Master-Controller RCO 700D-M/W: Data Sheet

The document describes a building management system master controller that can be used for automatic control, monitoring and optimization of building automation. It has various communication interfaces that allow it to integrate with other systems and connect to a network of other master controllers. Programming is done through engineering software to control functions like HVAC, alarms, data logging, and more.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
130 views4 pages

Master-Controller RCO 700D-M/W: Data Sheet

The document describes a building management system master controller that can be used for automatic control, monitoring and optimization of building automation. It has various communication interfaces that allow it to integrate with other systems and connect to a network of other master controllers. Programming is done through engineering software to control functions like HVAC, alarms, data logging, and more.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Building Management System

Master-Controller RCO 700D-M/W

Data sheet RCO 700D-M RCO 700D-W

Application

Controlesta RCO 700D-.. are free programmable Master Controllers. The devices are suitable for the operation within a network. The Master Controllers Controlesta RCO 700D-.. can be used for the automatic control, monitoring and optimisation within the building automation. The Master Controllers can be connected together via Ethernet to a Multi-Master-Network (peer-to-peer Communication). The implemented interfaces and protocols offer a variety of communication and integration abilities. As a native BACnet Controller the Master Controller supports on demand the BACnet protocol according to the ANSI/ASHRAE Standard 135-2004 (ISO16484-5). Options for the Data Link Layer of the BACnet Building Controller (B-BC): BACnet/Ethernet, BACnet/IP, BACnet/MSTP und BACnet/PTP. Router functionality according to Clause 6. BBMD (BACnet/IP Broadcast Management Device) function can be activated if required. The controller RCO 700D-W includes additionally an integrated Web server for the visualization and operation of plant data and alarms via Intranet or Internet with a standard web browser. The HTML pages are designed comfortably and efficiently with the RCO-tool. 32 Bit-Micro processor with real time operation system 8 MB SD-RAM 4 MB Flash Memory 1 slot for SD-Memory Card as internal and external data and program memory. 2 x RS232 Interface: Used for the connection to bms, pc, analogue/gms-messenger, modem and printer as well as for the connection of the already implemented protocols. 2 x RS485 Interface: For the connection of the already implemented protocols as well as for the communication to the Controlesta RCO C Master network. 2 x Ethernet Interfaces (In/Out with integrated Hub-Functionality) for the peer-to-peer communication based on Ethernet for the connection of Master Controller within the MultiMaster-Network and the connection to the BMS-Software. 1 x L-Bus 1-connection with selectable speed (default: 100 Kbps) for the connection of up to 32 Slave-Modules RCO C 1 x L-Bus 2-connection with selectable speed (default: 100 Kbps) for the connection of up to 32 I/O-Modules RCO D The already implemented protocols like ASCII, Modbus RTU Master/Slave, M-Bus, Wilo, Grundfos, RCO C, Energesta REN and BACnet can be combined with the integrated Interfaces (Ethernet, RS232, RS485). The operator panel RCO 640D-S can be connected via the L-Bus Standardised algorithms for PID regulation Integrated alarm and modem handling The free programming of all functions of the plant software is done by the engeneering software Controlesta RCO-tool Battery back up for the real time clock Approved to European EMC standards CENELEC EN 50 082-1 and EN 55 011 CE-Approval 0 ... 50 C -20 ... 60 C 0 ... 90 % rh., non condensing III

Features

Environmental Conditions

Ambient temperature Storage temperature Ambient humidity Protection Class

160242/4.10 Data are subject to change without notice

Building Management System


Master-Controller RCO 700D-M/W

Execution

Housing Production Dimensions Weight Power supply Output voltage Power consumption Wire capacity Main tightening torque Protection acc. to EN60529

plastic, for DIN-rail mounting According to ROHS w x h x d, 160 x 136 x 35 mm 270 g 24 VAC/DC +/- 10 %, Class II 8 modules can be supplied over T-BusConnectors with 24 VDC via LBus 2. If more than 8 modules are connected to the bus, a power module has to be used. 5 W without Slaves (max. 8 modules can be supplied) 14 ... 24 AWG (0,25 ... 2,5 mm2) 4 In-lb (0,45 Nm) IP 20

Electrical Data

Communication Interfaces

Interface
Com 1 (RS232) Com 2 (RS232)

Protocols / Functions
ASCII Protokoll Modbus RTU Master/Slave M-Bus Wilo Grundfos Energesta REN RCO-net BACnet Point to Point, EIA232 BACnet Point to Point, Modem Connection to - BMS (operation, visualisation) - PC (programming), - Modem (analogue, gsm) - Printer - Messenger (SMS to mobil provider, Fax, e-Mail) Modbus RTU Master/Slave Wilo Grundfos RCO C Energesta REN BACnet/MSTP Master BACnet/MSTP Slave L-Bus-protocol for the field bus communication with up to 32 RCO C slave-modules. Operator panels RCO 640D-S can be connected

Connection
RJ45 Length: 15m

Technical details
Transmision speed: 57.600 bps (default) adjustable up to 115.200 bps

BACnet: 9.600 / 57.600 / 115.200 bps

RS485_1 RS485_2

Two wire connection (Twisted Pair, shielded) up to max. 1200 m

Transmision speed: Up to 57.600 bps. Device address adjustable via DIP-switches BACnet: 9.600 / 19.200 / 38.400 / 76.800 bps

L-Bus 1

Four wire bus (Twisted Pair, shielded) incl. Power supply, lenght 40 600 m, dependend of cable type and speed of the bus, can be extended by use of a Power Bridge Module RCO 302D-P Four wire bus (Twisted Pair, shielded) incl. Power supply, lenght 40 600 m, dependend of cable type and speed of the bus, can be extended by use of a Power Bridge Module RCO 302D-P RJ45

Transmision speed: Standard: 100 Kbps adjustable to 20 Kbps Device address adjustable via DIP-switches

L-Bus 2

L-Bus-protocol for the field bus communication with up to 32 RCO D I/O-modules. Operator panels RCO 640D-S can be connected

Transmision speed: Standard: 100 Kbps adjustable to 20 / 100 / 500 / 1000 Kbps Device address adjustable via DIP-switches

Ethernet In/out

Ethernet protocol for the crosslinking of Master Controllers - BACnet/IP - BACnet/IP, Foreign Device - BACnet/Ethernet, ISO 8802-3

10/100 Base-T

Functional data

Memory

8 MB SD-RAM 4 MB Flash memory for the operating system 1 slot for SD-Memory Card as data and program memory Data and programs are secured on the SD-Memory Card In case of a power cut battery backup is provided Batterie: CR2032, 210mAh 2

Power failure safety Real time clock

Building Management System


Master-Controller RCO 700D-M/W

Programming

Each Controller RCO 700D-M or RCO 700D-W has to be programmed individually. The free programmability of all functions is done with the Engineering Software RCO-tool. The tool supports text programming as well as graphical programming. The RCO 700D-M or RCO 700D-W firmware provides a variety of helpful HVAC functions (PIDloop, Enthalpy) mathematical and logical operations. Time schedules, Alarms or Data logs can be set up easily. The RCO 700D-M or RCO 700D-W can be accessed by PC, laptop or the operator panel (L-Bus). If a modem is connected, remote access or alarm monitoring by PC is possible. Local or remote access can be password protected.

Software

Operation

Point schematic

6 2 3 9 10 11

A1 B1 G1A2 B2 G2

A3 B3 P3 G3

A4 B4 P4 G4 PE N L

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. DIP-switch settings

DIP-Switch for the addessing of the RCO-bus ID RS485_1 RS485_2 Ethernet Ethernet DIP-switch for the termination resistor L-Bus1 (T) COM1 (RS232) COM2 (RS232) L-Bus 1 L-Bus 2 Power

1 2 3 4 5 6 Address 0 1 2 3 4 5 6 Address 3 1 2 3 4 5 6 Address 6

ON OFF

1 2 3 4 5 6 Address 1 1 2 3 4 5 6 Address 4 1 2 3 4 5 6 Address 7

ON OFF

1 2 3 4 5 6 Address 2 1 2 3 4 5 6 Address 5 1 2 3 4 5 6 Address 63

ON OFF

ON OFF

ON OFF

ON OF

ON OFF

ON OFF

ON OFF

DIP-switch 1-6: Address 0-63 adjustable

The termination resistor for L-Bus 1 must be activated for the first and the last device (ON)

1 2

ON OFF

1 2

ON OFF

1 2

ON OFF

1 2

ON OFF

L-Bus 1 not active

L-Bus 1 active

L-Bus 1 active

L-Bus 1 active

The terminator resistor for the L-Bus 2 is allready activated internally

Building Management System


Master-Controller RCO 700D-M/W

Dimension drawing

30,00 25,00

160,00 156,00

Cutout dimension: 156 x 92 mm

88,30

Delivery

RCO 700D-M RCO 700D-W

136,00