Specifications
ECY-600 Series
TM
ECLYPSE Connected Overview
Controllers with 30 points
The ECY-600 Series controllers are designed to designed to control
various building automation applications such as air handling units,
chillers, boilers, pumps, cooling towers, and central plant applications.
They support BACnet/IP communications and are listed BACnet
Building Controllers (B-BC). This series supports the use of the ECY-
COM modules as well at two additional ECY-IOM extension modules.
These programmable controllers come with an embedded web server
that enables web-based application configuration and a visualization
interface. They also feature embedded scheduling, alarming, and log-
ging. Control logic and graphic user interface can be customized as
required for the application.
Features & Benefits
= ECLYPSE Series input/output and communication modules are
supported, providing competitive I/O combinations, and support-
ing up to 62 I/O points (up to 1 communication module and 2 I/O
modules).
= More compact architecture and flexible installation. Can be
mounted vertically or horizontally; perfect for panel retrofits or ap-
plications when limited horizontal space is available
= An optional full-color backlit display with jog dial provides direct
access to a wide range of controller functions
= Flexible networking using options for isolated applications and
fail-safe daisy-chaining applications. Two Ethernet ports and an
AUX port can be configured to create separate networks.
= Software-configurable IOs reduce controller manipulation.
= Different communication protocols such as BACnet MS/TP, BAC-
net/SC, BACnet/IP, MQTT, Modbus RTU, Modbus TCP, and M-
Bus are supported to ensure ease of communication, authentica-
tion, and error detection.
= Connectivity packs enable remote devices to be added to a con-
nector in ECLYPSE Building Intelligence. The connectivity packs
along with optional I/O and expansion modules provide ultimate
flexibility and expandability to customize your project needs.
Model and Connectivity Selection
Model Selection
Example: ECY-650
Series Model
600: 30-Points, 24VAC/DC Power Supply, 16 UI, 14 UO
ECY-
650: 30-Points, 24VAC/DC Power Supply, 16 UI, 14 UO, Color display
Connectivity Packs
Connectivity packs enable remote devices to be added to a connector in ECLYPSE Building Intelligence. A single pack adds x
connections and x * 100 points of connectivity.
BACnet Network Values in EC-gfxProgram are available without connectivity packs.
Connectivity Device ratios
1:1 2:1 8:1 100:1
Connections BACnet devices Modbus devices
Connectivity pack M-Bus devices Global point count
(device load) (IP or MS/TP) (TCP/IP or RTU)
C1* 1 1 2 8 100
C3 3 3 6 24 300
C5 5 5 10 40 500
C10 10 10 20 60 1000
C25 25 25 50 60 2500
C50 50 50 100** 60 5000
C100 100 100 200** 60 10000
*Minimum Connectivity Pack required to enable BACnet routing, MS/TP “Client”, integration, use of RS485 port
**Modbus RTU limited to 32 devices/RS-485 port, 96 devices total
Depending on the connector, a device can consume a whole connection or a fraction of a connection. The device ratios are the
following using a C5 connectivity pack (refer to table above):
= BACnet (1:1) = 5 BACnet with C5
= Modbus (2:1) = 10 Modbus with C5
= M-Bus (8:1) = 40 M-Bus with C5
Connectivity packs are cumulative but only one pack can be ordered with a controller. More packs can be added afterwards in the field.
The following shows how to calculate the connectivity needed:
To assist in calculating the required connectivity, contact your RSM for more details or refer to the price list if available.
Accessories
ECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers.
6ft (1.8m) cable for multiple-row panel installations. An HD15 cable must always be
ECLYPSE HD15 Cable followed by a power supply module. For more information, refer to the Hardware
Installation Guide.
Required for daisy-chaining the ECx-Display or the EC-Multi-Sensor with other subnet
ECx-Subnet-Adapter
devices
RTC Battery Adapter Adapter to add a size CR2032 coin cell battery (not included)
Recommended Applications
Model ECY-600 / 650
Air Handling Unit
Multi-Zone Application
Chiller
Boiler
Cooling Tower
2/6 ECY-600 Series
Model ECY-600 / 650
Central Plant
Product Specifications
Power Supply Input (24VAC) Subnetwork
Input Voltage Range 24VAC; ±15%; Class 2 Communication RS-485
Power Consumption 100VA maximum; internal and Cable Type Cat 5e, 8 conductor twisted pair
external loads included Connector RJ-45
12VA typical, no load
Connection Topology Daisy-chain
Recommended Transformer 100VA
Size Maximum number of standard 12
room devices supported per
Frequency Range 50 to 60Hz controller combined1
Power Supply Input (24VDC) Allure EC-Smart-Vue Series2 12
Input Voltage Range 24VDC; ±15%; Class 2 1. For more details about supported quantities, see the Product Selection Tool
available in Builder: https://builder.distech-controls.com.
Power Consumption 60W maximum; internal and 2. A controller can support a maximum of 2 Allure sensor models equipped with a
1
external loads included CO2 sensor. Any remaining connected sensors must be without a CO2 sensor.
5W typical, no load
Subnet-IP
Recommended Power Supply 60W Subnet-IP Connection Speed 10/100 Mbps
Size
Cable Type Cat 5e, 8 conductor twisted pair
1. Powering external devices through the Subnet-IP does not work if input supply is in
1
VDC. Subnet-IP Voltage 55VDC
1. Powering external devices through the Subnet-IP does not work if input supply is in
Current Limits VDC.
Power Supply Input 4A (internal fuse)
18V 240mA Hardware
Processor Sitara ARM processor
Subnet-IP 180mA (10W)
CPU Speed 1GHz
Subnet 450mA (6.75W)
Memory 4GB Non-volatile Flash
USB 2.0 500mA per port (applications & storage)
Communications 512MB RAM
Ethernet Connection Speed 10/100 Mbps Co-processor1 STM32 (ARM Cortex M0+)
MCU 32-bit
Cable Type Cat 5e, 8 conductor twisted pair
(unshielded) MCU Speed 64 MHz
Addressing IPv6, IPv4, or Hostname MCU Memory 512KB Non-volatile Flash
(system)
BACnet Profile BACnet Building Controller (B-
144KB RAM
BC))
Real Time Clock (RTC) Real Time Clock with
BACnet Listing BTL, WSP B-BC
rechargeable battery
BACnet Interconnectivity BBMD forwarding capabilities Supports SNTP network time
BACnet MS/TP to BACnet/IP synchronization
and BACnet/SC routing
RTC Battery 20 hours charge time, 20 days
BACnet Transport Layer IP, BACnet/SC (Node) & MS/TP discharge time
(optional) Up to 500 charge / discharge
Web Server Protocol HTML5 cycles
Web Server Application REST API MS621T coin cell battery; an
Interface adapter is available to add a
size CR2032 coin cell battery
BACnet MS/TP or Modbus 1 × RS-485 serial with the external connector
RTU communications ports
Ethernet 3 switched RJ-45 Ethernet ports
RS-485 Wiring 1-pair + Common/shield (Supported Protocols: BACnet/
RS-485 EOL Resistor Built-in IP, Modbus TCP, NTP, and
RS-485 Baud Rates 9600, 19 200, 38 400, or 76 800 REST)
Primary and secondary
bps
Ethernet ports with integrated
RS-485 Addressing Controller’s Web Configuration fail-safe for daisy-chain
Interface operation
Modbus TCP Devices must be on the same USB Connections 2 × USB 2.0 Ports
subnet
RS-485 Serial Communications Screw terminals (Supported
Wireless Adapter Optional, USB Port Connection Protocols: BACnet MS/TP or
Wi-Fi Communication Protocol IEEE 802.11g/n Modbus RTU)
Wi-Fi Network Types Client, Access Point, Hotspot 1. Dedicated for IO control and MSTP
ECY-600 Series 3/6
Subnet RJ-45 ECY-650 Display
Green LED Power status, I/O, Ethernet Display Type Backlit-color LCD
Traffic, Subnet-IP AUX, and Display Resolution 400 W x 240 H pixels (WQVGA)
RS-485 TX
Effective Viewing Area (W × H) 2.26 × 1.36” (57.3 × 34.54mm)
Orange LED Controller status, Subnet-IP diagonal: 2.63” (66.9mm)
PWR, RS-485 RX
Menu Navigation Jog dial turn, select navigation
1. Dedicated for IO control and MSTP
with Exit button
Environmental
Operating Temperature 1 ECY-600: -40 to 158°F (-40 to
70°C)
2 Universal Inputs (UI)
ECY-650: -4 to 122°F (-20 to
50°C)
3 General
Input Type Universal; software configurable
Storage Temperature ECY-600: -40 to 185°F (-40 to
85°C) Input Resolution 16-Bit analog / digital converter
ECY-650: -22 to 176°F (-30 to Power Supply Output 18VDC; maximum 240mA
80°C) Auto-reset fuse Provides 24VAC over voltage
Relative Humidity 0 to 90% non-condensing protection
Ingress Protection Rating IP20
Contact
Nema Rating 1 Type Dry contact
1. Some applications may be limited at high operating temperatures.
2. For controllers not equipped with an operator interface, the internal temperature Pulse/Counter
must not exceed 185°F (85°C).
3. For controllers equipped with an operator interface, the internal temperature must
not exceed 158°F (70°C). UI1 to UI4:
Pulse Input SO output compatible
Open-to-Wireless Adapter (Pending) Maximum Frequency 100Hz maximum
1
Communication Protocol EnOcean wireless standard
Minimum Duty Cycle 5ms On / 5ms Off
Connector Type USB
Number of Wireless Inputs Unlimited
2 UI5 to UI16:
Type Dry contact
Maximum Frequency 1Hz maximum
Minimum Duty Cycle 500ms On / 500ms Off
1. Available when an optional external ECLYPSE Open-to-Wireless Adapter is 0 to 10VDC
connected to the controller. Refer to the Open-to-Wireless Application Guide for a Range 0 to 10VDC
list of supported EnOcean wireless modules. (40kΩ input impedance)
2. Wireless inputs will only be limited by physical distance between the EnOcean
devices and the ECLYPSE Open-to-Wireless Adapter.
0 to 5VDC
Mechanical Range 0 to 5VDC
Dimensions (H × W × D) ECY-600: 4.79 ×7.36 × 2.46" (high input impedance)
(121.60 × 187.00 × 62.58 mm)
ECY-650: 4.79 ×7.36 × 2.91"
0 to 20mA
(121.60 × 187.00 × 73.86 mm) Internal Resistor 249 ohm
Shipping Weight 1.45lbs (0.66kg) External Resistor 249 ohm
Mounting DIN rail or screw mounting Resistance/Thermistor
Enclosure Material Flame retardant/Polycarbonate Range 0 to 350 KΩ
(FR/PC) Supported Thermistor Types Any that operate in this range
Enclosure Rating1 Plastic housing, UL94-5VB Pre-configured Temperature Sensor Types:
flammability rating Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF;
1. All materials and manufacturing processes comply with the RoHS directive and are
marked according to the Waste Electrical and Electronic Equipment (WEEE)
25ºC)
directive Platinum Pt1000 (1KΩ @ 32ºF; 0ºC)
Standards and Regulations Nickel RTD Ni1000 (1KΩ @ 32ºF; 0ºC)
CE Emission EN61000-6-3 (2007) A1 RTD Ni1000 (1KΩ @ 69.8ºF;
(2001) AC (2012) 21ºC)
CE Immunity EN61000-6-1 (2007)
IEC IEC 63044-5-1 (2019) Universal Outputs (UO)
IEC 63044-5-2 (2019)
FCC Compliance with FCC rules General
part 15, subpart B, class B Output Type Universal; software configurable
ICES Compliance ICES-003 Output Resolution 10-bit digital to analog converter
UL Listed (CDN & US) UL916 Energy Output Protection Built-in snubbing diode to
management equipment protect against back-EMF, for
example when used with a
12VDC relay
Output is internally protected
against short circuits
Load Resistance Minimum 200 Ω for 0-10VDC
and 0-12VDC outputs
4/6 ECY-600 Series
Maximum 500 Ω for 0-20mA Floating
output Minimum Pulse On/Off Time 500 milliseconds
Auto-reset fuse Provides 24VAC over voltage Drive Time Period Adjustable
protection
0 to 10VDC
0 or 12VDC (On/Off) Range 0 to 10VDC
Range 0 or 12VDC
Source Current Maximum 60 mA at 12VDC 0 to 20mA
(minimum load resistance Range 0 to 20mA
200Ω) Type Current source
PWM
Range Adjustable period from 2 to 65
seconds
Thermal Actuator Management Adjustable warm up and cool
down time
Dimensions
Figure 1: Controllers not equipped with an operator interface
ECY-600 Series 5/6
Figure 2: Controllers equipped with an operator interface
Specifications subject to change without notice.
ECLYPSE, Distech Controls, the Distech Controls logo, EC-Net, Allure, and Allure UNITOUCH are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE;
®
BTL is a registered trademark of the BACnet Manufacturers Association. The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of
such marks is under license. All other trademarks are property of their respective owners.
©, Distech Controls Inc., 2015 - 2024 All rights reserved.
Global Head Office - 4205 place de Java, Brossard, QC, Canada, J4Y 0C4 - EU Head Office - ZAC de Sacuny, 558 avenue Marcel Mérieux, 69530 Brignais, France
6/6 ECY-600 Series_SP_10_EN