ACS800 COPYING PARAMETERS
USING DRIVEWINDOW,
DRIVEWINDOW LIGHT AND KEYPAD
Description:
This will provide tips and tricks when copying parameters from the drive with DriveWindow
software, DriveWindow Light or the Drive Keypad.
Answer:
All parameter download will not program parameter 99.02 “APPLICATION MACRO”. This
parameter will need to be programmed before downloading saved DriveWindow parameters.
Open the DriveWindow saved parameter file. Next note the setting of parameter 99.02
“APPLICATION MACRO”. Then connect to the drive and program 99.02 “APPLICATION
MACRO” to the noted value before downloading the saved parameters.
DriveWindow:
Motor ID Run Results: DriveWindow software will ask you if you would like to download the
Motor ID run results.
AP Program: DriveWindow will copy all parameters including the AP program into the new
drive. DriveWindow will then automatically put the AP program into run mode.
Fieldbus Adapter: DriveWindow will copy all Fieldbus adapter setting from the drive. If the
drive has a Fieldbus Adapter on the drive the DriveWindow parameter file will need to be
downloaded twice. The 1st download will enable the Fieldbus adapter but will not provide any
parameter setting for the Fieldbus adapter. The 2nd download will provide the Fieldbus adapter
parameter settings.
Author: Jeff Fell – Application Eng.                         Date: 03, 2012
External                       Industry – Industrial, HVAC   Document #: LVD-EOTN30U-EN
http://www.abb.us/drives. or PLC                             Revision: A
Product Categories: ACS800
DriveWindow Light:
Motor ID Run Results: DriveWindow Light software parameter save will save AP Program and
Fieldbus Adapter parameter settings but no Motor ID Run Results parameter data. A
DriveWindow Light “Backup” will save the Motor ID run results and a “Restore” will download
Motor ID run results and program parameter 99.02 “APPLICATION MACRO”.
AP Program: DriveWindow Light will copy everything but the AP Text parameters 85.11 - 85.15
“STRING 1-5”, therefore, all parameters except parameters 85.11 – 85.15 will be downloaded to
the new drive. DriveWindow Light will then automatically put the AP program into run mode.
Fieldbus Adapter: DriveWindow will copy all Fieldbus adapter setting from the drive. If the
drive has a Fieldbus Adapter on the drive the DriveWindow parameter file will need to be
downloaded twice. The 1st download will enable the Fieldbus adapter but will not provide any
parameter setting for the Fieldbus adapter. The 2nd download will provide the Fieldbus adapter
parameter settings.
Keypad:
Motor ID Run Results: See ABB Knowledgebase “ACS800-HOW TO UPLOAD AND
DOWNLOAD MOTOR ID RUN RESULTS WITH THE DRIVE PANEL “.
AP Program: The Keypad will copy everything but the AP Text parameters 85.11 - 85.15
“STRING 1-5”, therefore, all parameters except parameters 85.11 – 85.15 will be downloaded to
the new drive. The Keypad will then automatically put the AP program into run mode.
Fieldbus Adapter: The Keypad will copy all Fieldbus adapter setting from the drive. If the drive
has a Fieldbus Adapter on the drive the Keypad will need to be downloaded twice. The 1st
download will enable the Fieldbus adapter but will not provide any parameter setting for the
Fieldbus adapter. The 2nd download will provide the Fieldbus adapter parameter settings.
Author: Jeff Fell – Application Eng.                         Date: 03, 2012
External                       Industry – Industrial, HVAC   Document #: LVD-EOTN30U-EN
http://www.abb.us/drives. or PLC                             Revision: A
Product Categories: ACS800
Documents or other reference material:
None
Corrective Actions:
None
Author: Jeff Fell – Application Eng.                         Date: 03, 2012
External                       Industry – Industrial, HVAC   Document #: LVD-EOTN30U-EN
http://www.abb.us/drives. or PLC                             Revision: A
Product Categories: ACS800