Rittal / 17.11.
2010 1
Ri4Power
General
What is Ri4Power ?
• Modular enclosure system with
compartments
• For Motor Control Centers (MCC)
and Power Control Centers (PCC)
• Type-tested to IEC 60439-1&2 and
IEC 61439 1&2 (Latest)
• Busbar systems
RiLine60 up to 1600A
Maxi-PLS up to 4000A
Flat-PLS up to 5500A
3/4 pole + PE/PEN
• Static installation technology
Ri4Power
General
Why a Form separated system ?
• To separate function units from
each other
• To make maintenance much
more easier
• To make working at a life
system more safe
• To avoid damages which can
be affected from a failure in
other compartments
• To reduce the risk of failures
Ri4Power
General
Ri4Power
General
Ri4Power areas of application
Modular system for low-voltage switchgear to 5500 A
Industries:
• Process Industries (steel, cement,
paper, chemicals, water, and waste
water treatment)
• Industry (mechanical engineering
and automotive) Airport, Ri4Power power distribution for the control tower
• Energy generation (wind, solar,
biomass, and small power plants)
• Infrastructure (buildings, data
centres, stadiums and airports)
Ri4Power – ISV
Introduction
RITTAL Distribution enclosures ISV
Wall mounted Free standing Free standing
to 630A to 1600A
Ri4Power – Form 1-4
Modular
Form 1 Form 2-4
Ri4Power
Modular
Form 1 Positions of the busbars
Form 2-4
Design of the connections sets
Fixed positions Variable positions
predefined Connection set
variants configurator
Design of the connection
accessories
(U-contact maker, baying
connector etc.)
Ri4Power – Form 1
Modular
Variants of sections
Modular and flexible
Circuit breaker Coupling section Modular Cable chamber Switch-disconnector-
section outgoing section fuse section
SASIL / SlimLine
Ri4Power – Form 2-4
Modular
Variants of sections
Modular and flexible
Switch-disconnector-
Circuit breaker Coupling section Modular Cable chamber fuse section
section outgoing section SASIL / SlimLine
Enclosures and components
enclosures inner separation + busbar components
outher cladding
TS enclosures Roof plates Front trimm panels
• Width: 300 / 400 / 600 / 800mm • IP2X / IP43 / IP55 • IP2X / IP43 / IP54
• Height:1800 / 2000 / 2200mm • For cable entry plates
• Depth: 400/600 / 800mm
Partial doors
• Width: 400 / 600 / 800mm
• Height:150 .... 2000mm
• New hinge and cross members
Side panels
IP2X / IP43 / IP55
Mounting brackets
Functional space Support frame For functional space divider
side panel modules • for DIN rail-mounted devices • for depth 400 / 600 / 800mm
• Height: 100/ 150/ 200/ 600mm• 1 to 4 rows for 24/36 units
• for depth: 400 / 600 / 800mm
• With knockouts for incoming
and outgoing power cables.
Functional space divider
Partial mounting plates • width: 400/ 600 / 800mm
• with and without duct • 3 depths + RiLine60 cutout
• attachment at the side
panel modules
System attachment Mini-TS profile
for main busbar • for assembly of the side panel Adaptor pieces
• for witdh: 300/ 400/ 600/ 800mm modules and cover plates for Mini-TS profile
• prepared for RiLine60 (3 + 4-pole) • for individual use with TS8 pitch • Assembly of
with 50mm pitch on 3 sides Mini-TS profile
• Connection 2 Mini-TS
profiles at an angle of
90°
Compact infeed system
• 3- or 4-pole Cover plate
• with Maxi-PLS busbar • Metalic cover
for main busbar
Busbar systems
To 1600 A RiLine60 (3/4-pole)
- Flatbar
- PLS800
- PLS1600
To 4000 A Maxi-PLS (3/4-pole)
(3200 A) - Maxi-PLS 1600
- Maxi-PLS 2000
- Maxi-PLS 3200
To 5500 A FlatPLS (3/4-polig)
(4000 A)- max. 4x 60x 10mm
- max. 4x 100x 10mm
The solution in detail:
Top,
Positions of the busbar system Front Rear in the roof section
N L1 L2 L3
N
L1
• Maxi PLS 1600 / 2000 / 3200 Top,
L2
Flat PLS60 / Flat PLS100 in the rear section
L3
• Flexible arrangement of busbars
L1
• Optimised position of busbars Centre position with
Position of the busbars is identical in
L2 185mm centre distance
600mm and 800mm deep enclosures NH on-load islolator
L3
Less copper required
Reduced forces in case L1 Bottom,
of a short circuit L2
in the rear section
L3
N N
L1 L2 L3 Bottom,
in the base section
Positions of the busbars:
So far New
• Busbars centred • Busbar rearwards
Variants of sections
Modular and flexible
Circuit breaker Coupling section Modular Cable chamber NH fused isolator
section outgoing section section SASIL / SlimLine
Variants of sections
Circuit breaker section
• For assembly of air circuit breaker
(ACB)
• For system infeed or powerful outlets
• Inner separation up to Form 4b
• Special side-wall modules for
attachment of the cable
connection system
Variants of sections
Coupling section
• Same enclosure like for circuit
breaker section No additional
enclosure type is needed
• Circuit breaker section
+ 200mm wide busbar riser
• Space saving arrangement
of the busbar riser on the
left and right possible
Variants of sections
Modular outgoing section
• Form separated compartments
from 150mm in the height
• Optional use of the vertical distribution
busbar system
– Behind the partial mounting plate
– Inside of the function room
– On the side as busbar dropper
Variants of sections
Cable chamber section
• Lateral routing of the incoming
wires to the respective compartment
• Cable entry optionally
top or bottom
• Comprehensive variants of cable
entry glands
• Additional metallic hazard protection
cover for the main busbar system
Variants of sections
NH fused isolator section
• For NH fused isolators
(SASIL) Jean Müller or SlimLine (ABB)
• Modular concept:
– Enclosure + attchement set + divider panel
• New distribution busbar system for flatbars
50 – 100x10mm up to 100 kA
Variable combination of field types
Circuit coupling Modular Distribution Cable Empty Busbar NH fused corner Switch dis- empty customized
breaker section outgoing busbar chamber section riser isolator section connector fuse section section
section section section section with busbar section section section
Ri4Power
Engineering guidelines
System Overview
(Type) testing acc. to IEC 60439-1 and IEC 61439 part 1 and 2
Applicable with devices of
Rittal PU Foam Gasketing
Neoprene
/ Rubber Rittal PU Foam
Gasket Gasket
IP Rating Temporar
y Permanent
Upto 70 Deg C
Temperature Less Continuous
Will get
Temp Cycles hard Will remain soft
required
Maintenance often No maintenance
Life Less More
Rittal Painting Technology
7 / 9 Tank
traditional
Process Rittal Process
7 Tank / 9 State of the art
Pretreatment Tank Process
De-Greasing Acid Based Alkali Based
Nano Ceramic
Phosphating FE / Zn Coating
Primer Coat Non existant EC Dip Coat
Pressurised
Process Dip Tank Conveyor
Rittal Painting Technology
Powder Coating - TYPES
Property Polyester Hybrid (Default) Epoxy
Adhesion Excellent Excellent Excellent
Flexibility Very Good Very Good Excellent - Very
Good
Hardness HB – 2H HB – 3H HB – 5H
Impact Resistance Good Very Good Excellent – Very
Good
Heat Resistance Poor Good Very Good
Chemical Good Very Good Excellent
Resistance
Corrosion Very Good Very Good Excellent
Resistance
Weatherability Excellent Fair – Poor Poor
Rittal Painting Technology
Set-up of standard surface finish of a
Rittal enclosure
EC dip-coat primer
(RAL 7035)
Thickness approx. 20 µm
RAL 7035 textured
powder coating
EC dip-coat primer offers
Thickness
increased corrosion protection ...
approx. 90 µm
Sheet steel
Low Voltage switchgear and controlgear assembly
with inner separation up to form 4
Form of inner separations (IEC 60 439-1):
busbar
• Form 1
function unit
without inside separation
terminal area
• Form 2a + 2b
separation between busbars and function units a b
• Form 3a + 3b
Simular to Form 2, additional divider between all
function units among themselves and function a b
units and terminal area
• Form 4a + 4b
Simular to Form 3, complete separation of busbars a b
and terminal area
Rittal Power Engineering
Project: e.g.
Panel builder new airport
Rittal: Components (Rittal-customer)
Manufacturer of Consultat
Switchgear
Offer
$
Tested safety
Type-tested to IEC 60 439-1
Max. admissible temperature
Dielectric strength
Short-circuit resistance
Effectiveness of the PE conductor
Creepage distances and clearances
IP protection category
Tested under arcing conditions to IEC 61 641
ASTA-approved