Datasheet

ECLYPSE™ Connected System


Controller

Overview Features & Benefits


The ECLYPSE Connected System Controller is Connectivity
a modular and scalable platform that is used to
control a wide range of HVAC applications. It The different types of connections supported by
supports multi-protocol communications the Connected System Controller are the
including BACnet/IP and is a listed BACnet following:
Building Controller (B-BC).
IP wired connection
The ECLYPSE Connected System Controller
consists of a control, automation and Internal switch with two Ethernet ports allows
connectivity server, power supply, and I/O the controllers to be wired in a star or daisy-
extension modules. chain topology. With a daisy-chain topology:
This programmable Connected System £ Fewer wire runs to a centralized switch are
Controller provides advanced functionality such required, thereby achieving installation and
as customizable control logic, Web-based cost reduction.
design and visualization interface (ENVYSION £ A laptop can be connected to the second
embedded), logging, alarming, and scheduling. Ethernet port for direct programming,
configuration, and commissioning using EC-
Applications gfxProgram or ENVYSION.
The ECLYPSE Connected System Controller is IP wireless (Wi-Fi) connection
typically used as: The following types of Wi-Fi connections are
£ A controller for medium/large sized Air possible when using the ECLYPSE Wi-Fi
Handling Units (AHU), central plant, lighting, Adapter:
power monitoring, and other applications. £ Wi-Fi Client - Connection to the building’s
£ Small building server and equipment existing Wi-Fi network or to another
controller with embedded ENVYSION. For controller’s Wi-Fi Hotspot or Access Point.
example, it can be used to control and serve £ Wi-Fi Access Point - extending the building’s
a boiler room. wired IP network to your Wi-Fi Client
devices.
£ Wi-Fi Hotspot - your own wireless area Open RESTful API
network, for wireless communication
between the controllers, or with a mobile With the RESTful API, the Connected System
device or laptop for configuration, Controller’s data can be accessed from different
commissioning and servicing. applications, such as energy dashboards,
analytics tools, and mobile applications. The
Both IP wired and wireless (Wi-Fi) connection RESTful API documentation explains the
The availability of both Ethernet ports and USB implementation protocol for this interface.
ports for the Wi-Fi Adapter, allows for
simultaneous wired IP and Wi-Fi communication
ENVYSION & xpressENVYSION - Web-
on the same controller, allowing you to choose based Graphic Design and Visualization
and combine these connection methods. For Interface
example, Wi-Fi can be used between two
controllers to jump a large atrium. ENVYSION is a web-based graphic design and
visualization interface used to create and deliver
Connect from anywhere interactive graphical user interfaces and an
optimal user experience for building owners and
Control technicians, facility managers,
facility managers to better manage facility data.
occupants, and others can easily connect to the
system, on-site or off-site, using the different xpressENVYSION offers a simplified and
available tools: streamlined experience in a workflow oriented,
£ ENVYSION to create and view the graphical drag & drop GUI environment while ENVYSION
interface still offers the full customization features and
editing environment.
£ EC-gfxProgram to create custom control
sequences £ The ECLYPSE Connected System
Controller comes embedded with both
£ myDC Control to view, edit, and configure
ENVYSION Studio and Viewer, and
system operating parameters xpressENVYSION.
IP Communication
£ Increased speed and improved handling of
numerous trend logs that enable
applications such as advanced analytics that
require a large amount of data.
£ Experience faster response and save time
when programming, configuring, creating
and viewing graphics, and upgrading your
system.
£ Control technicians can connect the
ECLYPSE Wi-Fi Adapter to the Connected Programmability
System Controller thereby creating a Wi-Fi
Hotspot network. The control technician can Supports Distech Controls’ EC-gfxProgram,
then connect wirelessly to the system using which makes Building Automation System
a mobile device or laptop, for faster, easier (BAS) programming effortless by allowing you to
system configuration, programming, visually assemble building blocks together to
commissioning and servicing. create a custom control sequence for any
£ The controller can be part of a Wi-Fi mesh HVAC / building automation application.
network that increases wireless network
reliability and robustness that allows for a
larger coverage area. Wi-Fi mesh is ideal for
areas where there is no line of sight or
where radio signals are intermittently
blocked.
£ Hostname management allows the controller
to be addressed by a nickname to facilitate
network management.

2 / 20 ECLYPSE™ Connected System Controller


Batch EC-gfxProgram Projects and BACnet/IP Device
Firmware Download The Connected System Controller is BTL-listed
EC-gfxProgram projects can be downloaded in as a BACnet Building Controller (B-BC) and is
batch to multiple controllers, for greater time certified WSP B-BC (Europe) and AMEV AS-A
savings. Batch firmware update can also be & AS-B (German-speaking countries). It
performed on multiple controllers. supports BACnet/IP for faster communication in
comparison to the traditional twisted pair
Simplified Network Commissioning communication bus.

The XpressNetwork Utility saves you time and Multi-Protocol Support


expense by giving you increased control over
multiple ECLYPSE controllers through device The Connected System Controller supports a
discovery and batch operations such as range of communication protocols such as
configuring and updating multiple ECLYPSE BACnet MS/TP, Modbus RTU, and Modbus
controllers on the network. TCP.
In addition, with the embedded step by step BACnet MS/TP and Modbus RTU
Commissioning Wizard, all configuration communications are made by connecting
operations can be setup and applied in one go. directly to separate RS-485 ports. The
Connected System Controller integrates up to
Increase productivity using the XpressNetwork three RS-485 ports when equipped with one
Companion mobile app, making it easier to ECY-RS485 extension module allowing the
identify and locate a controller on the network. controller to support more than one trunk or
Use the QR Code marked on ECLYPSE communication protocol at a time.
controllers to easily collect key controller data
and to facilitate its network integration with MS/TP to IP routing
XpressNetwork Utility.
Integrate full MS/TP trunks into a supervisory
Scalable and Modular system like the EC-NetAX Supervisor, without the
need for other hardware components such as
The Connected System Controller is sized to an external BACnet MS/TP to IP router.
cost-effectively meet the requirements of any
HVAC application from small to medium to large Modbus RTU and TCP
systems. The most capable Connected System Modbus RTU and TCP communication can be
Controller model can be expanded to support up used to integrate a wide variety of Modbus
to 20 input/output (I/O) modules (up to 320 I/Os) devices such as power and water meters,
while being able to adapt to new requirements Variable Frequency Drives, air flow sensors,
as the need arises. and more, without the need for additional
A range of I/O modules are available that have hardware such as a gateway.
universal inputs and outputs, digital inputs with
fast pulse support for use with energy meters
FIPS 140-2 Level 1 Compliant
and counters, 24VAC triac outputs for use with FIPS 140-2 Level 1 compliance provides an
smaller load applications (up to 1 amp) such as enhanced level of security to protect data the
electric fans and motors/actuators and relay controller is collecting and sharing making it
outputs for larger load/high power applications suitable for use in the most sensitive
such as electric heat and high power actuators. environments.
The Connected System Controller’s recurrent
power supply concept can be used when more Weather Forecast
power is required to power a series of I/O The weather forecast is directly available from
modules. A 100 to 240VAC power supply the internet to be shown on a connected ECx-
module eliminates the need for a line voltage to Display or to be used by the controller’s code.
24VAC power transformer to save installation
costs and time. A 24 VAC / VDC power supply Smart Room Control Support
module is equally available.
An ECY-RS485 communication module adds The Smart Room Control solution is an end-to-
two extra RS-485 trunks to support more end system for the control of HVAC equipment,
BACnet MS/TP and Modbus RTU devices. lighting, and shades/sunblinds, achieving the
highest levels of comfort for occupants while
A connecting cable is used to connect cutting costs from installation time and wiring/
successive rows of modules within a controls’ material requirements to energy consumption.
cabinet to provide power and communication. This solution combines:

ECLYPSE™ Connected System Controller 3 / 20


£ Lighting and shade/sunblind expansion Mobility
modules to control lights (DALI, on/off or
dimming) and shades/sunblinds (24 VDC or The controller can be remotely accessed to
100-240 VAC, up/down and angle rotation). program, configure, or maintain the installation
£ Multi-sensor combining motion and thus reducing costs associated with on-site
luminosity (Lux) sensors and equipped with visits. Through a mobile device or PC, a range
an Infrared receiver that works with a of tasks can be performed using the following
convenient remote control. free-to-use tools and interfaces:
£ Wireless (infrared) personal remote control £ ENVYSION web-based graphic design and
for increased occupant comfort. visualization interface
£ Allure™ Series Communicating Sensors for £ EC-gfxProgram graphical programming
increased occupant comfort settings. interface
£ myDC Control mobile application
Allure™Series Communicating
Sensor Support Hand/Off/Auto Switches and
Potentiometers
These controllers work with a wide range of
sensors, such as the Allure Series The front assembly of Hand/Off/Auto (HOA)
Communicating Sensors that are designed to equipped I/O models allow users to override the
provide intelligent sensing and control devices control outputs for commissioning and
for increased user experience and energy maintenance purposes.
efficiency. Universal outputs have potentiometers providing
£ Allure EC-Smart-Vue sensors feature a manual analog signal and output control to
backlit-display and graphical menus that override voltage or current signal.
provide precise environmental zone control,
with any combination of the following: High-Efficiency Design
temperature, humidity, CO2, and motion
sensor. The power supply uses the latest high-efficiency
switch-mode circuitry to make more power
£ Allure EC-Smart-Comfort sensors feature
available to operate additional modules and for
colored LED indicators to provide user
cooler operation.
feedback, rotary knobs to adjust the setpoint
offset and fan speed, and an occupancy Hot-Swappable Tool-Less Design and
override push button. This sensor can also
be expanded with a combination of up to 4 Unique Latching Mechanism
add-on push button modules for lighting and
The I/O modules are hot-swappable for
shade/ sunblind control.
replacement without interrupting power and
£ Allure EC-Smart-Air sensors combine communications to other modules.
precise environmental sensing in a discreet
and alluring enclosure for temperature, The front assembly of I/O modules separate
humidity, and CO2. from the wiring base by pushing the two latches
up to unlock a module’s front assembly and then
opening and pulling the hinged gull-wing covers.
The latch design locks the front assembly to the
wiring base.
The hinged gull-wing design protects and cover
the stacked dual row I/O terminal strips.

4 / 20 ECLYPSE™ Connected System Controller


Ease of Installation Robust Protection
The Connected System Controller modules are The I/O modules are protected against mis-
plug & play devices. They are equipped with wiring and faults to prevent damage caused by
HD-15 connectors that transmits power and incorrect wiring or other mishaps.
communications to the next module for fast and
The power supply module contains over-voltage
easy assembly.
and over-current output protection to protect the
I/O Status LEDs electronics in unstable power supply conditions
and against mis-wiring.
The status LEDs on the I/O modules allows the
user to confirm the status of the inputs/outputs Alarms, Trend Log, Schedule Support
and facilitate commissioning and
Embedded alarms, trend log and schedule
troubleshooting.
support allows for fully distributed data and logic
Auto-Addressing providing a more robust system. Embedded
trend logs simplify system troubleshooting when
The auto-addressing feature eliminates the compared to a centralized system.
need to manually assign an address to each I/O
module therefore reducing installation and Email Notifications Service
configuration time.
Technicians & facility managers can receive
Digital Inputs Up to 120Hz automatic email notifications for system status
and alarms to ensure faster system servicing
The ECY-16DI module supports pulsed signals and response time. Email notification text can
up to 120Hz for equipment status monitoring be customized to provide pertinent information
and alarm point monitoring, commonly used in about the issue at hand.
energy metering applications.

Color-Coded, Rising Cage Terminals


Terminal blocks are uniquely identified and
color-coded for clarity and to prevent wiring
mistakes. The rising cage clamp terminal block
connectors offer a more robust and secure wire
connection, designed to withstand activity and
vibrations.

ECLYPSE™ Connected System Controller 5 / 20


Model Selection
The ECLYPSE Connected System Controller consists of a power supply, a control, automation and
connectivity server, I/O extension modules, and communication modules to create a controller
tailored to its application. The different models for each are shown in the tables below.

Power Supply
A power supply module must be added after each HD15 cable (see Accessories below).
ECY-PS24 24VAC/VDC power supply module for the ECLYPSE Connected System
Controller.
ECY-PS100-240 100 to 240VAC power supply module for the ECLYPSE Connected
System Controller.

Control, Automation and Connectivity Servers


Connected System Controller for medium/large sized AHU and plant applications and small building
server/controller applications.
Model With Application Maximum BACnet MS/TP Maximum
Embedded Number of to IP Routing Number of
ENVYSION Points Support – Modbus
Supported Maximum Devices (RTU
Number of or TCP)
BACnet MS/TP
Devices
ECY-S1000-28 Small size 28 No1 3
ECY-S1000E-28 equipment such as
a large rooftop unit
ECY-S1000-28-MS 28 Yes2 3
or a small AHU.
ECY-S1000E-28-MS
ECY-S1000-48 Medium size 48 No1 10
ECY-S1000E-48 equipment such as
an AHU or a small
ECY-S1000-48-MS 48 Yes2 10
size plant room
ECY-S1000E-48-MS
ECY-S1000 Large size 3204 Yes2 963
ECY-S1000E equipment such as
large plant rooms
and large data
centers.
1. Upgrade and enable the functionality of your ECLYPSE controller’s RS-485 ports with our capacity-based upgrade to ECYS1000-48MS.
2. Up to 50 BACnet MS/TP devices recommended on each RS-485 port.
3. Up to 32 Modbus RTU devices recommended on each RS-485 port.
4. The ECY-S1000 models support a maximum of 320 points OR up to a maximum of 20 IO modules.

6 / 20 ECLYPSE™ Connected System Controller


I/O Modules Selection

Basic Power Consumption2, W


Inputs Outputs

Digital Analog Digital Analog

120Hz Pulse Counting

18VDC Power Supply

0-277VAC / 0-30VDC

24VAC Triac, 0.5 A


Form-C, 10A

0 to 10VDC1
0 or 12VDC
0 to 10VDC

Resistance

0 to 20mA1
Thermistor
0 to 5VDC
0 to 20mA
Quantity

Quantity
Counter

Floating
Contact

PWM

HOA
ECY-8UI 8 0.94
ECY-16DI 16 0.94
ECY-6UO 6 UO1 0.94
UO2
UO3
ECY-6UO-HOA 6 UO1 0.94
UO2
UO3
ECY-8DOR 8 0.94
ECY-8DOR-HOA 8 0.94
ECY-4UI4UO 4 4 UO1 0.94
UO2
UO3
ECY-4UI4UO-HOA 4 4 UO1 0.94
UO2
UO3
ECY-8UI6UO 8 6 UO1 0.94
UO2
UO3
ECY-8UI6UO-HOA 8 6 UO1 0.94
UO2
UO3
ECY-8UI6DOT 8 6 0.94
ECY-8UI6DOT-HOA 8 6 0.94
1. 0 to 10VDC is available on UO1 to UO6. 0 to 20 mA is available on UO1, UO2, and UO3; this option is individually selected through an on-board DIP switch
setting.
2. External loads excluded. See the ECLYPSE Selection Tool to calculate the number of Input/Output Extension Modules that can operate with a power supply.

Communication Modules Selection


Communications Module Description
ECY-RS485 ECLYPSE Communication module with two RS-485 ports for Modbus
RTU or BACnet MS/TP.

Accessories
ECLYPSE HD15 Cable 6ft (1.8m) cable for Connected System Controller multiple-row panel
installations. An HD15 cable must always be followed by a power supply
module. For more information, refer to the Hardware Installation Guide.
ECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers.

ECLYPSE™ Connected System Controller 7 / 20


Product Specifications
Power Supply (ECY-PS24)
Power Supply Input
Voltage Range 24VAC/DC; ±15%; Class 2
Power Consumption 60VA
Frequency Range 50 to 60Hz
Overcurrent Protection Field replaceable fuse
Fuse Type 4A, fast-acting, 5 × 20mm (GMA-4A)

Power Supply Output


DC Voltage 18VDC regulated
Rated Current Range 0 to 1.6A
Rated Power 30W1
1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connected
loads, must be less than this value. A separate transformer rated at 60VA minimum and 100VA maximum must be used for each ECY-PS24 power supply for it to
operate at full capacity.

Hardware
Power Distribution Direction Powered modules are connected to the right
Backplane Bus Pass-through connection for data and control signals
Status Indicator Green LED: power status

Mechanical
Dimensions (H × W × D) 4.74 × 2.85 × 2.31" (120.31 × 72.38 × 58.56mm)
0.17" 4.24 2.85" 72.38
2.31" 58.56
Inter-Connection Gap: 0.01" 0.40

0.83 21.13

4.74" 120.31 3.18" 80.82


5.20" 132.00

0.72 18.39

Front Profile Back


0.06" 1.44 2.61" 66.19 Inches Millimeters

Shipping weight 0.75lbs (0.34kg)


Mounting DIN rail or screw mounting
Enclosure Material 1
FR/ABS
Enclosure Rating Plastic housing, UL94-V0 flammability rating
Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive

8 / 20 ECLYPSE™ Connected System Controller


Environmental
Operating Temperature 32 to 122°F (0 to 50°C)
Storage Temperature -22 to 158°F (-30 to 70°C)
Relative Humidity 0 to 90% non-condensing
Ingress Protection Rating IP20
Nema Rating 1

Standards and Regulations


CE:
£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,
commercial and light-industrial environments
£ Immunity EN61000-6-1: 2007; Generic standards for residential,
commercial and light-industrial environments
FCC This device complies with FCC rules part 15, subpart B, class B
UL Listed (CDN & US) UL916 Energy management equipment

         

Power Supply (ECY-PS100-240)


Power Supply Input
Voltage Range 100 to 240 VAC Universal; +10%/-15%
Input Current 400mA typical
Frequency Range 50 to 60Hz
Standby Power consumption <0.5W
Overcurrent Protection Field replaceable fuse
Fuse Type 2.5A, Fast-acting, high-breaking, 250VAC, 5 × 20mm (TF2.5AH250V, IEC60127-2)

Power Supply Output


DC Voltage 18VDC regulated
Rated Current Range 0 to 2A
Rated Power 40W1
1. The total power consumption of all modules connected to the right of this power supply, and up to the next connected power supply, including any connected
loads, must be less than this value.

Hardware
Power Distribution Direction Powered modules are connected to the right
Backplane Bus Pass-through connection for data and control signals
Status Indicator Green LED: power status

Mechanical
Dimensions (H × W × D) 4.74 × 4.08 × 2.31" (120.31 × 103.65 × 58.56mm)

ECLYPSE™ Connected System Controller 9 / 20


4.08" 103.65
0.44" 11.13
Inter-Connection Gap: 0.01" 0.40 2.31" 58.56

0.83 21.13

4.74" 120.31 3.18" 80.82


5.24 133.03

0.72 18.39

Front Profile Back


0.06" 1.44 3.83" 97.33 Inches Millimeters

Shipping weight 0.71lbs (0.32kg)


Mounting DIN rail or screw mounting
Refer to Hardware Installation Guide for more information
Enclosure Material1 FR/ABS
Enclosure Rating Plastic housing, UL94-5VB flammability rating
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive

Environmental
Operating Temperature 32 to 122°F (0 to 50°C)
Storage Temperature -22 to 158°F (-30 to 70°C)
Relative Humidity 0 to 90% non-condensing
Altitude <6562ft (2000m)
Pollution Degree 2
Ingress Protection Rating IP20
(must be mounted in a protective enclosure to conform with electrical installation standards)
Overvoltage Category II - 2.5 kV
Electrical Protection DC output is Separated Extra-Low Voltage (SELV);
SELV is implemented through reinforced insulation

10 / 20 ECLYPSE™ Connected System Controller


Standards and Regulations
CE:
£ Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household
and similar use - Part 1: General requirements
£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,
commercial and light-industrial environments
£ Immunity EN61000-6-1: 2007; Generic standards for residential,
commercial and light-industrial environments
UL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment
For Measurement, Control, And Laboratory Use - Part 1:
General Requirements - Edition 2 - Revision Date 2008/10/28
FCC This device complies with FCC rules part 15, subpart B, class B

         

Control, Automation and Connectivity Server (ECY-S1000)


Power Supply Input
Voltage 18VDC
Power Consumption 8.9W; external loads excluded

Communications
Ethernet Connection Speed 10/100 Mbps
£ Addressing IPv4 or Hostname
BACnet Profile BACnet Building Controller (B-BC)), AMEV AS-A and AS-B (pending)
BACnet Listing BTL, WSP B-BC
BACnet Interconnectivity BBMD forwarding capabilities
BACnet/IP to BACnet MS/TP routing
BACnet Transport Layer IP & MS/TP (optional)
Web Server Protocol HTML5
Web Server Application Interface REST API
Supported BACnet MS/TP and Modbus RTU and TCP Connectivity:
£ BACnet MS/TP or Modbus RTU 1 × RS-485 serial communications ports
Each RS-485 port supports one communication protocol at a time
£ RS-485 Wiring 1-pair + Common/shield
£ RS-485 EOL Resistor Built-in
£ RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps
£ RS-485 Addressing Controller’s Web Configuration Interface
£ Modbus TCP Devices must be on the same subnet
Supported Wireless Connectivity:
£ Wireless Adapter Optional, USB Port Connection
£ Wi-Fi Communication Protocol IEEE 802.11b/g/n and 802.11s
£ Wi-Fi Network Types Client, Access Point, Hotspot, Mesh
£ Wi-Fi Mesh Max. 30 devices on a single channel

ECLYPSE™ Connected System Controller 11 / 20


Supported Smart Room Control Components1:
Maximum number of supported devices per controller combined 12
£ Allure EC-Smart-Vue Series Up to 121
£ Allure EC-Smart-Comfort Series Up to 6
£ Allure EC-Smart-Air Series Up to 61
£ EC-Multi Sensor Up to 42
£ ECx-Light-4 / ECx-Light-4D / ECx-Light-DALI Up to 22
£ ECx-Blind-4 / ECx-Blind-4LV Up to 22
1. For more details about supported quantities, see the ECLYPSE Selection Tool.xlsm spreadsheet file available for download from SmartSource.
2. A controller can support a maximum of 2 Allure sensor models equipped with a CO2 sensor. Any remaining connected sensors must be without a CO2sensor.

Hardware
Processor Sitara ARM processor
CPU Speed 1GHz
Memory 4GB Non-volatile Flash (applications & storage)
512MB RAM
Real Time Clock (RTC) Real Time Clock with rechargeable battery
Supports SNTP network time synchronization
RTC Battery 20 hours charge time, 20 days discharge time
Up to 500 charge / discharge cycles
Cryptographic Module FIPS 140-2 Level 1 Compliant
Communications Ports:
£ Ethernet 2 switched RJ-45 Ethernet ports
Supported Protocols BACnet/IP, Modbus TCP, NTP, and REST
£ USB Connections 2 × USB 2.0 Ports
1 × Micro-USB 2.0 Ports
£ RS-485 Serial Communications Screw terminals
Supported Protocols BACnet MS/TP or Modbus RTU
£ Subnet RJ-45
Status Indicators Green LED: Power status, Subnet TX, RS-485 TX, and Ethernet Traffic
Orange LED: Controller status, Subnet RX, RS-485 RX, and Ethernet Speed

Mechanical
Dimensions (H × W × D) 4.74 × 3.57 × 2.31" (120.31 × 90.67 × 58.56mm)

12 / 20 ECLYPSE™ Connected System Controller


3.57" 90.67 2.31" 58.56 0.4" 1.09
Inter-Connection Gap: 0.01" 0.40

0.83 21.08

4.74" 120.31 3.18" 80.82

5.13" 130.29

0.73 18.54

0.39" 9.98 0.06" 1.44 Front Profile Back

3.33" 84.47 Inches Millimeters

Shipping weight 0.85lbs (0.39kg)


Mounting DIN rail or screw mounting
Enclosure Material FR/ABS
Enclosure Rating1 Plastic housing, UL94-V0 flammability rating
Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive

Environmental
Operating Temperature 32 to 122°F (0 to 50°C)
Storage Temperature -22 to 158°F (-30 to 70°C)
Relative Humidity 0 to 90% non-condensing
Ingress Protection Rating IP20
Nema Rating 1

Standards and Regulations


CE:
£ Emission EN61000-6-3: 2007+A1:2011; Generic standards for residential,
commercial and light-industrial environments
£ Immunity EN61000-6-1: 2007; Generic standards for residential,
commercial and light-industrial environments
FCC This device complies with FCC rules part 15, subpart B, class B
UL Listed (CDN & US) UL916 Energy management equipment

           

ECLYPSE™ Connected System Controller 13 / 20


I/O Modules
Power Supply Input
Voltage 18VDC
Power Consumption Calculate power supply requirements with the ECLYPSE Selection Tool

Hardware
Status Indicator Green LEDs: inputs and outputs

For ECY-8UI, ECY-16DI, ECY-6UO, ECY-6UO-HOA, ECY-4UI4UO, ECY-4UI4UO-


HOA, ECY-8UI6UO, ECY-8UI6UO-HOA, ECY-8UI6DOT, & ECY-8UI6DOT-HOA
Models:
Mechanical
Dimensions (H × W × D) 4.74 × 3.20 × 2.31" (120.31 × 81.17 × 58.56mm)
3.20" 81.17 2.31" 58.56

Inter-Connection Gap: 0.01" 0.40

0.83 21.08

4.74" 120.31 3.18" 80.82

4.80" 121.75

0.73 18.54

Front Profile Back


0.06" 1.44 2.95" 74.99 Inches Millimeters

Shipping weight 0.85lbs (0.39kg)


Mounting DIN rail or screw mounting
Hot-swappable Yes
Enclosure Material FR/ABS
Enclosure Rating 1
Plastic housing, UL94-V0 flammability rating; Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive

Environmental
Operating Temperature 32 to 122°F (0 to 50°C)
Storage Temperature -22 to 158°F (-30 to 70°C)
Relative Humidity 0 to 90% non-condensing
Ingress Protection Rating IP20
Nema Rating 1

14 / 20 ECLYPSE™ Connected System Controller


Standards and Regulations
CE:
£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,
commercial and light-industrial environments
£ Immunity EN61000-6-1: 2007; Generic standards for residential,
commercial and light-industrial environments
FCC This device complies with FCC rules part 15, subpart B, class B
UL Listed (CDN & US) UL916 Energy management equipment

         

I/O Modules - Universal Inputs (UI)


General
Input Type Universal; software configurable
Current Input Option Selection DIP switch
Input Resolution 16-bit analog to digital converter
Power Supply Output 18VDC; 20mA maximum per 0 to 20 mA input

Contact
Type Dry contact

Counter
Type Dry contact
Maximum Frequency 1Hz maximum,
Minimum Duty Cycle 500milliseconds On / 500milliseconds Off

0 to 10VDC
Range 0 to 10VDC (40kΩ input impedance)

0 to 5VDC
Range 0 to 5VDC (high input impedance)

0 to 20mA
Range 0 to 20mA
249Ω DIP-switch configurable internal resistor

Resistance/Thermistor
Range 0 to 350 KΩ
Supported Thermistor Types Any that operate in this range
Pre-configured Temperature Sensor Types:
£ Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF; 25ºC)
£ Platinum Pt1000 (1KΩ @ 32ºF; 0ºC)
£ Nickel RTD Ni1000 (1KΩ @ 32ºF; 0ºC)
RTD Ni1000 (1KΩ @ 69.8ºF; 21ºC)

ECLYPSE™ Connected System Controller 15 / 20


I/O Modules - Digital Inputs (DI)
General
Input Type Dry contact or Open-Collector
Low Threshold < 2.5V
High Threshold > 3.0V

Pulse/Counter
Pulse Input S0 output compatible
Maximum Frequency 120Hz
Minimum Duty Cycle 4.167milliseconds On / 4.167milliseconds Off

I/O Modules - Universal Outputs (UO)


General
Output Type Universal; software configurable
Output Resolution 10-bit digital to analog Converter
Output Protection Built-in snubbing diode to protect against back-EMF,
for example when used with a 12VDC relay
Load Resistance Minimum 200Ω for 0 to 10VDC and 0 to 12VDC outputs
Maximum 500Ω for 0 to 20mA output
Auto-reset Fuse 60mA @ 140ºF; 60ºC

0 or 12VDC (On/Off)
Range 0 or 12VDC

PWM
Range Adjustable period from 2 to 65seconds

Floating
Minimum Pulse On/Off Time 500milliseconds
Drive Time Period Adjustable

0 to 10VDC
Range 0 to 10VDC linear

0 to 20mA
Range 0 to 20mA
Current Source 20mA maximum per 0 to 20 mA output
Ports UO1, UO2, and UO3 only DIP switch

HOA
Hand-Off-Auto switch When equipped
Supervision allows control logic to read the current
HOA switch and potentiometer settings
Threshold Configurable
Potentiometer Voltage Range 0 to 12VDC

16 / 20 ECLYPSE™ Connected System Controller


I/O Modules - Digital Output (DOT)
General
Output Type 24VAC Triac; software configurable
Maximum Current 0.5A continuous
1A @ 15% duty cycle for a 10 minute period
Power Source External power supply

0 or 24VAC (On/Off)
Range 0 or 24VAC

PWM
Range Adjustable period from 2 to 65seconds

Floating
Minimum Pulse On/Off Time 500milliseconds
Drive Time Period Adjustable

HOA
Hand-Off-Auto switch When equipped
Supervision allows control logic to read the current HOA switch setting

I/O Modules - Digital Output (DOR)


For ECY-8DOR & ECY-8DOR-HOA Models:
General
Output Type Relay contact
Relay Type Form C
Power Source Dry contact (external power supply)
Operating Voltage 0 to 277VAC or 0-30VDC ±10%, see HIG for mounting specifications
Maximum Current
£ Resistive Load 10A
£ Inductive Load 6A
£ Motor Load 3A
Protection Outputs must be protected with max 10 A external circuit breaker

Digital
Range On/Off

HOA
Hand-Off-Auto switch When equipped
Supervision allows control logic to read the current HOA switch setting

ECLYPSE™ Connected System Controller 17 / 20


Mechanical
Dimensions (H × W × D) 4.74 × 5.15 × 2.31" (120.31 × 130.07 × 58.56mm)
5.15" 130.07 2.31" 58.56

Inter-Connection Gap: 0.01" 0.40

0.83 21.08

O1 O2 O3 O4 O5 O6 O7 O8

MAN

AUTO

4.74" 120.31 OFF


3.18" 80.82

4.8" 121.75

0.73 18.54

Front Profile Back


0.06" 1.44 4.94" 125.32 Inches Millimeters

Shipping weight 0.75lbs (0.34kg)


Mounting DIN rail or screw mounting
Hot-swappable Yes (once high voltages have been removed)
Enclosure Material FR/ABS
Enclosure Rating1 Plastic housing, UL94-5VB flammability rating
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive

Environmental
Operating Temperature 32 to 122°F (0 to 50°C)
Storage Temperature -22 to 158°F (-30 to 70°C)
Relative Humidity 0 to 90% non-condensing
Altitude <6562ft (2000m)
Pollution Degree 2
Ingress Protection Rating IP20
(must be mounted in a protective enclosure to conform with electrical installation standards)
Overvoltage Category II - 2.5 kV

Standards and Regulations


CE:
£ Electrical Safety EN 60730-1 : 2011 - Automatic electrical controls for household
and similar use - Part 1: General requirements
£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,
commercial and light-industrial environments
£ Immunity EN61000-6-1: 2007; Generic standards for residential,
commercial and light-industrial environments
UL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment
For Measurement, Control, And Laboratory Use - Part 1:
General Requirements - Edition 2 - Revision Date 2008/10/28
FCC This device complies with FCC rules part 15, subpart B, class B

         

18 / 20 ECLYPSE™ Connected System Controller


Communications Module
ECY-RS485 Communications Module
Supported Quantity 1 × ECY-RS485 per ECY-S1000

Power Supply Input


Voltage 18VDC
Power Consumption 1.25 W

Communications
Supported BACnet MS/TP or Modbus RTU Connectivity:
£ BACnet MS/TP or Modbus RTU 2 × RS-485 serial communications ports
Each RS-485 port supports one communication protocol at a time
£ RS-485 Wiring 1-pair + Common/shield
£ Connection Type Screw terminals
£ RS-485 EOL Resistor Built-in
£ RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 bps
£ RS-485 Addressing Controller’s Web Configuration Interface
Status Indicators Green LED: TX
Orange LED: RX

Mechanical
Dimensions (H × W × D) 4.74 × 3.16 × 2.31" (120.31 × 80.19 × 58.56mm)
3.20 [81.17] 2.31 [58.56]

Inter-Connection Gap: 0.01 [0.40]

0.51 [12.90]

0.83 [21.08]

RX1 TX1 RX2 TX2

4.74 [120.31] 3.18 [80.82]

5.30 [134.65]

0.73 [18.54]

Front Profile Back


0.06 [1.44] 2.95 [74.99] Inches [Millimeters]

Shipping weight 0.55lbs (0.25 kg)


Mounting DIN rail or screw mounting
Enclosure Material FR/ABS
Enclosure Rating 1
Plastic housing, UL94-V0 flammability rating
Plenum rating per UL1995
1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)
directive

ECLYPSE™ Connected System Controller 19 / 20


Environmental
Operating Temperature 32 to 122°F (0 to 50°C)
Storage Temperature -22 to 158°F (-30 to 70°C)
Relative Humidity 0 to 90% non-condensing
Ingress Protection Rating IP20
Nema Rating 1

Standards and Regulations


CE:
£ Emission EN61000-6-3: 2007; A1:2011; Generic standards for residential,
commercial and light-industrial environments
£ Immunity EN61000-6-1: 2007; Generic standards for residential,
commercial and light-industrial environments
FCC This device complies with FCC rules part 15, subpart B, class B
UL Listed (CDN & US) UL916 Energy management equipment

         

Specifications subject to change without notice.


ECLYPSE, Distech Controls, the Distech Controls logo, EC-Net, and Allure are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE; BTL
is a registered trademark of the BACnet Manufacturers Association. All other trademarks are property of their respective owner.
©, Distech Controls Inc., 2015 - 2016. All rights reserved.

20 / 20 ECY-CSC_DS_19_EN

You might also like