0% found this document useful (0 votes)
217 views4 pages

EJB UL Enclosures: Certificate NEMA Type 4X

The document provides specifications for EJB UL Enclosures for use in hazardous areas. It lists the enclosures' classifications for hazardous locations in Europe and North America, environmental ratings of NEMA Type 4X and IP66, an operating temperature range of -25°C to +60°C, and applicable certification standards including UL, CSA, and ATEX. Technical details are provided for enclosure body dimensions and materials.

Uploaded by

shahbaz Ahmad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
217 views4 pages

EJB UL Enclosures: Certificate NEMA Type 4X

The document provides specifications for EJB UL Enclosures for use in hazardous areas. It lists the enclosures' classifications for hazardous locations in Europe and North America, environmental ratings of NEMA Type 4X and IP66, an operating temperature range of -25°C to +60°C, and applicable certification standards including UL, CSA, and ATEX. Technical details are provided for enclosure body dimensions and materials.

Uploaded by

shahbaz Ahmad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

EJB UL Enclosures Ex Enclosures

Installation: hazardous areas (EU) - hazardous locations (US-CNC)


Classification: Group II (EU) - Groups B, C, D, E, F, G (US - CNC)

Certificate
NEMA Type 4X

REFERENCE STANDARDS REFERENCE STANDARDS


TERMINAL BOARD / POWER UNITS CONTROL TERMINAL BOARD / POWER UNITS CONTROL
AND SIGNALLING UNITS AND SIGNALLING UNITS
ENCLOSURE FOR USE IN HAZARDOUS LOCATIONS (FTRV) ENCLOSURE FOR USE IN ZONE CLASSIFIED HAZARDOUS LOCATIONS
Class I - Groups B, C, e D (FTQH, FTQH7)
INSTALLATION Class II - Groups E, F, e G USC:
Class III Class I - Zone 1 - AEx d IIB + H2 Gb
ENVIRONMENTAL RATINGS Type 1, 4 and 4X Zone 21 - AEx tb IIIC Db IP66
INSTALLATION CNC:
AMBIENT TEMPERATURE -25°C ÷ +60°C
Class I - Zone 1- AEx d IIB+H2 Gb
UL 1203 - 4° Ed. (15 Sett. 2006) Class II - Division 1 - Groups E, F, e G
UL 50 - 12° Ed. (27 April 2012) Class III - Division 1
CERTIFICATION AND UL 50E - 1° Ed. (27 April 2012)
ENVIRONMENTAL RATINGS IP66, Type 1, 4 and 4X
COMPLIANCES Explosion-Proof / Dust-Ignition-Proof
Electrical Equipment for Use in AMBIENT TEMPERATURE -55°C ÷ +60°C
Hazardous (Classified) Locations USC:
CERTIFICATE OF COMPLIANCE NEC 500: UL 20120510-E302348 UL 60079-0 - 6° Ed. - Part 0
UL 60079-1 - 6° Ed. - Part 1
ANSI/ISA 60079-31:2013 - Part 31
REFERENCE STANDARDS CERTIFICATION AND UL 50 - 12° Ed. (27 April 2012)
TERMINAL BOARD / POWER UNITS CONTROL COMPLIANCES UL 50E - 1° Ed. (27 April 2012)
AND SIGNALLING UNITS CNC:
CAN/CSA-C22.1 60079-0:2011 Part 0
Directive 2014/34/EU CAN/CSA-C22.1 60079-1:2011 Part 1
( II 2 G) Ex db IIA or IIB or IIB+H2 T6…T3 CAN/CSA-C22.1 60079-31:2011Part 31
( II 2 G) Ex db [ia/ib IIA or IIB or IIC Ga] CERTIFICATE OF COMPLIANCE NEC 505: UL 20141204-E302348
EXECUTION IIA or IIB or IIB+H2 T6
( II 2 D) Ex tb IIIC T85°C…T200°C
( II 2 D) Ex tb [ia Da/ib] IIIC T85°C
Mechanical characteristics
EN/IEC 60079-0; EN/IEC 60079-1;
RULES OF COMPLIANCE Body and cover marine grade copper free aluminium light alloy
EN/IEC 60079-11; EN/IEC 60079-31
EC Type-Examination Certificate INERIS 13 ATEX 0022X Screws stainless steel - internal / external
PROTECTION DEGREE IP66 Internal plate hot dip galvanized steel / aluminium
AMBIENT TEMPERATURE -60°C ÷ +80°C Fixing galvanized steel stirrups th.10mm
OTHER AVAILABLE CERTIFICATES IECEx: IECEx INE 13_0070X Gaskets O-RING silicon rubber on cover

On Request Accessories:
• External epoxy painting (any colours)
• Internal anticondensate painting orange RAL-2004
• O-Ring gaskets on cover
• Drain and breather valves
• Stainless steel AISI-316L hinges

128 BARTEC FEAM - Catalogue 2020


EJB UL Enclosures Ex Enclosures

Technical Features
A B C D E F G H I L INT. PLATE WEIGHT
CODE DETAIL
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] X-Y [mm] [Kg]

EJB21-UL 320 280 177 189 180 233 121 214 174 13 180 - 140 13,50 A

EJB31-UL 450 350 248 260 294 287 191 341 241 13 325 - 225 27,00 A

EJB51-UL 600 400 266 278 360 333 195 481 281 13 460 - 260 52,50 A

EJB61-UL 710 500 389 397 500 460 277 566 356 12 560 - 360 114,00 A

EJB63-UL 710 500 259 267 500 460 147 571 362 12 560 - 360 92,00 A

A B C D E F G H I L INT. PLATE LIBRE


CODE DETAIL
[Inch] [Inch] [Inch] [Inch] [Inch] [Inch] [Inch] [Inch] [Inch] [Inch] X-Y [Inch] [Lbs]

EJB21-UL 12,60 11,10 7,00 7,50 7,10 9,20 4,80 8,50 6,90 0,60 7.10 - 5.60 31,00 A

EJB31-UL 17,80 13,80 9,80 10,30 11,60 11,30 7,60 13,50 9,50 0,60 12.80 - 8.90 62,00 A

EJB51-UL 23,70 15,80 10,50 11,00 14,20 13,20 7,70 19,00 11,10 0,60 18.20 - 10.30 121,00 A

EJB UL
EJB61-UL 28,00 19,70 15,40 15,70 19,70 18,20 11,00 22,30 14,10 0,50 22.10 - 14.20 262,00 A

EJB63-UL 28,00 19,70 10,20 10,60 19,70 18,20 5,80 22,50 14,30 0,50 22.10 - 14.20 212,00 A

Reference details
2
A
D

C B F

L
G
E
A
HxI

Body enclosures drilling layout


AREA FOR ENTRY INSTALLATION (LONG WALL SIDES) AREA FOR ENTRY INSTALLATION (SHORT WALL SIDES)
ENCLOSURE
CODE A B A B C D C D
[mm] [mm] [inch.] [inch.] [mm] [mm] [inch.] [inch.]

EJB21-UL 190 80 7,50 3,20 150 80 6,00 3,20

EJB31-UL 320 140 12,60 5,60 230 140 9,10 5,60

EJB51-UL 450 120 17,80 4,80 250 120 9,90 4,80

EJB61-UL 550 260 21,70 10,30 350 260 13,80 10,30

EJB63-UL 550 150 21,70 6,00 350 150 13,80 6,00

Catalogue 2020 - BARTEC FEAM 129


EJB UL Enclosures Ex Enclosures

Body enclosures minimum distance between wall entries


MINIMUM DISTANCE BETWEEN WALL ENTRIES (CENTER TO CENTER)
1st ROW [mm] - 2nd ROW [inch.]

4” 139
- - - - - - - -
- (5.47)
3” 115 126
- - - - - - -
M90 (4.53) (4.96)

2 1/2” 101 108 120


- - - - - -
M75 (3.98) (4.25) (4.72)
2” 88 94 102 112
- - - - -
M63 (3.46) (3.70) (4.02) (4.41)
1 1/2” 75 82 88 95 106
- - - -
M50 (2.95) (3.23) (3.46) (3.74) (4.17)
1 1/4” 67 70 77 84 91 103
- - -
M40 (2.64) (2.76) (3.03) (3.31) (3.58) (4.06)

1” 58 63 66 73 80 86 99
- -
M32 (2.28) (2.48) (2.60) (2.87) (3.15) (3.39) (3.90)

3/4” 52 55 59 63 69 79 83 95
-
M25 (2.05) (2.17) (2.32) (2.48) (2.72) (2.99) (3.27) (3.74)

1/2” 46 49 52 57 60 67 73 80 93
M20 (1.81) (1.93) (2.05) (2.24) (2.36) (2.64) (2.87) (3.15) (3.66)
NPT 1/2” 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 4”
Metric M20 M25 M32 M40 M50 M63 M75 M90 -

Reference details
WALL DRILLING AREA
A C
D
B

Cover enclosures drilling layout

MINUMUM DISTANCE COVER DRILLING AREA


AREA FOR OPERATORS
BETWEEN OPENINGS F
ENCLOSURE INSTALLATION ENCLOSURE COVER
(CENTER TO CENTER)
CODE
E F E F
[mm] [inch.]
[mm] [mm] [inch.] [inch.]

EJB21-UL 200 150 7,90 6,00 50 2,00

EJB31-UL 300 200 11,90 7,90 50 2,00


E

EJB51-UL 460 260 18,20 10,30 50 2,00

EJB61-UL 570 370 22,50 14,60 50 2,00

EJB63-UL 570 370 22,50 14,60 50 2,00

130 BARTEC FEAM - Catalogue 2020


EJB UL Enclosures Ex Enclosures

Indicative quantity of terminals and relevant section

SEZ. 2,5 SEZ. 6,0 SEZ. 10,0 SEZ. 16,0 SEZ. 35,0 SEZ. 50,0 SEZ. 70,0 SEZ. 240,0 INT. PLATE X - Y
CODE
[sq/mm] [sq/mm] [sq/mm] [sq/mm] [sq/mm] [sq/mm] [sq/mm] [sq/mm] [mm] [inch.]

EJB21-UL 30 x 1 20 x 1 14 x 1 12 x 1 8x1 6x1 2x1 1x1 180 -140 7.10 - 5.60

EJB31-UL 52 x 2 32 x 2 24 x 2 20 x 2 14 x 2 12 x 1 8x1 4x1 325 -225 12.80 - 8.90

EJB51-UL 80 x 2 46 x 2 36 x 2 30 x 2 22 x 2 18 x 2 16 x 1 6x1 460 -260 18.20 - 10.30

EJB61-UL 92 x 3 58 x 3 46 x 3 38 x 3 28 x 3 26 x 2 22 x 2 12 x 1 560 -350 22.10 - 14.20

EJB63-UL 92 x 3 58 x 3 46 x 3 38 x 3 28 x 3 26 x 2 22 x 2 12 x 1 560 -350 22.10 - 14.20

Additional Technical features for NEC 500 only

PRODUCT COVERED
Explosion-proof enclosures for use in Hazardous Locations, Class I, Groups B, C, and D; Class II, Groups E, F, and G; Class III.
These enclosures are Classified as to explosion and fire hazards only in according to Standard UL1203 4° ed.
The explosion-proof enclosures are suitable for Class I, Group B Hazardous Locations only when provided with from M20 to M90, 1/2 in. to 3 in., supply connection openings. If
other supply connection openings are provided, then the enclosures are suitable for Class I, Groups C & D Hazardous Locations only.
The 1/2 in. NPSM operator openings are only suitable for enclosures marked for Class I, Groups B, C & D Hazardous Locations
The enclosures covered by this Certification may have electrical components installed inside. The installation of electrical components shall not reduce the mechanical integrity of
the enclosures.

EJB UL
The enclosures may or may not be provided with hinges for service of the enclosures only.

PROTECTION AGAINST CORROSION


All ferrous-metal other than stainless steel shall be protected against corrosion, except at joint surfaces and conduit threads There shall be no materials
applied to joint surfaces.

GROUNDING 2
Internal Ground Screw – Hexagon head screw M6 x 10 with a stainless steel flat and lock washer provided on the base of the enclosure body.
External Ground – Terminal colored green, marked with the letter or word “G”, “GROUND”, or marked with a grounding symbol.

SUPPLY CONNECTIONS
NPT and Metric Supply Connections - The side walls of the enclosure are provided with conduit openings or none may be supplied, in which case field drilling and tapping
instructions are provided with each enclosure. The entry is drilled and tapped completely through the enclosure wall, and the inside edge is smoothed and well-rounded such that
the conductor insulation will not be damaged when installed. All unused openings are closed with plated steel, plated cast iron or aluminum close-up plugs which are threaded to
match the opening. Closer-up Plugs have to be Listed for the same Class, Group and Division as marked on Enclosure nameplate.

OPERATOR OPENINGS
The cover of the enclosure may be provided with operator openings in the cover only and located only as given in drilling and tapping instructions provided with each Classified enclosure. All unused
openings are closed with plated steel, plated cast iron or aluminum close-up plugs which are threaded to match the opening. Closer-up Plugs have to be Listed for the same Class, Group and Division
as marked on Enclosure nameplate.

REMARK:
Due to the development of the national and international specifications and of the technology, the above technical characteristics showed on this bulletin can be considered as binding on our confirmation only.
Catalogue 2020 - BARTEC FEAM 131

You might also like