic integration of DG into the electric
grid. It also defines the South African Grid code requirements for DG sources like solar
photovoltaic and wind.
Traditional Power systems have been known to be vertically integrated with one utility
responsible for handling of all functions of the power system. Electricity is produced from large
generation plants typically situated far from consumers. Electricity is then delivered to
consumers through High Voltage (HV), Medium Voltage (MV) and Low Voltage (LV) networks
(Fernnandez Sarabia, 2011). Coal continues to dominate the South African energy mix with
most of its mines and power stations located in Gauteng and Free State provinces. Eskom is
responsible for operation and coordination of the system particularly in the generation and
6
transmission levels, with the municipality taking part in the distribution of electricity (Bohlmann
et al., 2019).
In figure 2.1, at level 1 there is generation of electricity in large plants located far away from
consumers. The voltage is stepped up by transformers from 24kV (generation voltage) to
transmission level voltages of 132 kV, 400 kV or 765 kV. At level 2, the voltage is transmitted
using overhead lines and underground cables to distribution level. At level 3, the voltage is
stepped down into lower voltages using transformers and distributed to the consumers
(Fernnandez Sarabia, 2011)
Hydropower is less popular compared to solar and wind due to the complexity and access to
rivers and lakes, slowing its utilisation and development. Contrary to this, wind and Solar PV
continue to dominate due to their easy access and less dependency on physical location
particularly Solar PV.
7
Figure 2.2: The modern concept of Power Systems (Fernnandez Sarabia, 2011)
Figure 2.2 illustrates the modern concept of electricity generation. Part of the energy is supplied
by centralized generation usually far from consumers and a part of it supplied by distributed
generation usually close to the consumers.
A high penetration of these units under the same power system infrastructure may impact the
network stability. Most of these generation sources are variable with high dependency on
8
climate and can pose a threat to the national grid. Most economies have written interconnection
codes highlighting the requirements for these generators in case of abnormal interruptions
(Frede Blaabjerg, Yongheng Yang, 2017).
The most popular DG Technologies are listed in Table 2.1
Table 2.1: DG Technologies and their typical sizes (Niwas et al., 2009)
Technologies 10-18 are renewable DG sources while other can only be considered renewable
if operated with biofuels (Niwas et al., 2009).
DG technologies are becoming increasingly more popular due to their merits they bring into
the power network such as energy security and voltage stability. Most of these technologies
are cleaner providing more benefits in the modern world where the world is fighting pollution
and Co2 emissions.
Currently, power systems are becoming very complex in the operation, structure, management
and ownership. DG plays a significant role in the mix to solve some of the problems that exists
9
in power networks and are also useful in proving ancillary services, aggregation technology
(Niwas et al., 2009).
Table 2.2: Benefits and Drawbacks of DG (Pepermans et al., 2005), (Fernnandez Sarabia, 2011)
Benefits Drawbacks
Grid support, DG can contribute power to the grid High financial costs, these have high
to maintain a sustainable system. Increases capital costs hence they are still
reliability to consumers. expensive to deploy.
Environmental concerns, provides clean energy Grid Instability some of the DG use
considering that the reduction of carbon emissions converters which inject harmonics into the
is a global objective presently. grid. System frequency may deviate from
rated value of 50Hz
Collective generation of heat and electricity, May result in over-voltage and
use of CHP systems. unbalanced system, if there is no proper
coordination with the grid supply.
DG have shorter installation time and payback May alter the short circuit levels, hence
period need to change relay settings.
Improves voltage profiles, power quality and Connection issues, changes the power
supports voltage stability. Ability of the power flow, can reduce the effectiveness of
system to withstand high loading conditions. protection equipment
The energy sector is mostly controlled by Eskom, a state-run enterprise which not only
produces 95% of South Africa’s electricity, but also operates and owns the country’s
transmission system. Private entities only produce about 2% of the country’s electricity
(Pegels, 2010).
10
Figure 2.3: South Africa's Energy Mix (Bello et al., 2013)
As seen on Figure 2.3, DG currently contributes a small portion of the total generating capacity
in the country. The government introduced the Integrated Resource plan in 2010 with the aim
of increasing the Renewable energy contribution to 17 800MW by 2030. The economy is open
to the idea of going green and saving the environment. It is one of the leading economies in
Africa in terms of Renewable energy generation and contribution to the grid. The idea is to
mitigate the country’s energy crisis, isolation of electricity in the rural and remote areas of SA
and to curb the environmental problems arising from over dependence on coal.
Figure 2.4 shows South Africa’s plan to have a shared contribution of 17 800MW from
Renewable Energy. The Integrated Resource Plan 2010 (IRP2010), is a living plan by the
11
government which is continuously adjusted as necessitated. Every two years, the plan is
updated (Department of Energy, 2011).
The nation’s pledge to promote RE technologies was derived back from the post-apartheid
period in 1996 when most of the policies emerged from the Constitution. In 1998, South African
government published a White Paper on Energy Policy and following that, other policy
documents were published like the 2003 White Paper on Renewable Energy (WPRE) and the
2011 White Paper on National Climate Change Response Policy (WPNCCRP). The National
Development Plan (NDP) was also published in 2011 reflecting on the Government’s pledge
to promoting RE technologies for sustainable growth (Jain & Jain, 2017).
In terms of GDP, in the year 2012 SA was the fourth major investor in RE. In that year, 16.9%
of total energy consumption was from Renewables. Back in 2009, the National Energy
Regulator of South Africa (NERSA) had announced renewable energy feed-in-tariffs (REFIT)
(Jain & Jain, 2017). REFIT policy was aimed at reducing prices of RE electricity by setting up
definite prices for a predetermined period that would cover the cost of supplying electricity as
well as a reasonable profit in order to allow investment from RE developers. The idea of REFIT
policy was implemented and adopted due to the positive experience of other countries like
Germany, Spain and USA (Nakumuryango & Inglesi-lotz, 2016).
The Grid Code is an outline of operational rules and requirements given by the power system
operators to connect to the grid. The National Energy Regulator of South Africa (NERSA)
developed the South African Grid code, and it stipulates the minimum grid connection
requirements for RPP who are connected or wish to connect to the SA grid. It applies to all the
RE sources or Distributed Generation including solar, wind, small hydropower and bioenergy
(NERSA, 2014).
According to (NERSA, 2014) the Renewable Power Plant (RPP) should be designed to endure
abrupt phase fluctuations of up to 20° at the Point of Connection (POC) without decreasing
their output. Immediately after a settling period, the RPP should recommence operation within
five seconds. Plants of the size ranging from 0 to 100kVA should be designed to withstand
voltage ride through conditions (NERSA, 2014).
12
Figure 2.5: : Voltage Ride Through Capability for the RPPs of size 0-100kVA (NERSA,
2014)
Figure 2.5 shows the voltage ride through capability of RPPs with the capacity of 0-100kVA.
The shaded region shows the region in which the RPP is expected to continue normal
operation. The table below shows the maximum disconnection times of the RPP of the size 0-
100kVA (NERSA, 2014).
Table 2.3: Maximum disconnection times for RPPs of size 0-100kVA (NERSA, 2014).
13
RPP of the capacity 100kVA or higher should be designed to be able to endure voltage drops
to zero for a minimum of 0.150 seconds as well as withstanding voltage peaks of up to 120%
of nominal voltage for a minimu time of 2 seconds without disconnecting. Figure 2.6 shows the
conditions that the RPPs should comply with and applies to both symmetrical and asymmetrical
faults. It shows the voltage ride through capability of RPPs with capacity higher than 100kVA
(NERSA, 2014)
Figure 2.6: Voltage Ride Through Capability for the RPPs of the size greater than 100kVA
(NERSA, 2014)
In summary, during a fault if voltage relapses to Area A and Area B, the RPP may not
disconnect. Disconnection of the RPP is only allowed in Area C. In area B and D, the RPP
should be able to control the reactive current. In Area D, the plant should remain connected
and have the capability to deliver maximum voltage support.
In Area B, the plant should prioritize supply of reactive power while the secondary priority is
supply of active power. It should be able to maintain the active power when there is voltage
drops however a decrease in the active power inside the Plant’s design specifications must be
proportional to the voltage drop for all voltages below 85%. When the fault has cleared, the
RPP can restore its active power production to 90% of the level accessible instantly preceding
to what the active power was before the fault. This action should be done within 1 second
(NERSA, 2014).
14
2.4.5 Wind Energy Generation
Wind energy generation uses large turbines to transform wind energy into electricity
(Fernnandez Sarabia, 2011). There has been a massive growth in the installation of wind
turbines over the past few decades. Presently, the installed generation is over 440GW and is
anticipated to surpass 760 GW by 2020, therefore making wind energy generation important
for the modern and future energy mix (Blaabjerg, 2014).
Figure 2.7: Global Cumulative wind power capacity 2001-2020 (Blaabjerg, 2014)
The figure shows how wind power has increased over the years globally from 2001 -2016 and
the anticipated capacity by 2020. South Africa is one of the major wind power generation
players in Africa. By the end of 2015, wind generation accounted for approximately 55% of the
RE capacity worldwide excluding hydropower. In terms of global electricity production, wind
accounted for 3.7%. The South African Wind Energy Association (SAWEA) predicts that wind
energy alone could potentially generate 62% of SA’s present energy needs (MUSONI, 2018).
The power electronics configuration of the turbines has changed over the years. Squirrel-cage
induction generators (SCIG) were the type of wind turbines used in the 1980s which were
basically configured as soft starters. Thyristors were used in the power electronics of the
15
turbines. In the 1990s, the technology used rotor resistance control of WRIGs (wound-rotor
induction generators). Since the millennium year 2000, more advanced power electronics
converters have been introduced (Blaabjerg, 2014). They can now handle continuous wind
turbine power generated. DFIGs (Double-Fed induction generators) are now being used.
Figure 2.8: A typical Wind Turbine System (Some systems avoid gear box) (Blaabjerg, 2014).
As shown in the above figure, a typical WTS has a rotor, gearbox in certain applications, an
electric generator, power electronics converter and a transformer (Herbert et al., 2007). There
are different categories in wind turbine designing which normally depend on speed
controllability, generator and aerodynamic power limiting. Power electronics also plays a
crucial role in the WT concepts. The Doubly Fed Induction Generator (DFIG) has become
widely common over the past decade (Blaabjerg, 2014).
Figure 2.9: Wind Turbine system with DFIG control (Blaabjerg, 2014)
16
The figure shows a wind turbine using the DFIG configuration. The stator is connected to the
grid through a transformer while the rotor connects to the grid through power converters and
normally have about 30% power capacity of the wind generator. The rotational speed of the
rotor blades maximises the energy yield of the system. The rotor frequency and current are
controlled by the power electronics in the DFIG configuration controls. The main drawback of
DFIG systems are their use of slip rings which have inadequate power controllability in the
event of grid or generator disturbances (Blaabjerg, 2014).
Within certain limits, DFIG control has the capability to keep the electrical power constant
despite the unstable wind. However, in this control, there are problems associated with the
stator’s direct connection to the grid such as huge disturbances leading to excessive fault
currents in the stator. There are advantages with high stator currents particularly for the
protection relay coordination in the power system. The high current allows for the circuit
breakers to trip the faulty section of the network while isolating the wind turbine from the fault.
The main aim of the protection system is to protect the wind turbine in the event of a fault. This
also includes anti-islanding protection. The desired variable speed ratio is one of the factors
used to determine the stator-rotor ratio on designing of DFIG controls. This however might
make it impossible to achieve desired rotor voltage when trying to control the excessive
currents in the rotor when there is a fault. Hence only partial control is given onto the converter
during grid faults (Jauch et al., 2007).
17
2.4.6 Solar Energy Generation
Although solar energy presently represents a small percentage in the global energy mix, there
has been an overall increase in the use of the technology particularly solar PV for distributed
power generation. There has been a reduction in their costs in the past decade due to
technological advancement, economies of scale and innovations in the financing of the
technology. The cost is likely to continue decreasing sand hence provide opportunities for
developing countries to explore the technologies as well. Solar energy has an installed capacity
greater than 137GW globally and has annual additions of about 40GW every year
(International Finance Corporation, 2015)
The most common solar energy generation are PV (Photovoltaic) systems. A PV system
converts direct sunlight into electrical energy. The electricity produced is normally in the form
of direct current (DC). It uses solar cells which are semi conductive materials that convert the
self-contained energy of photons into DC when exposed to sunlight. Solar PV systems are
environmentally friendly and have simple designs. They however require large spaces of land
and have high capital costs (Fernnandez Sarabia, 2011)
The figure shows the maximum potentials for most DG Resources however it is impossible to
harness all the energy. Solar Energy has the most potential due to the sun being powerful. in
If humans could harness all the energy from the sun, then it would provide 10 000 times what
18
the world needs. Currently, the Global average energy consumption is about 18TW and it is
predicted that by 2050 the consumption will be 30TW and 46TW by 2100. The maximum power
that can be supplied by fossil power by 2050 is estimated to be about 18TW. This leaves about
12TW needed supply from Carbon-free sources (Tao, 2014). In SA, most areas average over
2 500 sun hours per year. There is great potential in the generation of electricity through Solar
in the country.
Components of a PV system
19
tracking the maximum power point of the solar array. The efficiency of the inverter is
important with most inverters designed with an efficiency of over 90% which may be
affected by climate and environmental factors. The inverter's overload capability must
be considered when sizing grid-connected inverters. It is best to use an inverter with a
power rating of 70% to 90% of the PV array to achieve optimal system performance.
This also depends on several factors such as climate and the inverter’s performance
characteristics.
• Back-Up Generator- can be used in conjunction with the Grid and PV system.
Particularly useful in off-grid installations in case of winter months where there is low
solar radiation.
• Electrical load; - these are appliances, such as lights, plugs and other equipment
powered by the PV system (Zeman, 2013)
Types of PV systems
Solar PV systems can be categorised into three main types;
1. Off-grid systems; - also known as stand-alone systems. They rely on PV modules as
energy source. The common configuration consists of only PV modules with batteries
for energy storage, a DC/AC inverter and a load.
2. Grid connected systems; - also known as Grid-Tie systems. The inverter is tied to the
grid supplying power to the loads directly from the solar modules and feeding excess
back into the grid. They do not require batteries for storage though sometimes they
may have them for back-up.
3. Grid Fallback systems;- these systems are not popular as the rest of the types. In this
configuration, the solar panels generate power which charge the battery bank. The
energy in converted by the inverter into AC which feeds the loads. When the batteries
are completely drained, the system switches back to the grid supply (Boxwell, 2012).
4. Hybrid Systems; - These consists PV modules connected to a DC/AC inverter with a
complementary source of electricity generation for example a diesel, gas or wind
generator (Zeman, 2013)
Grid-connected PV systems
Grid connected, also known as grid-tie systems are the most common type of PV system. They
are designed using solar arrays, inverters and other balance of systems such as mounting
structure, power transformers (for large plants) and may have back-up storage etc (Raj et al.,
2016). A grid-connected system can be represented on a schematic as shown on figure 2.12.
20
Figure 2.12: Grid-connected PV system schematic (Raj et al., 2016)
Different types of Grid-Tie inverters are being manufactured world-wide, which basically
convert the DC from the solar arrays to Alternating Current (AC) (Raj et al., 2016). Grid-
connected system in residential applications are connected before the utility meter with the
Solar PV system supplying the loads during the day and the grid supplying loads at night. For
applications in large power plants, voltage from the PV system is stepped up by power
transformers to higher voltages and transmitted into the grid.
In the past, DG plants such as Solar PV could disengage from the grid during severe faults
and allowed to reconnect after clearing of the fault. Nowadays however, due to the significant
share of renewables, they may not be allowed to disconnect. The system may break down if
several generating plants in the power system disconnect simultaneously which may result in
a blackout. Most countries now outline grid connection requirements for DG through a grid
code. The Low Voltage Ride Through requirement is established and is intended to warrant
that the generating plants remain connected when there is a fault (Dirksen & Gmbh, 2013).
21
2.4.7 Fuel cells
Fuel cells can be defined as static energy conversion devices converting fuel chemical energy
into direct current (Wang & Nehrir, 2006). The generation sizes are normally as small as 1kW
up to 1MW (Guaitolini et al., 2018). They are not a common type of electricity generation in
South Africa. The main types include;-
• SOFC- Solid Oxide Fuel Cells
• AFC- Alkaline Fuel Cells
• PAFC- Phosphoric Acid Fuel Cells
• MCFC- Molten Carbonate Fuel Cells and
• PEMFC- Polymer Electrolyte Membrane Fuel Cells (Guaitolini et al., 2018)
Main advantages; -
• High efficiency
• Flexible modular structure
• None or low emissions of gases and noise free
• Allow for grid reinforcement
• Defer the need for systems upgrades
• Improve system integrity, reliability & efficiency (Wang & Nehrir, 2006)
22
They use DC/DC converters to control the output voltage to the desired DC voltage range. An
inverter is subsequently used for the conversion of the fairly good input DC voltage to AC
(Wang & Nehrir, 2006).
Figure 2.13 shows a block diagram of the Fuel cell power generation and the interface with
utility grid. They use DC/DC converters and three phase Power Width Modulator (PWM)
inverter for conversion. Batteries and super capacitors are normally used as storage devices
in the system technology. Undesired harmonics are eliminated by the LC bandpass filter. In
the PEMFC system a short transmission line is used to connect to the utility grid (Nehrir et al.,
2006). The PEMFC is one of the most common type of fuel cells electricity generation used
globally.
Inverter
Gas PM DC/AC
Load /
Turbine Generator AC/DC Power Grid
Rectifier
The figure above shows a simple Micro-turbine system with converters and the electric grid or
load. These types of models are normally small in capacity size with low maintenance required,
very durable and with low emissions. Natural gas, ethanol or diesel can be used with the
turbines (Báez-Rivera et al., 2006).
Single shaft or split shaft are the two types of micro-turbines and are named according to their
configurations. The single shaft has the generator and turbine connected while the split shaft
connects the generator and turbine through a gearbox. The shaft runs at high speed and has
no lubrication. Normally the power plant is air-cooled with two-pole permanent magnet
generator (Lasseter, 2002).
23
.
Concept of operation
With induction generators, a prime mover which can be a turbine or engine is used to rotate
the shaft quicker than the synchronous frequency. The flux direction and active currents should
change direction for the machine to provide power. Induction generator power factors depend
on the load and is normally lagging. They are much preferred than the synchronous generators.
They use reactive power to build a magnetic field by using the mains. They can’t be easily
used for backup generation particularly during islanded operation. The induction generators
are asynchronous machines.
On the other hand, synchronous generators run at specific synchronous speed and can be
called constant speed generators. Unlike the induction generators whose power factor is
lagging, the synchronous generators have variable power factor, they work very well in power
factor correction applications. They provide lagging power factors when they operate on infinite
busbars and there is over-excitation and delivering leading power factors when there is under
excitation. Nowadays, the synchronous generators are commonly used in hydro, wind and
thermal power systems. System sizes range from 1kW to a few Mega-watts (Blaabjerg, 2014),
(Józef et al., 2018).
24
a. Symmetrical Faults- Can be referred to as balanced faults. They are normally
excessive and occur intermittently in the power system. Examples include three-phase
to ground faults and three phase faults.
b. Asymmetrical Faults- also known as unbalanced faults and occur more frequently in
a power network. They are normally less severe compared to symmetrical faults.
Examples include single-phase to ground faults, line to line faults and phase-phase to
ground faults. The most common are the single-phase to ground faults, merely 65 to
70% in power systems (Thakur, 2016).
25
Arises from contact between two phases/lines and ground. AN example is shown on the figure
below with a fault between Yellow and Blue phase to Ground.
d. Three-phase faults
These types of faults occur when three phases have contact (Red, Yellow and Blue). They
normally account for about 5% of all faults in a power system. These types of faults are
balanced, an illustration is shown on Figure 2.18
26
This type of fault normally occurs when there is contact between the three phases (Red Yellow
and Blue) with Ground as illustrated on Figure 2.19.
A relay is a device used in protection systems for opening and closing electrical contacts
leading to the operation of other devices under electric control such as circuit breakers. The
role of a relay is simply to detect intolerable or undesirable conditions within an allocated area.
The relay acts to disconnect the area affected as means of protection to prevent damage to
humans and equipment, by operating the suitable circuit breakers. Relays can be classified
according to their functions, either as measuring devices or on/off relays also known as all-or-
nothing relays. Examples of on/off relays include time-lag relays, auxiliary relays, and tripping
relays (El-Hawary, 2015).
a. Current relays- These types of relays are triggered by current. They operate at
predetermined current levels for example undercurrent or overcurrent relays.
b. Voltage relays- are triggered by voltage, operating at predetermined levels of voltage
for example overvoltage or undervoltage relays
c. Power relays- are triggered by power operating at predetermined levels of power for
example overpower or underpower relays.
d. Directional relays- these can be grouped into two types;
(i) Alternating current- these are triggered by the phase relationship between
alternating quantities.
(ii) Direct current- these are activated according to the direction of the current.
They are normally of the permanent-magnetic, moving-coil pattern.
e. Frequency relays- are triggered by frequency and operate and predetermined levels
of frequency. Examples are overfrequency and underfrequency relays.
f. Temperature relays- are triggered by temperature and operate at predetermined
levels of temperature.
g. Differential relays-these relays use scalar difference between two quantities such as
current & voltage during their operation.
h. Distance relays- are commonly applied in distance protection of transmission lines.
They operate according to the "distance" between the relay's current transformer and
the fault. Three elements are used to measure the distance which are resistance,
reactance, or impedance (El-Hawary, 2015).
27
2.7 Simulation Software (DigSilent PowerFactory)
DigSilent also known as PowerFactory is a leading power system analysis software typically
used in generation, transmission, distribution and industrial systems. Some of its functionality
over the recent years includes real-time simulation, wind power and distributed generation
modelling. Some of its basic features include load flow and short circuit analysis, network
modelling and basic MV/LV network analysis. It also has advanced features which are
contingency analysis, network reduction, cable analysis, power quality and harmonic studies,
protection coordination and reliability studies amongst others. The most important tool covered
in this thesis is the Protection function and distributed generation (DigSILENT, 2019).
There are different methods of calculating short-circuit current which include the nodal method,
complete method, symmetrical component method and dynamic time method (Brady, 2014).
The most widely used is the symmetrical component method both when using DigSilent
software or when doing hand calculations.
The IEC 60909 standard is used in this study is based on the superposition method of
calculating short circuits by providing an equivalent voltage source at the fault location. The
following assumptions are made;
a. Bus voltage is assumed to be equal to the rated voltage.
b. Load currents are disregarded
c. Loads are not taken into account in the positive and negative sequence of the network
2.8 Summary
This chapter provided a comprehensive literature review on the traditional power system which
was known to be vertically integrated with one utility handling all the functions of the power
system versus the new concept power systems which is more decentralized with the inclusion
of distributed generation. The basics of power system components was covered, the protection
system and different distributed generation sources including the South African energy mix
with the 2030 vision of increasing their RE contribution. Part of the literature survey explained
in the chapter covers the regulatory requirements around the connection of DG into the power
grid particularly in the case of South Africa. The different types of faults that occur in a power
system are explained with illustrations of the faults. The last part of the chapter explains the
simulation software used in the study, (DigSilent PowerFactory) providing a description of what
the software does and the IEC 60909 standard in calculating short circuit current.
28
CHAPTER THREE
IMPACT OF DG ON ELECTRIC PROTECTION SYSTEM
3.1 Introduction
Population in South Africa has been increasing day by day and there has been a high increase
in infrastructural development in the country over the years. Infrastructural development
requires the use energy. Many people in the rural developments still do not have access to
electricity. This has led to a high demand for energy and the need to resort to other means of
generating electricity apart from the traditional methods. The integration of DG has its own
advantages which include improved voltage profile, security of supply, cleaner energy sources
and improved reliability of the network (Bari et al., 2017).
While the penetration of DG has its pros, their integration in power systems initiate some
challenges for grid operation. DG integration creates a full spectrum of problems, ranging from
voltage profile, power flow, protection, and stability. The existence of DG elements in power
systems and transmission lines may also cause maloperation of protection devices which may
result in failure to correctly identify faults. Furthermore, the increasing penetration of DG using
power electronics-based devices in power systems is also raising important challenges
regarding the overall power system stability. Most DG technologies are usually based on power
electronic converters and these systems are likely to interact with each other, triggering
instability in power systems in certain conditions.
The most common impact in protection systems is on protection coordination of Relay devices.
It is important for a protection system to be highly effective and capable of isolating a faults in
a network (Choudhary et al., 2015). This chapter covers the impact of DG on the electric
protection system as identified by other sources and different ways to mitigate them.
a. Reliability- the protection system must be dependable and secure. There must be
assurance that it will work as is it designed to work. In the event of a fault , the protection
system closest to the fault must isolate the fault. It should also be secure enough to
avoid unnecessary operation during normal operation.
b. Sensitivity- must be able to detect every small internal fault current.
c. Discrimination- ability to distinguish between external and internal faults in a zone.
Protection coordination in Overcurrent Relays is an example of discrimination in
protection systems.
29
d. Simplicity- they must be simple and easy to repair or maintain.
e. Economy- must be cheap, achieving the best protection system and minimum cost.
f. Speed- response time must be quick in the event of a fault (Onah, 2019).
The appearance of the challenges depends on numerous factors including the kind of DG
source. Most of the time, penetration of DG requires changing of the existing protection
(Kumpulainen, 2004).
Theoretically, Figure 3.1 can be used to explain the concept of how DG can contribute to the
fault current. In the event of a fault at the end of the feeder as shown on the diagram, the total
fault current with be the addition of 𝐼1 and 𝐼2 . The impedances will be as follows;
30
𝑍𝑔 = Generator impedance
𝑍𝐿 = Line/ Feeder impedance
From Thevenin equivalent circuit, if we assume the feeder relay sees current 𝐼𝐹 , when there is
no production from DG. The ratio between 𝐼𝐹 and 𝐼1 can be derived as;
𝐼1 𝑍𝑔 (𝑍𝑆 +𝑍𝐿 )
=
𝐼𝐹 𝑍𝑆 (𝑍𝐿 + 𝑍𝑔 )+ 𝑍𝐿 𝑍𝑔
The generator’s short circuit impedance may be expressed using the short circuit impedance
of feeding network will be;
𝑍𝑔 = 𝑎𝑍𝑆
While the impedance of the line can be expressed as
𝑍𝐿 = 𝑏𝑍𝑆
𝐼1 𝑎+𝑎𝑏
=
𝐼𝐹 𝑎+𝑏+𝑎𝑏
Figure 3.2: Fault in a transmission line (Distance Protection) (Saad et al., 2018)
From Figure 3.2, 𝑍𝑚 = 𝑉𝑚 / 𝐼𝑚 (Saad et al., 2018). In normal operation, the impedance 𝑍𝑚 is
measured by the Distance relay which will be approximately equal to the load impedance.
31
When there is a fault in the protected zone, the impedance of the distance relay will be lower
than that of the transmission line. Whenever the impedance value is lower than the set value,
then the fault is within the relay protection zone.
In summary, the standard operation of distance relays involves dividing of voltage at the
relaying point by the current measured. The apparent impedance is compared to the reach
point impedance. A fault in the line is assumed by the relay in the event of the measured
impedance being lower than the reach point impedance. Operating time and reach accuracy
are used to assess the distance relay performance. The level of voltage seen by the relay
when there is a fault is one of the factors that affect its reach accuracy (Edvard Csanyi, 2012).
Figure 3.3 shows time grading of Distance relays in a power system. Zone typically covers
80% to 90% of the line (Ahmad & Bukka, 2015). This is the primary protection and hence the
tripping time is minimum. It is represented by the equation;
Zone 2 is set at minimum 120% of the protected line. Common practice is to set Zone 2 reach
equal to 100% of the protected line as well as 50% of the shortest adjacent line. This is Backup
protection hence the tripping time is higher than that of Zone 1. Time grading of 0.4 seconds is
commonly used. This is represented by the equation below;
32
The rest of the protection zone is covered by Zone 3 which is normally 0.7 seconds. It is
represented by the equation;
𝑍3𝐴 = 0.8 [𝑍𝐴𝐵 + 0.8 (𝑍𝐵𝐶 + 0.8 𝑍𝐶𝐷 )] (Saad et al., 2018)
The impedance measured by Distance relay S1 on line B1 will change with the penetration of
DG and may exceed the measured values in a case where the sources aren’t connected. The
impedance 𝑍𝑚 can be calculated using the formula;
𝑈𝑚 𝐼1 𝑍𝐷𝐿−2 + 𝐼𝑡 ∗𝑍𝑘
𝑍𝑚 = = (Saad et al., 2018).
𝐼𝑚 𝐼1
There is a change in the impedance measured due to the advent of DG into the network. This
may result in non-selective tripping of the relays which can be calculated by the below
equation;
𝐼𝑡 𝐼1 + 𝐼𝐷𝐺
𝐾𝑖𝑓 = =
𝐼1 𝐼1
The K coefficient in the equation compensates for the change in fault current to restore the
distance relay protection settings. The three zones will then be defined by the equations;
33
𝑍1𝐴 = 0.8 𝑍𝐴𝐵
Zone 1 is barely affected as it is the primary protection, Zone 2 and 3 impedances may change
(Saad et al., 2018).
May also be referred to as the R-X plot. At the operation frequency of the power network, the
relative values of Resistance (R) and inductance (X) are used to determine the fault angle. The
fault angle in distance protection affects the impedance relay of a relay.
Figure 3.5: Operating characteristic for one distance protection relay (Iagǎr et al., 2018)
Figure 3.5 illustrated the distance relay characteristic curve of one protection zone when
operation in forward direction. The distance protection zones can operate autonomously in
directional mode (Forward, reverse or non-directional mode) (Iagǎr et al., 2018).
Xph-e represents the reactive reach during single phase to ground faults
Xph-ph represents reactive reach during phase to phase faults
Rph-e is the resistive reach during single phase to ground faults
Rph-ph is the resistive reach during phase to phase faults
Zline is the line impedance (Iagǎr et al., 2018)
Arcs and other earth faults may be involved as part of the resistive component of the fault
impedance hence may affect the impedance angle. Under-reach may occur which is a situation
where the characteristic angle of the relay is set to the angle of the line under resistive fault
circumstances (Abdulfetah Shobole, Mustafa Baysal, Mohammed Wadi, 2017).
34
Figure 3.6: Distance relay characteristic curve with arc resistance coverage and load
encroachment (Abdulfetah Shobole, Mustafa Baysal, Mohammed Wadi, 2017)
Figure 3.6 illustrates the distance relay characteristic curves with increased arc resistance
coverage. PQ shown in the diagram is the arc resistance
𝐴𝐵
𝐴𝑄 =
𝐶𝑜𝑠 (∅ − 𝜃)
Where;
AQ = Relay impedance setting
AB = Impedance of protected line (Abdulfetah Shobole, Mustafa Baysal, Mohammed
Wadi, 2017)
The main advantage of distance protection over other types of protection like overcurrent
protection is its ability to isolate a fault of a protected circuit, which may be independent of
source impedance variations (Edvard Csanyi, 2012).
There are some problems associated with distance relays particularly with the integration of
DG. Some of the key issues are discussed below.
a. Under-reach
According to (Brady, 2014) this is an area of concern particularly for networks with numerous
in-feed feeders. As previously discussed, distance protection works on the concept of zones
where the firsts zone is the primary protection and covers about 80% of the line, while zone 2
protects the remaining section and a margin of the remote line. On the other hand, zone 3
provides the remote line with back-up protection. On the other hand, the reach of the second
and third zones can be affected by the presence of in-feed feeders. This may impact the
protection system by introducing security and selectivity issues.
35
An example of under-reaching of relays can be illustrated as shown in Figure 3.7
Considering the example of the 38kV radial network, where the parameters are given as below;
Relay at Busbar Qis the backup relay, while relay at Busbar B is set as the primary relay. With
the integration of DG, the fault current at Busbar C will be;
Where 𝑍𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 is the combination of 𝑍𝑠𝑜𝑢𝑟𝑐𝑒 and 𝑍𝐺𝑒𝑛 . The fault current is a total of
36
𝐼𝑠𝑦𝑠𝑡𝑒𝑚 ≈ 100456° A per phase
It can be depicted that there is a reduction in the system fault current from 1102A to 1004A
with the integration of DG. This may lead to a delay in relay trip time and the required fault
clearance time for the Backup relay may no longer be provided (Klopotan, 2012).
To curb the under-reach problem, there is need for Zone 2 and Zone 3 settings to be increased
which may also lead to loadability reduction (Brady, 2014).
b. Over-reaching of relays
The reverse of under-reaching of relays is over-reaching. Figure 3.7 can be used to illustrate
over-reaching of relays in protection systems.
If overcurrent relays or an Impedance relay (Overcurrent started) are used in the system, DG
could result in over-reach of the relays (Brady, 2014).
c. Loadability reduction
Basically, relay loadability means the capability of the relay to function under high load
conditions. The maximum current a conductor can carry before it anneals losing its elasticity
can be used to describe maximum loadability limit of transmission lines. Usually, calculations
are done to limit the amount of current a conductor can carry before annealing.
37
d. Cascade Tripping
Unexpected loading conditions may result in undesired third zone operations resulting in
cascade tripping. An example is shown on the figure below
Overload conditions in the line led to the load reaching third zone reach of the relays.
Subsequent to the line tripping, loading condition may increase on the part of the line that
remains connected leading to the reach of third zone relays as shown in Figure 3.8. The
outcome is further highlighted if the initial tripping happens in the in-feed feeder. Normally this
occurs in networks with high penetration of DG (Brady, 2014).
The calculation of overcurrent relay settings involves the calculation of the current and time
setting. The load current is used to determine the current setting. Time setting can be
calculated using the formula below;
𝑇𝑀𝑆 𝑥 0.14
𝑡= 𝐼
0.02 (Hudananta et al., 2018)
([𝐼 𝐹 ] −1)
𝑠𝑒𝑡
38
Where;
t= Time of operation in seconds
𝐼𝐹 = Short circuit current in Amps
𝐼𝑠𝑒𝑡 = Current setting
TMS= Time multiplier setting
The current setting of pickup current can be determined in two ways, namely;
Figure 3.9: Multiple sources radial system (Ilik & Arsoy, 2017)
Figure 3.10: Upstream and downstream relays for f1 fault (Ilik & Arsoy, 2017)
The coordination of the directional overcurrent relay can be explained by Figure 3.9 and 3.10.
Relays (R12, R23 and R34) are the downstream relays while (R21, R32 and R43) are the
upstream relays. The downstream relays are coordinated together and only trip from a utility
fault while upstream relays are also coordinated to trip from the DG fault contributions. If a
three-phase fault occurs at f1, then relays R12, R23, R32 and R43 will detect the fault current.
39
The behaviour of the relays is illustrated in figure 3.10, R23 being the main protection relay for
the downstream currents which should trip first. R12 is a back-up relay which will trip if R23
fails to isolate the downstream fault current. Normally the time intervals between the relays is
set between 0.2 to 0.5 seconds. The same applies for the upstream currents, R32 should trip
first as it is the main protection relay. If it fails to isolate the upstream fault currents, then R43
will trip (Ilik & Arsoy, 2017).
It is highly important that the protection system keeps its operating time minimum to increase
the life of equipment and improve voltage quality of a network. Two types of relays will be
analysed in this section.
According to (Onah, 2019), these types of relays are normally used in situations where there
is a small difference between the levels of currents flowing for faults in various points of a
network. In such cases, series wired sections do not have substantial impedances at their
junctions. Normally the impedances of the sections will be less than the source impedance.
The tripping time differences of the relays linked to the adjacent sections is made in such a
way that it is enough to trip the suitable circuit breaker clearing the fault. Generally, time
grading of up to 0.5 seconds is adequate. An example if shown on Figures 3.11 (a) and (b)
below;
40
Figure 3.11 (a) shows an example of a protection system network with definite time relays,
Figure 3.11 (b) illustrates the time grading of 0.5 seconds between the relays. Discrimination
is only dependent on time (Onah, 2019).
These types of relays operate when the current in a power system reaches a predetermined
value. An example is shown below.
Figure 3.12: Definite current relay characteristic curve (Fernnandez Sarabia, 2011)
Settings of the relays are configured such that the relay closest to the source will operate at
the highest current values while the relays furthest to the source operates at small current
values. The relay furthest to the source, operates first isolating the loads from the fault.
Protection settings are based on maximum fault conditions particularly on three phase faults.
A fault will not be cleared until it reaches the protection setting value. The downside of these
relays is that the fault may damage equipment before it is cleared when clearance is prolonged.
Hence definite current relays are rarely used as the only protection devices but rather in
combination with other protection devices (Fernnandez Sarabia, 2011).
The limitation of definite time relays is overcome by using inverse time/ current relays as they
can interrupt bigger faults quickly. An example is shown on Figure 3.13.
41
Figure 3.13: Inverse Time/Current Characteristic Relays (Onah, 2019)
As shown in Figure 3.13 (a) the impedance between the source (𝐸𝑠 ) which is represented by
𝑍𝑠 and the input end of the network (𝐼𝑛 ) is smaller compared to impedance 𝑍𝑝𝑠 . This means
there is a difference in the fault levels 𝐼𝑛 and 𝐼𝑟 . 𝐼𝑛 will be greater than 𝐼𝑟 . In the case, inverse
time/current relays are used as protection devices.
Figure 3.13 (b) shows the relay characteristic curves of the inverse time/current relays. These
relays normally operate under definite minimum operating times greater than certain current
levels and hence why they are called Inverse Definite Minimum Time Relays (IDMT). Their
main advantage is the quick interruption time at high fault currents (Barsoum & Lee, 2018).
42
An example is shown on Figure 3.14;
Figure 3.14: Example of the impact of DG on the distribution network (Wang et al., 2008)
The DG interconnection shown in Figure 3.14 may impact relay protection in the distribution
network. For instance, if a fault occurs at K1, without the connection of DG then the short circuit
current would be solely from the grid. However, with the connection of DG, then it will add onto
the short circuit current. This means that at point OF1 will be affected by the short circuit current
from both, the DG source and the grid. The impact of the protection sensitivity increases as
the DG capacity increases (Wang et al., 2008)
The same happens when a fault occurs at point K2 or K3, without the connection of DG then
OF1 will only see the fault current from the grid and only see short-circuit contribution from DG
when connected. This may impact the line protection when the fault current is large enough.
Relay protection at OF2 will see the short circuit current when a fault occurs at K4 and may
result in wrongful tripping of the instantaneous overcurrent protection of the feeder when DG
is connected. The connection of DG only means there are more than one power source in the
network lines. In the event that there is a fault in one of the lines, but the DG continues to
operate then it may continuously provide short circuit current resulting in the unbound state of
the fault (Wang et al., 2008).
43
3.7.1 Short Circuit levels of the Network
Short-circuit current levels may be increased by the connection of DG into the power system.
Fault currents increase with the penetration of DG as opposed to the operation of the network
when there is only one generating unit. The contribution of the DG sources depends on several
factors including the generating capacity, type of DG and the distance of the DG source from
the fault (Bhise et al., 2017).
When there are power surges within the DG, the DG source may disconnect which is called
nuisance tripping. These power surges may occur when there is a sudden loss of load for
instance, when running a motor connected to a DG, then the motor is suddenly switched off,
then there is power surge which result in nuisance tripping. Any fault that occurs outside the
protection zone, may cause nuisance tripping (Bhise et al., 2017).
It is essential to coordinate DG protection system with the current feeder design in order to
have a positive benefit. The interconnection at which DG is connected is called the Point of
Common Coupling (PCC). Protection settings at the PCC should be done appropriately to
protect DG from any damages and lessen the impact on the grid when there is a fault. The
same applies when interconnecting DG to the utility grid, the right protection should be used
based on numerous factors such as the transformer size, type of generator and the
interconnection point.
Part of the design for the interconnection of DG includes, installation of the Distributed
Generator as per transformer characteristics and the earthing arrangement which should be
compatible with the utility system. Failure to properly ground equipment may result in over-
voltages which can damage equipment (Fernnandez Sarabia, 2011).
In radial networks, there are ways that can be used to check that the protection system is well
coordinated. The primary protection device that is closest to the fault must operate first before
44
other protection devices. The below methods can be used to verify protection coordination,
time based, current based and logic coordination (Nsengiyumva et al., 2018).
This procedure is done by giving the right time to all the relays controlling the circuit breakers
in the protection network. The aim is to ensure the first breaker to trip is the one closest to the
fault and the next backup breaker has a longer time delay. Figure 3.15 shows an example of
how this is done. When there is a fault, then Relays R1 should operate before R2 and R3 as it
is closer to the fault. All three relays will see the fault, R2 will isolate the fault if R1 fails. The
same applies for R3, it will isolate the fault in the event of R1 and R2 failing to operate
(Nsengiyumva et al., 2018).
c. Logic Coordination
This type of protection coordination overcomes the limitation of the time based and current
coordination. An additional advantage is the reduced tripping time delay for the circuit breaker
closest to the source.
45
Figure 3.16: Logic Coordination
As shown in Figure 3.16 Relays R1, R2 and R3 will be activated in the event of a fault. When
the first relay closest to the fault R1 is activated, it immediately delivers a blocking signal to
Relay R2 to allow it to increase the upstream relay time delay. The same applies to Relay R2
and R3 when they get activated. This makes the coordination much more efficient and
increases reduced the time delay in eliminating faults (Nsengiyumva et al., 2018).
Figure 3.17 demonstrates the loss of coordination between protection relays derived from the
advent of DG. For instance, when there is a fault at point F, Relay R7 being the primary relay
while R8 and R9 are backup relays with respect to R7 (R7-R8 and R7-R9). Both pairs will
sense an increase in fault currents when there is a fault. The impact on R7 is not as critical
46
compared to R8 and R9 as it is the primary relay. The CTI for R8 and R9 with respect to R7
may change compared to when the network had no DG (Nsengiyumva et al., 2018).
Furthermore, the loss of coordination can also be demonstrated using the Inverse Time relay
graphs for R7 and R8 coordination. From Figure 3.18 it is evident that the backup Relay R8
speeds up its tripping time with the integration of DG which increase the fault current. R7 is not
affected due to the fact that its tripping time is at the horizontal asymptote curve (Nsengiyumva
et al., 2018). Therefore, the loss of coordination is caused by the fact that CTI can no longer
be conserved between the relay pairs R7-R8.
3.7.5 Islanding
Islanding is the isolation of a portion of a network either naturally or due to dispatch. Islanding
can be demonstrated as seen on Figure 3.19
47
Figure 3.19: Islanding operation (Nsengiyumva et al., 2018)
If there is a fault at point F as seen on Figure 3.19, Relay R10 will isolate the fault. However,
Bus 7 to Bus 10 will create an island network which will be powered by the Distributed
Generation source (DG) (assumption being that it can carry the network and maintain stable
operation).
The impact of islanding on Relay pairs (R7-R8) can further be illustrated by the inverse time
relay graphs as seen on Figure 3.20. When the system enters the islanding mode, backup
Relay R8 will increase its interruption time because there is a reduction in the fault current
while R7 is not affected as it is the primary relay. This may result in an undesired tripping time
of the backup relay when there is a fault (Nsengiyumva et al., 2018).
Figure 3.20: The impact of islanding on Operation of Relays (Nsengiyumva et al., 2018)
48
3.7.6 Protection Blinding
When DG is injected between the feeding substation and a fault location, then the fault current
measured by the relays may be reduced by a size negatively contributed by the DG source.
However, this may negatively impact Overcurrent relays and is undesirable. This is because
the relays see less fault current when there is DG compared to when there is no DG in this
particular situation. This can be illustrated on Figure 3.21
In the event of a fault at F2, the Relay connected to CB4 will not respond to the fault due to
protection blinding.
b. Microgrids;- they are a good way to connect DG without affecting the protection system
of the utility. Microgrids can be designed with their own storage and protection devices.
They can also be interconnected to the grid, or in a self-sufficient way, by being completely
being independent with no connection to the main grid (Wang et al., 2008).
49
fault cleared. However, this could lead to more problems if the DG disconnects too quickly
or too slowly. Normally countries have rules and regulations that stipulate how DG must be
disconnected when there is a fault or abnormalities in the DG source’s voltage and
frequency. In case of automatic reclosing in a network, DG must disconnect before initial
reclosing (Conti, 2009).
e. Using Fault Current Limiters (FCL) to restore relay settings when there is a fault
(Nsengiyumva et al., 2018).
f. Using fault ride through strategy to control all inverter based DGs (Nsengiyumva et
al., 2018). This method is employed by most countries including South Africa.
50
CHAPTER FOUR
MODELLING AND SIMULATION
4.4 Introduction
This chapter analyses how the system was modelled on DigSilent. The West Coast was used
in the studies. This is part of the Western Cape province in South Africa. Data collection was
done at Eskom (South Africa’s utility provider). The modelling of Busbars, transformers, Circuit
Breakers, Loads and other components of the system are described thoroughly. Two types of
DG were modelled in the studies, Wind and Solar PV Generators. The end of the chapter
describes the modelling of the protection relays and their protection settings.
4.2.1 Busbars
The first step of simulating the West Coast network was to model the Busbars. The network
consisted of 14 Busbars in total. The Table below shows the Busbar parameters which were
simulated in accordance with the South African Grid in order to reflect the true effect of
connecting embedded generation into the network.
51
Figures below show an example of how the Busbars were modelled in DigSilent showing load
flow data. The same procedure was used to populate all the Busbars.
52
4.2.2 Circuit Breakers and Terminal Nodes
Circuit Breakers (CBs) were modelled by connecting them between a Busbar and the terminal
nodes. The circuit breakers are part of the protection system for the power system network.
The nodes were rated at the same voltage as the Busbars at which they were connected.
Figures below illustrate the CB and node data used.
53
4.2.4 Line Modelling
Line parameters are shown in Appendix B. The towers and lines were populated on the same
template. The network comprises of overhead lines only with the same type of towers but
different types of conductors. Below is an example of how one of the lines were modelled.
Tower geometry type model was used. All line parameter specifications were as per Eskom’s
West Coast network.
54
Figure 4.6: Line Modelling (b)
4.2.5 Transformers
Refer to Appendix D for transformer specifications. The network comprises of three different
transformer types;
a) Auto-transformers- the basic idea of the autotransformers is to allow the interconnection
of windings electrically. The rating of these transformers is normally higher than the original
two-winding configuration rating (El-Hawary, 2015).
Figure 4.7 shows the basic concept of auto transformers with the windings connected in series.
The network comprises of two autotransformers with the load flow information modelled as
shown on Figure 4.8.
55
Figure 4.8: Auto-Transformer Modelling
b) Two winding transformers- these are the most common with two windings connected on
the primary and secondary core of the transformer (El-Hawary, 2015). Modelling of the two
winding transformers is similar to that of the auto transformers. The modelling is shown
below;
56
different from that of the autotransformers and the two winding transformers. Figure 4.10
shows the modelling of the three-winding transformers.
57
4.2.7 Wind Generator Modelling
The model is representation of Sere wind farm, a wind generator plant in Western Cape
Province, South Africa. Sere windfarm comprises of 44 wind turbines each with an output of
2.3MVA. The combined real power output from the windfarm is 100MW. It is an Eskom owned
windfarm and is situated in an area called Skaapvlei in West Coast.
A DigSilent generic model of the wind generator was used to model the plant and the
information is shown on the figure below. The plant has a two winding transformer which steps
the voltage up from 0.69kV generation voltage to 33kV feeding Koekenaap load and into the
West Coast network.
58
Single line diagram of the Windfarm
Figure 4.14 shows the single line diagram of the windfarm modelled on DigSilent. The wind
generator has been modelled such that it supplies a load at 33kV Bus while excess power is
fed into the grid.
The plant specifications were populated as shown on the figure below. Bulte PV plant has a
transformer connected to it which steps the voltage up from the generation voltage of 0.4kV to
11kV into the West Coast Network.
59
Figure 4.15: Solar PV Modelling
The capability curve reflects the operating regions of the PV plant, see figure below.
60
Figure 4.17: General Load Modelling
61
4.4 Protection system modelling
Apart from the Circuit breakers and NECR for earthing, current transformers and relay settings
were populated into the network. The impedance relays were modelled on the HV network and
partially on the MV network whilst Overcurrent and Earth fault relays were populated as back-
up on HV network and main protection on MV and LV network.
62
4.4.2 Relays
On the HV network, the RED 670 and REF 615 ABB models were used, refer to Table 4.1.
RED 670 ABB is a differential protection Relay normally used on HV Networks. Apart from the
relays’ main role of protection in the power system, it is also used for control and monitoring of
cables and all overhead lines from generation, transmission to distribution networks. The REF
615 ABB relay is a feeder protection relay. It is seamlessly aligned for measurement,
protection, control and supervision of substations and power systems (El-Hawary, 2015).
The Vamp 140 relay, 7SJ50_IT relay and REL 511 relay ABB manufactured relays were used
to model the network in the MV and LV networks.
An outline of all the relays employed in the network is shown in Tables 4.1 and 4.2.
63
Table 4.5: Relay Protection Settings (Distance Protection)
Protection Device Location Branch Manufacture Model Stage Reactance Reactance Resistance Resistance Time Directional Stage Reactance Reactance Resistance Resistance Time Directional
r (Phase) [pri. Ohm] [sec. Ohm] [pri. Ohm] [sec. Ohm] (Earth) [pri. Ohm] [sec. Ohm] [pri. Ohm] [sec. Ohm]
Juno_Bulte Juno/66 kV
1 1_REL511 BB Juno-Bulte ABB REL 511 Z1P 3.000 3.000 1.970 1.970 0.00 Forward Z1G 3.000 3.000 1.970 1.970 0.00 Forward
Z2P 9.370 9.370 6.160 6.160 0.40 Forward Z2G 9.370 9.370 6.160 6.160 0.40 Forward
Z3P 0.940 0.940 0.620 0.620 2.50 Reverse Z3G 0.940 0.940 0.620 0.620 2.50 Reverse
Z4P 45.140 45.140 29.620 29.620 3.00 Forward Z4G 45.150 45.150 29.620 29.620 3.00 Forward
61
Table 4.6: Overcurrent Protection Relay Settings
Protection Device Location Branch Manufacture Model Stage Current Current Current Time Characteristic Directional Stage Current Current Current Time Characteristi Directional
r (Phase) [pri.A] [sec.A] [p.u.] (Earth) [pri.A] [sec.A] [p.u.] c
Bulte/11 kV GAD_2xOC_EF<0.1-
1 Bulte_Municipal_GAD BB General Load Reyrolle 0.9>_SEF_1A A> 350 1.75 1.75 0.25 NI None EF> 60 0.30 0.30 0.20 NI None
IEC
Bulte/11 kV Bulte-Bulte PV IEC standard standard
2 Bulte_PV 1_P145 BB Farm Areva P14x 100-120 V I>1 672 0.84 0.84 0.31 inverse Forward IN1>1 96 0.12 0.12 0.19 inverse Forward
62
Table 4.7: Instrument Transformer Settings
Ratio Ratio
Protection Device Location Branch Manufacturer Model CT Slot VT Slot
[pri.A/sec.A] [pri.V/sec.V]
Bulte/11 kV GAD_2xOC_EF<0.1-
1 Bulte_Municipal_GAD BB General Load Reyrolle 0.9>_SEF_1A Bulte_Municipal_CT Ct-3p 200A/1A
Bulte/11 kV Bulte_11 11000V/110
2 Bulte_PV 1_P145 BB Bulte-Bulte PV Farm Areva P14x 100-120 V Bulte_PV 1_CT Ct-3P 800A/1A kV BB_VT Vt-3P V
Bulte_Transformer 1_VAMP Bulte/11 kV
3 140 BB Bulte 66/11 kV T1 VAMP VAMP 140 Bulte_Transformer 1_MVOC_CT Ct-3p 600A/1A
Bulte_Transformer 1_VAMP Bulte/66 kV
4 140_HV B/U E/F BB Bulte 66/11 kV T1 VAMP VAMP 140 Bulte_Transformer 1_HVEF_CT Ct-3I0 200A/1A
Bulte_Vanrhynsdorp 1_VAMP Bulte/66 kV
5 140 BB Bulte-Vanrhynsdorp VAMP VAMP 140 Bulte_Vanrhynsdorp 1_CT Ct-3p 400A/1A
Juno/66 kV
6 Juno_Bulte 1_7SJ50 BB Juno-Bulte Siemens 7SJ50_IT Juno_Bulte 1_CT Ct-3P/3xI0 600A/1A
Juno/66 kV Juno_66 66000V/110
7 Juno_Bulte 1_REL511 BB Juno-Bulte ABB REL 511 Juno_Bulte 1_CT Ct 600A/1A kV BB_VT Vt V
Juno/132 kV
8 Juno_Koekenaap 1_7SJ50 BB Juno-Koekenaap Siemens 7SJ50_IT Juno_Koekenaap 1_CT Ct-3P/3xI0 600A/1A
Juno/132 kV 1200A/1 Juno_132 132000V/11
9 Juno_Skaapvlei 1_RED670 BB Juno-Skaapvlei ABB RED 670 Juno_Skaapvlei 1_CT Ct A kV BB_VT Vt 0V
63
CHAPTER 5
RESULTS
5.1 Introduction
This chapter analyses the results obtained from the network model simulated in DigSilent
PowerFactory. The chapter begins by analysing the fault levels before and after the connection
of DG. Three-phase faults are analysed on Busbars and single-phase to ground fault on the
network lines. The results of the fault currents will be populated in tables and discussed as part
of case study 1.
Case study 2 will cover results obtained from Overcurrent relays and the characteristic curves
of the IDMT Relays before and after the connection of DG. Time grading of the protection
relays will also be analysed. Part of the results also includes Case study 3 which outlines the
results obtained from the Distance Relays.
The IEC 60909 was used to analyse the fault current levels before and after the connection of
DG. The impact of the DG on the network will be analysed by comparing the fault level currents
on the conventional network and when it includes DG. Two types of faults are covered which
are single-phase to ground faults (accounts for about 70% of faults in a power system) and
three-phase faults (symmetrical).
In order to determine some of the effects on the protection system of connecting DG to the
utility grid, it is important to analyse the percentage change in fault currents before and after
the connection of DG. All DG sources connected to the grid contribute to fault current levels
and can have a substantial impact on the performance of protection devices.
64
Figure 5.1: Single-phase to Ground Fault on transmission line
A summary of the fault levels on the Aurora to Juno 400kV line is shown on Table 5.1 shows
the short circuit currents at different distances of the 400kV line from Bulte to Juno substation.
After
Distance Before % After Skaapvlei % After both
Bulte PV % Change
of the line both DG Change Wind Generator Change DG plants
farm
65
From Table 5.1, it can be depicted that the most impact is at 100% of the Juno to Bulte line
after the connection of DG. Skaapvlei Wind Generator contributing the most fault currents with
a 7.9% increase in fault levels.
After
Distance Before % After Skaapvlei % After both
Bulte PV % Change
of the line both DG Change Wind Generator Change DG plants
farm
A summary of the fault levels in case of a single-phase to ground fault on the Juno to Bulte
66kV line is summarised in Table 5.2. DG input to the fault current levels is very low with the
highest increase in fault levels of 4% after the combined connection of the Solar and Wind
Generators, 0% of the line.
After
Distance Before % After Skaapvlei % After both
Bulte PV % Change
of the line both DG Change Wind Generator Change DG plants
Generator
Amps Amps Amps Amps
Table 5.3 shows the fault levels at 0% and 100% of Bulte 11kV line. It can be depicted that
there is an increase in the fault levels with the worst-case scenario at 100% of the line which
is towards the Solar PV Generator. 6.34% increase in fault levels is a result of the Bulte PV
Generator. Earth Fault and overcurrent protection is applied on the MV and LV networks using
66
the IDMT Relays. The fault current results were used to model the IDMT curves in case of a
fault which is explained in Case Study 3.
b) Three-phase faults
DigSilent Software was used to calculate the fault currents in the event of a three-phase fault
at each Busbar in the network with and without the connection of DG.
AFTER
AFTER
BEFORE % SKAAPVLEI % WITH BOTH DG %
SUBSTATION BULTE PV
DG CHANGE WINDFARM CHANGE PLANTS CHANGE
FARM
ONLY
Juno 400 kV BB
5017 5032 0.30% 5133 2.31% 5146 2.57%
Juno 132 kV BB
5674 5718 0.78% 6035 6.36% 6077 7.10%
Koekenaap 132
3155 3170 0.48% 3251 3.04% 3263 3.42%
kV BB
Skaapvlei 132 kV
0 0 0 3028 0 3037 0
BB
Vredendal 66 kV
2346 2374 1.19% 2349 0.13% 2376 1.28%
BB
Vanrhynsdorp 66
1628 1662 2.09% 1622 -0.37% 1656 1.72%
kV BB
Vanrhynsdorp
1870 1889 1.02% 1850 -1.07% 1868 -0.11%
22 kV BB
67
5.3 Case study 2: Overcurrent Protection (MV & LV Networks)
This section will outline the results obtained from the DigSilent modelled Overcurrent relay
settings. The results will be shown in the form of Overcurrent relay graphs reflecting the time
delay settings on each relay when there is a three-phase fault.
The figure above shows an illustration of the overcurrent relay connected to the LV side of the
two-winding transformer. IDMT relays are used on the network and the relay characteristic is
shown on the figure above. The fault current of 4 652kA is symbolised by a vertical line cutting
the relay characteristic curve at 1.13s. The IDMT relay will trip in 1.13s when a fault occurs at
Bulte 11kV BB before the connection of Distributed Generation. The 1.13s is because there
are two more relays that would trip before the relay at the transformer however to illustrate the
impact of the connection of DG, the relay at the LV side of the transformer is analysed.
68
Figure 5.3: IDMT Relay characteristic after connection of DG
Figure 5.3 shows the IDMT relay characteristic of the relay connected to the LV side of the
two-winding transformer after the connection of DG. There is fault current contribution mostly
from the Bulte Solar PV Farm causing a shift in the IDMT Curve. The relay trip time is 1.51s
compared to 1.1s before connection of DG. This is because the relay at the Solar PV Farm
would trip before the transformer relay.
The relay characteristic curves of the IDMT relays and their grade margins in the event of a
fault were displayed using DigSilent PowerFactory software. The relays have a grading margin
of 0.4s which is the IEC requirement/standard.
69
IDMT Relay B
IDMT Relay A
The above figure shows the relay characteristic curves of the Overcurrent relays, the fault
currents and grade margins. When there is a three-phase fault at Bulte 11kV Busbar, IDMT
Relay A (purple), the one closest to the Solar PV Farm is set to trip within 1.1 seconds. IDMT
Relay, (Red curve) represents the relay on the LV side of Bulte Transformer which would trip
in 1.5 seconds. Other relays connected in the network have not been demonstrated, one relay
would trip instantaneously and the other within 0.4 seconds.
Using the Time-based coordination explained in Chapter 3, IDMT Relay A is closest to the fault
and should see the fault before IDMT Relay B.
70
5.4 Case study 3: Distance Protection Relays
Characteristics of the distance relays were derived from the network in the event of fault. Figure
5.5 shows the fault location in the network. Figure 5.6 shows the characteristic of Skaapvlei
distance relay when there is a three-phase fault on the Skaapvlei to Juno line. The short-circuit
currents were calculated using the IEC 60909 method
71
In the event of a fault at 0% of line, Zone 1 will trip instantaneously as shown in Figure 5.6.
Distance relays are also used in all the zones with a time grading of 0.4s. When there is a fault in
Zone 1, the relay will trip instantaneously while Zone 2 will trip in 0.4s. For a fault at 100% of line,
the fault will be seen in Zone 2 time as shown in Figure 5.8 and will trip in 0.4s. Zone 1 is set to
cover 80% of line whilst Zone 2 should cover 120% of line.
Figure 5.8: Distance Relays characteristic curve after Skaapvlei fault at 100% of the line
If Zone 1 and Zone 2 relays do not isolate the fault, then Zone 3 Relay will trip in 0.8 seconds.
72
CHAPTER 6
DISCUSSION, CONCLUSION AND RECOMMENDATIONS
6.1 Introduction
This chapter gives a general discussion of the thesis particularly of the results obtained. A
conclusion is drawn and ends with recommendations to curb the impact of DG on the electric
protection system.
The main aim of the research was to investigate the impact of DG on the electric protection
system by using DigSilent software to simulate a network showing pre- and post- connections
of DG particularly wind and solar Photovoltaic (PV) to clearly show fault levels and any change
in the relay settings/protection system. The two types of DG technologies investigated are the
most common in South Africa. Based on the results obtained in Chapter 5, there was an
increase in fault levels in the event of three phase faults on Busbars and single-phase to
ground faults on the lines. The most impact occurred at the point closest to the DG sources
which led to an increase in fault levels.
The relays were coordinated with a time grading of 0.4seconds and it could be seen on the
Overcurrent relays that the relay trip time changed from 0.4 seconds to 0.8 seconds to
accommodate the penetration of DG. High penetration of DG into the network could easily
result in loss of coordination therefore it is important that utilities design their protection
systems to accommodate the penetration of DG in the future.
Other studies have identified some of the problems related to the connection of DG to the
power network particularly on the protection system including nuisance tripping, islanding,
protection blinding amongst others, two particular impacts have been identified in this study
which is the impact on short circuit levels and protection coordination. The radial characteristic
of the traditional power system also changes with the penetration of DG. Some of the solutions
adopted to curb the effects of the connection of DG include limiting the generation sizes, using
Fault Current Limiters and adaptive protections schemes.
73
6.3 Conclusion
Global concern regarding energy costs, security and greenhouse gases has left the power
industry resorting to Flexible AC Transmission Systems elements and Renewable Energy
Sources mostly in the form of DG. The penetration of DG into the power network which was
primarily designed to work as a radial network can create a full spectrum of problems ranging
from voltage profile, power flow, protection and stability. The study carried out focused on the
impact of DG on the protection system.
Based on the analysis and results obtained from the study, it is apparent that these DG sources
contribute to the level of fault current. In order to limit some of the effects on the protection
system of connecting DG to the utility grid, it is important to know the percentage change in
fault currents before and after the connection of DG. The IEC60909 method was used to
analyse fault current pre and post connection of DG. There was an overall increase in short
circuit current with the connection of DG. The maximum fault current increase was seen on the
Busbars closest to the DG sources. Overcurrent protection was applied in the MV and LV
networks, clearly indicating the impact of DG on protection coordination of the relays. The
study analysed the fault current contribution percentage increase on transmission lines with
the connection of DG. This was seen to impact distance relays and could significantly impact
coordination of the relays. It can be concluded that DG has an impact on the short circuit levels
and on protection coordination in an electric grid.
While the size of the DG sources currently embedded in the South African grid are insignificant
enough to pose a big threat on the protection devices, there is a huge growth in the
development and integration of these generators and hence it is important to make sure the
protection system can handle the fault currents.
6.4 Recommendations
1. Utilities that are still expanding and adopting cleaner energy like South Africa need to take
DG into account when designing their utility expansion by making sure the protection
devices can accommodate numerous generation sources at any level of the power
network. While this can be a costly move, it avoids any serious implication of the
penetration of DG into the network.
2. A study of the penetration of DG into the network and how it might affect the protection
system needs to be carried out before the DG sources are connected into the utility grid.
Plant owners to need to seek approval from Municipalities or relevant authorities before
they can connect into the network.
74
Bibliography
A.O. Osahenvemwen, O.O. 2008. Electric Power Transmission line Faults in Nigeria.pdf.
International Journal of Electrical and Power Engineering, 2(6).
Ahmad, A. & Bukka, S.K. 2015. Implementation of Adaptive Zone-2 Protection for
Transmission Lines. International Journal Of Modern Engineering Research (IJMER),
5(6): 6–13. www.ijmer.com.
Báez-Rivera, Y., Schulz, N.N. & Gao, W. 2006. Advanced modeling of micro-turbine controls
for system analysis. Power Systems Conference 2006: Advanced Metering, Protection,
Control, Communication and Distributed Resources, PSC, IEEE, 229: 219–223.
Bari, N.A., Jawale, S.D. & Deshmuikh, B.T. 2017. Adaptive Over-Current Protection for
Distribution System with Distributed Generation. International Journal of Innovative
Research in Electrical, Electronics, Instrumentation and Control Engineering
(IJIREEICE), 5(9): 13–18.
Barsoum, N. & Lee, K. 2018. Simulation of Overcurrent Relay in 33kV Power Grid Protection.
Open Science Journal of Electrical and Electronic Engineering, 5(5): 54–63.
http://www.openscienceonline.com/journal/j3e.
Bello, M., Smit, R., Carter-Brown, C. & Davidson, I.E. 2013. Power Planning for renewable
energy grid integration - Case Study of South Africa. IEEE Power and Energy Society
General Meeting: 1–5.
Bhise, D.R., Kankale, R.S. & Jadhao, S. 2017. Impact of distributed generation on protection
of power system. IEEE International Conference on Innovative Mechanisms for Industry
Applications, ICIMIA 2017 - Proceedings, (Icimia): 399–405.
Bohlmann, H.R., Horridge, J.M., Inglesi-Lotz, R., Roos, E.L. & Stander, L. 2019. Regional
75
employment and economic growth effects of South Africa’s transition to low-carbon
energy supply mix. Energy Policy, Elsevier, 128(January): 830–837.
https://doi.org/10.1016/j.enpol.2019.01.065.
Boxwell, M. 2012. Solar Electricity Handbook. 6th Editio. S. Glasbey, ed. Warwickshire, United
Kingdom: Greenstream Publishing. www.GreenstreamPublishing.com.
Brady, C. 2014. Investigation of Relay Protection Systems in MV Networks With Large in-feed
of DIstributed Generation. Department of Enrgy Technology, Aalborg University,
Denmark, (June): 96. www.et.aau.dk.
Chiradeja, P. 2005. Benefit of Distributed Generation : A Line Loss Reduction Analysis. IEEE
Power and Energy Society General Meeting: 1–5.
Choudhary, N.K., Mohanty, S.R. & Kumar Singh, R. 2015. Coordination of Overcurrent Relay
in Distributed System for Different Network Configuration. Journal of Power and Energy
Engineering, 03(10): 1–9. http://dx.doi.org/10.4236/jpee.2015.310001.
Department of Energy. 2011. Integrated Resource Plan for Electricity 2010-2030. Department
of Energy (South Africa), (March): 78. http://www.energy.gov.za/IRP/irp
files/IRP2010_2030_Final_Report_20110325.pdf.
El-Hawary, M. 2015. Electrical Power Systems. P. M. Anderson, ed. New York, USA: IEEE
Press.
Eskom Holdings SOC Ltd. 2019. Coal Power. Eskom Holdings SOC Ltd.
76
http://www.eskom.co.za/AboutElectricity/ElectricityTechnologies/Pages/Coal_Power.asp
x 26 March 2019.
Eskom Holdings SOC Ltd. 2010. Distribution Policy: POLICY FOR NEUTRAL EARTHING OF
ELECTRICAL NETWORKS. Policy Document, (May).
http://www.eskom.co.za/Whatweredoing/Documents/Eskom_policy_for_neutral_earthin
g_of_electrical_networks_DPL_34-2149.pdf.
Folarin, A., Sakala, J.D., Matlotse, E. & Gasennelwe-jeffrey, M.A. 2018. Modeling and
Simulation of Faults in Distribution Network System Using MATLAB / Simulink 1 Dauda.
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE), 13(3): 43–51.
www.iosrjournals.org.
Frede Blaabjerg, Yongheng Yang, D.Y. 2017. Distributed Power-Generation Systems and
Protection. IEEE: 1–21.
Gawande, S.P., Porate, K.B., Thakre, K.L. & Bodhe, G.L. 2011. Synchronization of
Synchronous Generator and Induction Generator for Voltage. 2010 3rd International
Conference on Emerging Trends in Engineering and Technology: 407–412.
http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=5698358&isnumber=569827
8%0A.
Guaitolini, S.V.M., Yahyaoui, I., Fardin, J.F., Encarnacao, L.F. & Tadeo, F. 2018. A review of
fuel cell and energy cogeneration technologies. 2018 9th International Renewable Energy
Congress, IREC 2018 (IEEE), (Irec): 1–6.
http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=8362573&isnumber=836244
2.
Herbert, G.M.J., Iniyan, S., Sreevalsan, E. & Rajapandian, S. 2007. A review of wind energy
technologies. Renewable and Sustainable Energy Reviews, Elsevier, 11: 1117–1145.
Hudananta, S., Haryono, T. & Sarjiya. 2018. Study of overcurrent protection on distribution
network with distributed generation: An Indonesian case. Proceedings - 2017
International Seminar on Application for Technology of Information and Communication:
Empowering Technology for a Better Human Life, iSemantic 2017, 2018-Janua: 126–131.
77
Iagǎr, A., Popa, G.N. & Diniş, C.M. 2018. Study of a phase-to-ground fault on a 400 kV
overhead transmission line. IOP Conference Series: Materials Science and Engineering,
294(1): 14.
Ilik, S.C. & Arsoy, A.B. 2017. Effects of Distributed Generation on Overcurrent Relay
Coordination and an Adaptive Protection Scheme. IOP Conference Series: Earth and
Environmental Science, 73(1).
International Finance Corporation, W.B.G. 2015. Utility-Scale Solar Photovoltaic Power Plants.
World Bank Group.
Jain, S. & Jain, P.K. 2017. The rise of Renewable Energy implementation in South Africa.
Energy Procedia, Elsevier, 143: 721–726. https://doi.org/10.1016/j.egypro.2017.12.752.
Jauch, C., Sørensen, P., Norheim, I. & Rasmussen, C. 2007. Simulation of the impact of wind
power on the transient fault behavior of the Nordic power system. , 77: 135–144.
Józef, L., Bartosz, O. & Aleksandra, S. 2018. Overcurrent Protections in MV Grid with Local
Energy Sources. Institute of Electrical Power Engineering, Poznań University of
Technology, Poznań, Poland, 64: 08005.
Keller, K. 2010. Overcurrent Protection Learn more about Overcurrent Protection Electrical
System Grounding and Bonding Protection of DERs. Elsevier: 16.
https://www.sciencedirect.com/topics/engineering/overcurrent-protection 23 June 2019.
Krupa, J. & Burch, S. 2011. A new energy future for South Africa: The political ecology of South
African renewable energy. Energy Policy, Elsevier, 39(10): 6254–6261.
http://dx.doi.org/10.1016/j.enpol.2011.07.024.
78
Lasseter, R. 2002. Dynamic models for micro-turbines and fuel cells. 2001 Power Engineering
Society Summer Meeting. Conference Proceedings (Cat. No.01CH37262), IEEE, 2: 761–
766 vol.2.
Nehrir, H., Caish & Shaw, S.R. 2006. Fuel cells: promising devices for distributed generation.
IEEE Power and Energy Magazine, 4(1): 47–53.
http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=1578531&isnumber=33348%
0A.
Neisius, H.T., Dzafic, I., Henselmeyer, S., Ablakovic, D. & Lecek, N. 2012. Modeling of auto-
transformers for load flow calculations. IEEE PES Innovative Smart Grid Technologies
Conference Europe: 1–6.
http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=6465850&isnumber=646560
1.
NERSA. 2014. GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS ( RPPs )
CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM ( TS ) OR THE
DISTRIBUTION SYSTEM ( DS ) IN SOUTH AFRICA. NERSA, 8(July).
Niwas, S., Singh, S., Østergaard, J. & Jain, N. 2009. Distributed Generation in Power Systems:
An Overview and Key Issues. Proceedings of IEC.
http://orbit.dtu.dk/files/5202512/24IEC_paper.pdf.
Nsengiyumva, E., Saulo, J.M. & Nyakoe, G.N. 2018. APPLICATION OF ADAPTIVE
PROTECTION SCHEME IN DISTRIBUTION NETWORKS WITH DISTRIBUTED
GENERATION : A REVIEW. International Journal of Engineering Technology and
Scientific Innovation, 03(05): 14. www.ijetsi.org.
79
Onah, A.J. 2019. Investigating Phase Over-Current ( OC ) Protection in Medium-Voltage
networks. European Journal of Engineering Research and Science (EJERS), 4(6): 41–
49. http://dx.doi.org/10.24018/ejers.2019.4.6.1307.
Pegels, A. 2010. Renewable energy in South Africa: Potentials, barriers and options for
support. Energy Policy, 38(9): 4945–4954. http://dx.doi.org/10.1016/j.enpol.2010.03.077.
Pepermans, G., Driesen, J., Haeseldonckx, D., Belmans, R. & D, W. 2005. Distributed
generation : definition , benefits and issues $. Elsevier, 33: 787–798.
Raj, A., Gupta, M. & Panda, S. 2016. Design Simulation and Performance Assessment of Yield
and Loss Forecasting for 100 KWp Grid Connected Solar PV System. 2016 2nd
International Conference on Next Generation Computing Technologies (NGCT), IEEE,
(October): 528–533.
Saad, S.M., El Naily, N. & Mohamed, F.A. 2018. Investigating the effect of DG infeed on the
effective cover of distance protection scheme in mixed-MV distribution network.
International Journal of Renewable Energy Development (IJRED), 7(3): 223.
http://ejournal.undip.ac.id/index.php/ijred.
Thakur, T. 2016. Three Phase Faults Analysis of Power System. Global Journal of Researches
in Engineering (USA), 16(5): 13.
The University of Edinburgh. 2017. Renewable Energy | The Solar Spark. The University of
Edinburgh. http://www.solarspark.chem.ed.ac.uk/science/renewable-energy 30 March
2019.
Times Media. 2015. Eskom and SA Energy Crisis. Cape Town: Times Media Books.
Wang, C. & Nehrir, M.H. 2006. Distributed Generation Applications of Fuel Cells. 2006
Power Systems Conference: Advanced Metering, Protection, COmmunication, and
80
Distributed Resources (IEEE): 244–248.
http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=4064675&isnumber=406464
2.
Wang, W., Pan, Z.C., Cong, W., Yu, C.G. & Gu, F. 2008. Impact of distributed generation on
relay protection and its improved measures. 2008 China International Conference on
Electricity Distribution, CICED 2008, IEEE: 1–5.
81
Appendix A: West Coast Overview (South Africa)
75
Appendix B: Line Parameters
76
Appendix C: Busbar Voltages
1 Helios 400kV
2 Aurora 400kV
3 Juno 400kV
4 Juno 132kV
5 Koekenaap 132kV
6 Skaapvlei 132kV
7 Juno 66kV
8 Vredendal 66kV
9 Butle 66kV
10 Vanrhysdorp 66kV
11 Vanrhysdorp 22kV
77
Appendix E: General Loads
Voltage
Load Active Power Reactive Power
(Per unit)
Helios 145.845 MW 86.775 MVar 1.0
78