Texcan - Teck Catalogue
Texcan - Teck Catalogue
CATALOGUE
Wire & Cable Specialists
Our Commitment specialized technical assistance and superior
sales service to meet our customers’ needs.
Our commitment to our customers is simple -
We constantly strive to bring value to our
we deliver even when others can’t.
customers. We provide:
As one of Canada’s largest wire, cable and data
• An extensive range of stock wire products
communication distributors for over 40 years,
• Computerized order processing
Texcan supplies solutions for automotive, power
• Regionalized bar coded warehousing
distribution, control, industrial automation,
• Competitive pricing
commercial, residential, premise wiring and
• Inventory tracking technology
networking applications. Our commitment to
• JIT inventory
superior customer service is the number one
reason customers keep coming back.
Our parent company, Sonepar, is a major Strategic Partnerships
global electrical distributor, with divisions in 44
Texcan has worked hard to develop
countries, 5 continents, over 46,000 associates
partnerships with customers and vendors and
and 2,800 branches.
continues to be committed to developing such
strategic alliances. These partnerships provide
Texcan with a successful
Dedicated to Our and proven record with some of the
Customers largest customers in the pulp and paper,
mining, petrochemical, transportation, and
Texcan understands that business is done communication industries.
between people. We consider a job finished
when the customer is completely satisfied. This Thanks to our relationships with key vendors
approach highlights our commitment to quality such as: Prysmian Group, Southwire, Belden,
and our high level of customer service. This Nexans, Northern Cables, Deca Cables, Marmon
winning combination focuses on a personalized Electrical, CMP, and PTI Cables Inc., Texcan is
approach to our customers. able to offer its customers a diverse selection
of quality products. We are confident we can
continue to be your successful partner now and
in the future.
Product Expertise and
Specialized Services
Texcan has five stocking locations in Western
Over 40 Years
Canada. With over 200 employees, Texcan is able
to provide product application expertise, of Service
CÂBLES
CABLESINC.
Table of Contents
Page No.
Teck Cable 4
Standard Design Features 5
Armoured Control 600V 6
Teck Multiconductor 600V - 14 AWG 7
- 12 AWG 8
- 10 AWG 9
Teck Composite 600V - 14 AWG 10
- 12 AWG 10
Teck 1C 1000V 11
Teck 2C 1000V 12
Teck 3C 1000V 13
Teck 4C 1000V 14
Teck Unshielded - 1C 5kV 15
- 3C 5kV 16
Teck Shielded - 1C 100% 5kV 17
- 3C 100% 5kV 18
- 1C 133% 5KV (aka 100% 8kV) 19
- 3C 133% 5KV (aka 100% 8kV) 20
- 3C 133% 8kV 21
- 1C 133% 15kV 22
- 3C 133% 15kV 23
- 1C 133% 25kV 24
- 3C 133% 25kV 25
- 1C 133% 28kV 26
- 3C 133% 28kV 27
- 1C 100% 35kV 28
- 3C 100% 35kV 29
Teck Connectors 30-31
Technical Information - Metric Conversions 32
- Installation Data 33
To Place an Order - For many of the products in the catalogue, you will find everything that you need to place
an order. Should you need any assistance or require special orders, please contact your sales representative. A
complete list of our sales offices can be found on the back cover of this catalogue.
Introduction
Teck cable, a flexible armoured cable originally
designed for use in Canadian mines, has become
a key component for the distribution of electricity
through a broad range of industrial, commercial
and manufacturing facilities.
Applications Specifications
Teck cable is used extensively by the pulp and paper, • CSA FT1 & FT4
chemical, mining, petrochemical and manufacturing • CSA C22.2 No. 131 for Teck cables rated up to and including 5kV
industries in a broad range of applications, especially • CSA C68.10 for shielded Teck cables rated 5kV and above
where cable may be subjected to mechanical damage (C68.10 pending)
and corrosive chemicals. Commercial applications for • CSA C22.2 No. 0.3 Clause 4.11.4 FT4 flame test
Teck cable include apartment buildings and commercial •C SA C22.2 No. 174 for use in the following hazardous locations (HL):
complexes. Teck cable is also an economical alternative as - Class 1 Group A, B, C, D. Division 1 & 2
the need for conduits or ducts and pull boxes is eliminated. - Class II Group E, F, G. Division 1 & 2
- Class III
Teck cable is approved for use; in wet and dry locations,
• ICEA S-66-524 / NEMA WC7 for Teck cables rated above 5kV
indoor and outdoor, in exposed and concealed wiring,
• IEEE 383 &1202 (70,000 BTU/hr) flame test
in ventilated, non-ventilated and ladder type cable
• ICEA T-29-520 (210,000 BTU/hr) Vertical Cable Tray Flame Test
trays, for direct earth burial and for service entrance
• ICEA T-30-520 (70,000 BTU/hr) Vertical Cable Tray Flame Test
installations, above and below ground. It is ‘HL’ rated for
*Refer to CE Code for details
use in all hazardous locations when used with optional
‘HL’ approved connectors.
CAUTION NOTICE
In case of fire, well maintained early warning smoke detectors will give an alarm long before non-metallic coverings become combustible.
However, the Electrical and Electronic Manufacturers Association of Canada has suggested that all purchasers of PVC insulated / jacketed
products be advised of the following:
• Non-metallic coverings of electrical cables can burn and may transmit fire when ignited.
• Burning non-metallic coverings may emit acid gases which are toxic and may generate dense smoke.
• Emission of acid gases may corrode metal in the vicinity e.g. sensitive instruments and reinforcing rods in cement.
The installer and/or user assumes all liability for the consequences of the installation and/or use of any of the products in violation of any
applicable law, regulation, or code.
Conductors – Class B compact or compressed concentric OUTER JACKET INNER JACKET INSULATION
stranded soft drawn bare copper per ASTM, conforming to CSA C68.3.
TAPE FILLERS BOND
CONDUCTOR
Conductor Shielding – A thermoset semi-conducting
shield is extruded over the conductor on all cables rated over 1kV.
Minimum thickness in accordance with CSA C68.3, Table 2.
FILLERS
TAPE CONDUCTOR
ARMOUR INSULATION
SPECIFIC ATIONS CONSTRUC TION
• CSA FT4 Conductor: Bare copper Class B compressed stranded
• CSA C22.2 No. 239 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
• CSA C22.2 No. 174 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
• CSA C22.2 No. 38 Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
*Refer to CE Code for details Armour: Aluminum Interlocked Armour (AIA)
Outer Jacket: Low-temperature and moisture resistant Polyvinyl Chloride (PVC), blue
Options: Galvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
16 AWG
Approximate Net Weight
AWG Size
Diameter (Over) w/ Armour
No. of
Part Number
Conductors
Outer Jacket
Cond. Bond Wire Inner Jacket (in.) Armour (in.) LB/MFT KG/KM
(in.)
Note: A
ll dimensions are nominal and are subject to normal manufacturing * See pages 30 & 31 for corresponding connector.
tolerance. Specifications are subject to change without prior notice.
TAPE CONDUCTOR
ARMOUR INSULATION
SPECIFIC ATIONS CONSTRUC TION
• CSA FT1 & FT4 Conductor: Bare copper Class B compressed stranded
• CSA C22.2 No. 131 & 174 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
6 0 0 V M ULTI
CON T R OL
• IEEE 383 & 1202 (70,000 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
BTU/hr) Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
*Refer to CE Code for details
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
14 AWG
Approximate Copper Net Weight
AWG Size
Insulation Diameter (Over) Content w/ Armour
Part No. of
Thickness
Number Conductors
(in.) Insul. Inner Jacket Armour Outer LB/ KG/ LB/ KG/
Cond. Bond Wire
(in.) (in.) (in.) Jacket (in.) MFT KM MFT KM
Note: A
ll dimensions are nominal and are subject to normal manufacturing * See pages 30 & 31 for corresponding connector.
tolerance. Specifications are subject to change without prior notice.
TAPE CONDUCTOR
ARMOUR INSULATION
SPECIFIC ATIONS CONSTRUC TION
• CSA FT1 & FT4 Conductor: Bare copper Class B compressed stranded
• CSA C22.2 No. 131 & 174 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
6 0 0 V M ULTI
CON T R OL
• IEEE 383 & 1202 (70,000 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
BTU/hr) Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
*Refer to CE Code for details
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
12 AWG
Approximate Copper Net Weight
AWG Size
Insulation Diameter (Over) Content w/ Armour
Part No. of
Thickness
Number Conductors
(in.) Insul. Inner Jacket Armour Outer LB/ KG/ LB/ KG/
Cond. Bond Wire
(in.) (in.) (in.) Jacket (in.) MFT KM MFT KM
Note: A
ll dimensions are nominal and are subject to normal manufacturing * See pages 30 & 31 for corresponding connector.
tolerance. Specifications are subject to change without prior notice.
TAPE CONDUCTOR
ARMOUR INSULATION
SPECIFIC ATIONS CONSTRUC TION
• CSA FT1 & FT4 Conductor: Bare copper Class B compressed stranded
• CSA C22.2 No. 131 & 174 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
6 0 0 V M ULTI
CON T R OL
• IEEE 383 & 1202 (70,000 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
BTU/hr) Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
*Refer to CE Code for details
Options: Galvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
10 AWG
Approximate Copper Net Weight
AWG Size
Insulation Diameter (Over) Content w/ Armour
Part No. of
Thickness
Number Conductors
(in.) Insul. Inner Jacket Armour Outer LB/ KG/ LB/ KG/
Cond. Bond Wire
(in.) (in.) (in.) Jacket (in.) MFT KM MFT KM
Note: A
ll dimensions are nominal and are subject to normal manufacturing * See pages 30 & 31 for corresponding connector.
tolerance. Specifications are subject to change without prior notice.
• CSA FT1 & FT4 Conductor: Bare copper Class B compressed stranded
• CSA C22.2 No. 131 & 174 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
• IEEE 383 & 1202 (70,000 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
BTU/hr) Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
*Refer to CE Code for details
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
14 AWG
6 0 0 V CO M PO S I T E
CON TR OL
12 AWG
Approximate Net Weight
AWG Size Copper Content
Insulation Diameter (Over) w/ Armour
Part
Thickness
Number
(in.) Inner LB/ KG/ LB/ KG/
Armour (in.) Outer Jacket
Control Power Bond Wire Jacket (in.) (in.) MFT KM MFT KM
Note: A
ll dimensions are nominal and are subject to normal manufacturing * See pages 30 & 31 for corresponding connector.
tolerance. Specifications are subject to change without prior notice.
HL Options: Other coloured outer jacket and constructions available upon request
05018-13-010 4 6 0.060 0.350 0.490 0.730 0.810 211 314 410 610
05018-17-010 3 6 0.060 0.380 0.520 0.760 0.840 244 363 450 680
05018-21-010 2 6 0.060 0.420 0.560 0.780 0.870 286 426 510 760
05018-25-010 1 4 0.080 0.490 0.660 0.880 0.960 390 581 680 1010
05019-01-010 1/0 4 0.080 0.530 0.690 0.910 1.000 458 682 760 1130
05019-05-010 2/0 4 0.080 0.580 0.710 0.950 1.040 544 810 860 1280
CON TR O L
05019-09-010 3/0 3 0.080 0.630 0.810 1.030 1.120 685 1020 1080 1610
1KV T E C K
05019-13-010 4/0 3 0.080 0.690 0.860 1.080 1.170 820 1220 1270 1890
05020-01-010 250 2 0.090 0.750 0.990 1.210 1.290 980 1459 1490 2210
05020-05-010 300 2 0.090 0.770 1.040 1.280 1.370 1112 1655 1920 2857
05020-09-010 350 1 0.090 0.815 1.120 1.360 1.445 1340 1994 1910 1910
05020-13-010 400 1 0.090 0.850 1.155 1.395 1.480 1499 2231 2088 3107
05020-21-010 500 1/0 0.090 0.925 1.200 1.475 1.560 1841 2604 2510 3740
05020-25-010 600 1/0 0.090 1.005 1.305 1.545 1.655 2173 3234 2877 4281
05020-41-010 750 2/0 0.090 1.160 1.370 1.590 1.690 2570 3825 3510 5230
05021-01-010 1000 2/0 0.090 1.310 1.590 1.810 1.900 3340 4970 4430 6590
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
TAPE CONDUCTOR
ARMOUR
SPECIFIC ATIONS CONSTRUC TION INSULATION
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
• IEEE 383 & 1202 (70,000 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
BTU/hr) Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
*Refer to CE Code for details
Options: Galvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
05018-14-010 4 8 0.060 0.350 0.850 1.070 1.160 312 464 744 1107
1KV T E C K
05018-18-010 3 6 0.060 0.380 0.930 1.150 1.230 415 618 905 1347
05018-22-010 2 6 0.060 0.420 0.980 1.200 1.280 502 747 1030 1533
05018-26-010 1 6 0.080 0.490 1.120 1.340 1.420 612 911 1235 1838
05019-02-010 1/0 6 0.080 0.530 1.230 1.450 1.530 740 1101 1425 2120
05019-06-010 2/0 6 0.080 0.580 1.280 1.500 1.580 922 1372 1660 2470
05019-10-010 3/0 4 0.080 0.630 1.370 1.590 1.690 1190 1771 1995 2969
05019-14-010 4/0 4 0.080 0.690 1.480 1.700 1.790 1466 2182 2350 3497
05020-02-010 250 4 0.090 0.750 1.620 1.840 1.930 1709 2543 2779 4135
05020-06-010 300 4 0.090 0.760 1.765 2.005 2.115 2018 3003 3341 4972
05020-10-010 350 3 0.090 0.860 1.870 2.090 2.180 2373 3561 3650 5431
05020-14-010 400 3 0.090 0.850 1.945 2.185 2.295 2687 3999 4147 6171
05020-22-010 500 3 0.090 0.990 2.110 2.330 2.450 3316 4935 4895 7284
05020-42-010 750 1 0.090 1.160 2.450 2.670 2.790 4941 7353 6872 10226
05020-46-010 1000 1 0.090 1.310 2.760 2.980 3.100 6562 9766 8993 13382
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
ARMOUR INSULATION
SPECIFIC ATIONS CONSTRUC TION
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
• IEEE 383 & 1202 (70,000 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
BTU/hr) Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
*Refer to CE Code for details
Options: Galvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
CON TR O L
05018-15-010 4 8 0.060 0.350 0.910 1.160 1.250 447 665 970 1444
1KV T E C K
05018-19-010 3 6 0.060 0.380 0.970 1.220 1.300 582 866 1136 1691
05018-23-010 2 6 0.060 0.420 1.020 1.280 1.370 710 1056 1311 1951
05018-27-010 1 6 0.080 0.490 1.210 1.440 1.540 866 1288 1593 2371
05019-03-010 1/0 6 0.080 0.530 1.290 1.560 1.680 1069 1590 1906 2837
05019-07-010 2/0 6 0.080 0.580 1.380 1.650 1.770 1327 1974 2225 3311
05019-11-010 3/0 4 0.080 0.630 1.490 1.750 1.870 1670 2485 2666 3967
05019-15-010 4/0 4 0.080 0.690 1.600 1.860 1.980 2109 3138 3207 4772
05020-03-010 250 4 0.090 0.750 1.800 2.050 2.170 2470 3675 3800 5655
05020-07-010 300 4 0.090 0.760 1.885 2.125 2.235 2961 4406 4460 6637
05020-11-010 350 3 0.090 0.860 2.010 2.260 2.400 3437 5114 4979 7409
05020-15-010 400 3 0.090 0.850 2.075 2.315 2.455 3948 5875 5719 8511
05020-23-010 500 3 0.090 0.990 2.270 2.520 2.660 4839 7200 6586 9798
05020-33-010 600 2 0.090 1.005 2.410 2.650 2.790 5868 8733 7948 11828
05020-43-010 750 2 0.090 1.160 2.760 2.890 3.030 7225 10751 9267 13790
05021-03-010 1000 1 0.090 1.310 3.080 3.280 3.440 9612 14303 12184 18130
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
ARMOUR INSULATION
SPECIFIC ATIONS CONSTRUC TION
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
• IEEE 383 & 1202 (70,000 Ground (Bonding) Conductor: Uninsulated stranded bare copper conductor
BTU/hr) Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
*Refer to CE Code for details
Options: Galvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
05018-16-010 4 8 0.060 0.350 1.040 1.260 1.350 579 862 1168 1738
1KV T E C K
05018-20-010 3 6 0.060 0.380 1.090 1.310 1.400 748 1113 1373 2043
05018-24-010 2 6 0.060 0.420 1.150 1.370 1.460 919 1368 1583 2356
05018-28-010 1 6 0.080 0.490 1.380 1.600 1.720 1128 1679 2032 3024
05019-04-010 1/0 6 0.080 0.530 1.470 1.690 1.810 1398 2081 2365 3520
05019-08-010 2/0 6 0.080 0.580 1.570 1.790 1.910 1742 2593 2745 4085
05019-12-010 3/0 4 0.080 0.630 1.690 1.910 2.030 2223 3308 3398 5057
05019-16-010 4/0 4 0.080 0.690 1.870 2.090 2.210 2769 4121 4170 6205
05020-04-010 250 4 0.090 0.750 2.010 2.230 2.350 3249 4835 4789 7126
05020-12-010 350 3 0.090 0.860 2.240 2.460 2.600 4528 6738 6307 9385
05020-24-010 500 3 0.090 0.990 2.540 2.760 2.900 6395 9516 8438 12556
05020-44-010 750 2 0.090 1.160 3.020 3.240 3.420 9564 14232 12411 18468
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
CONDUCTOR
SHIELD
19001-01-060 6 8 0.090 0.390 0.540 0.760 0.850 143 213 370 550
19001-02-060 4 6 0.090 0.430 0.620 0.840 0.930 223 332 490 730
19001-04-060 2 6 0.090 0.490 0.670 0.890 0.980 301 448 590 890
19001-05-060 1 4 0.090 0.520 0.710 0.930 1.020 405 603 720 1060
19001-06-060 1/0 4 0.090 0.560 0.740 0.960 1.060 474 705 800 1190
19001-07-060 2/0 4 0.090 0.600 0.810 1.030 1.130 561 835 900 1350
19001-08-060 3/0 3 0.090 0.640 0.860 1.080 1.180 708 1054 1130 1680
19001-09-060 4/0 3 0.090 0.700 0.940 1.160 1.260 847 1261 1330 1970
19001-10-060 250 2 0.090 0.750 1.020 1.240 1.340 1012 1506 1530 2280
19001-11-060 300 2 0.090 0.805 1.075 1.315 1.405 1128 1679 1695 2522
19001-12-060 350 1 0.090 0.850 1.155 1.395 1.480 1345 2001 1960 2910
19001-13-060 400 1 0.090 0.895 1.200 1.440 1.530 1499 2231 2133 3174
19001-15-060 500 1/0 0.090 0.970 1.270 1.490 1.590 1548 2304 2570 3830
5KV UN SH I EL D ED
19001-16-060 600 1/0 0.090 1.055 1.355 1.595 1.705 2174 3235 2929 4359
19001-24-060 750 2/0 0.090 1.150 1.460 1.680 1.780 2243 3338 3900 5800 CO NT R O L
19001-25-060 1000 2/0 0.090 1.300 1.640 1.860 1.960 2819 4195 4930 7340
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.
19003-02-060 6 8 0.090 0.390 1.050 1.270 1.370 301 448 927 1380
19003-03-060 4 8 0.090 0.430 1.150 1.370 1.470 442 658 1138 1694
19003-04-060 2 6 0.090 0.490 1.270 1.490 1.590 703 1046 1476 2197
19003-05-060 1 6 0.090 0.520 1.370 1.590 1.690 970 1444 1752 2607
19003-06-060 1/0 6 0.090 0.560 1.450 1.670 1.770 1082 1610 2012 2994
19003-07-060 2/0 6 0.090 0.600 1.540 1.760 1.860 1343 1999 2334 3473
19003-08-060 3/0 4 0.090 0.640 1.650 1.870 1.970 1720 2560 2835 4219
19003-09-060 4/0 4 0.090 0.700 1.760 1.980 2.080 2315 3445 3328 4952
19003-10-060 250 4 0.090 0.750 1.930 2.150 2.250 2469 3684 3910 5819
19003-11-060 300 4 0.090 0.805 1.980 2.220 2.330 2961 4406 4616 6869
19003-12-060 350 3 0.090 0.850 2.140 2.360 2.490 3476 5173 5102 7592
5KV UN SH I EL D ED
19003-13-060 400 3 0.090 0.895 2.170 2.410 2.550 3948 5875 5836 8685
500
CO NT R O L
19003-15-060 2 0.090 0.970 2.400 2.620 2.750 4837 7198 6721 10001
19003-16-060 600 2 0.090 1.051 2.530 2.750 2.890 5868 8733 8110 12069
19003-20-060 750 2 0.090 1.150 2.790 3.010 3.140 7224 10750 9469 14090
19003-25-060 1000 1 0.090 1.300 3.170 3.390 3.540 9715 14458 13790 20520
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
CONDUCTOR
SHIELD
19002-02-060 6 8 0.090 0.390 0.680 0.900 0.990 144 214 510 770
19002-03-060 4 6 0.090 0.430 0.720 0.940 1.030 224 333 590 880
19002-04-060 2 6 0.090 0.490 0.780 1.030 1.120 302 449 750 1120
19002-05-060 1 4 0.090 0.520 0.810 1.000 1.150 406 604 870 1300
19002-06-060 1/0 4 0.090 0.560 0.880 1.130 1.220 475 707 1010 1500
19002-07-060 2/0 4 0.090 0.600 0.920 1.170 1.260 562 836 1120 1670
19002-08-060 3/0 3 0.090 0.640 0.970 1.220 1.310 709 1055 1300 1930
19002-09-060 4/0 3 0.090 0.700 1.020 1.270 1.360 843 1255 1470 2180
19002-10-060 250 2 0.090 0.750 1.100 1.380 1.480 1013 1508 1680 2500
19002-12-060 350 1 0.090 0.850 1.240 1.520 1.620 1389 2067 2120 3150
19002-14-060 500 1/0 0.090 0.970 1.340 1.620 1.720 1928 2869 2770 4130
19002-16-060 750 2/0 0.090 1.150 1.540 1.830 1.930 2820 4197 3780 5760
19002-17-060 1000 2/0 0.090 1.300 1.760 2.050 2.150 3607 5368 5010 7460
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000 Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test Metallic Shield: Helically applied 15% gapped copper tape
• ICEA T-29-520 (210,000 Ground (Bonding) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000
BTU/hr) Vertical Flame Test Armour: Aluminum Interlocked Armour (AIA)
*Refer to CE Code for details Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: Galvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield
19008-02-060 6 8 0.090 0.900 1.170 1.450 1.540 349 519 1120 1670
19008-03-060 4 8 0.090 0.430 1.260 1.540 1.630 503 749 1350 2010
19008-04-060 2 6 0.090 0.490 1.390 1.670 1.770 771 1147 1740 2590
19008-05-060 1 6 0.090 0.520 1.450 1.730 1.830 939 1397 1960 2920
19008-06-060 1/0 6 0.090 0.560 1.530 1.810 1.910 1148 1708 2290 3410
19008-07-060 2/0 6 0.090 0.600 1.620 1.910 2.010 141 2104 2620 3900
19008-08-060 3/0 4 0.090 0.640 1.780 2.070 2.170 1798 2668 3210 4780
19008-09-060 4/0 4 0.090 0.700 1.900 2.190 2.290 2212 3292 3720 5530
19008-10-060 250 4 0.090 0.750 2.010 2.300 2.430 2583 3844 4300 6400
19008-11-060 300 4 0.090 0.890 2.115 2.355 2.495 3058 4551 4980 7411
19008-12-060 350 3 0.090 0.906 2.210 2.450 2.590 3569 5311 5638 8390
19008-13-060 400 3 0.090 0.960 2.315 2.555 2.695 4054 6033 6202 9230
19008-14-060 500 2 0.090 0.970 2.480 2.770 2.900 4998 7438 7130 10610
19008-16-060 600 2 0.090 1.115 2.645 2.885 3.025 5991 8916 8471 12606
19008-20-060 750 2 0.090 1.150 2.980 3.270 3.420 7440 11072 10330 15370
19008-25-060 1000 1 0.090 1.300 3.310 3.600 3.750 9860 14674 13080 19460
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
CONDUCTOR
SHIELD
CONCENTRIC COPPER
CONDUCTOR
BOND CONDUCTOR
SPECIFIC ATIONS CONSTRUC TION
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000
Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test
• ICEA T-29-520 (210,000 Ground (Bonding/Shield) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000 Armour: Aluminum Interlocked Armour (AIA)
BTU/hr) Vertical Flame Test
Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
*Refer to CE Code for details
Options: Other coloured outer jacket and constructions available upon request
HL
19012-02-060 6 8 0.115 0.440 0.730 0.950 1.040 145 216 550 820
19012-03-060 4 6 0.115 0.480 0.770 0.990 1.080 225 335 680 1010
19012-04-060 2 6 0.115 0.540 0.830 1.080 1.170 303 451 840 1250
19012-05-060 1 4 0.115 0.570 0.910 1.160 1.250 407 606 960 1430
19012-06-060 1/0 4 0.115 0.610 0.940 1.190 1.280 453 674 1060 1570
19012-07-060 2/0 4 0.115 0.650 0.980 1.230 1.320 476 708 1170 1740
19012-08-060 3/0 3 0.115 0.700 1.030 1.310 1.400 563 838 1350 2000
19012-09-060 4/0 3 0.115 0.750 1.080 1.360 1.450 710 1057 1520 2260
19012-10-060 250 2 0.115 0.800 1.160 1.440 1.530 849 1263 1730 2580
19012-12-060 350 1 0.115 0.940 1.290 1.570 1.670 1169 1740 2170 3230
19012-14-060 500 1/0 0.115 1.020 1.410 1.690 1.790 1390 2069 2860 4260
19012-16-060 750 2/0 0.115 1.200 1.600 1.890 1.990 2821 4198 3940 5860
19012-17-060 1000 2/0 0.115 1.350 1.810 2.100 2.200 3608 5369 5090 7570
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000 Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test Metallic Shield: Helically applied 15% gapped copper tape
• ICEA T-29-520 (210,000 Ground (Bonding) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000
BTU/hr) Vertical Flame Test Armour: Aluminum Interlocked Armour (AIA)
*Refer to CE Code for details Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield
19018-03-060 4 8 0.115 0.480 1.370 1.650 1.750 505 752 1500 2230
19018-04-060 2 6 0.115 0.540 1.500 1.780 1.880 744 1152 1930 2870
19018-05-060 1 6 0.115 0.570 1.570 1.860 1.960 943 1403 2150 3200
19018-06-060 1/0 6 0.115 0.610 1.650 1.940 2.040 1151 1713 2430 3620
19018-07-060 2/0 6 0.115 0.650 1.800 2.090 2.190 1417 2109 2890 4300
19018-08-060 3/0 4 0.115 0.700 1.900 2.190 2.290 1796 2673 3360 5000
19018-09-060 4/0 4 0.115 0.750 2.010 2.300 2.430 2215 3296 3940 5860
19018-10-060 250 4 0.115 0.800 2.130 2.420 2.550 2583 3844 4470 6650
19018-11-060 300 4 0.115 0.920 2.225 2.465 2.605 3064 4560 5155 7671
19018-12-060 350 3 0.115 0.940 2.430 2.720 2.850 3572 5316 5650 8400
19018-14-060 500 2 0.115 1.020 2.640 2.930 3.060 5004 7447 7440 11070
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000 Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test Metallic Shield: Helically applied 15% gapped copper tape
• ICEA T-29-520 (210,000 Ground (Bonding) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000
BTU/hr) Vertical Flame Test Armour: Aluminum Interlocked Armour (AIA)
*Refer to CE Code for details Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield
19014-01-012 6 8 0.140 0.495 1.405 1.645 1.755 403 600 1434 2134
19014-04-012 4 8 0.140 0.535 1.490 1.730 1.840 513 763 1619 2409
19014-02-012 2 6 0.140 0.590 1.610 1.850 1.960 783 1165 2127 3165
19014-05-012 1 6 0.140 0.621 1.735 1.975 2.085 951 1415 2482 3694
19014-06-012 1/0 6 0.140 0.658 1.815 2.055 2.165 1160 1726 2769 4121
19014-07-012 2/0 6 0.140 0.702 1.910 2.150 2.260 1426 2122 3137 4668
19014-08-012 3/0 4 0.140 0.749 2.010 2.250 2.390 1759 2618 3679 5475
19014-09-012 4/0 4 0.140 0.801 2.125 2.365 2.505 2226 3313 4258 6337
19014-10-012 250 4 0.140 0.843 2.215 2.455 2.595 2595 3862 4716 7018
19014-13-012 300 4 0.140 0.896 2.325 2.570 2.710 3069 4567 5330 7932
19014-11-012 350 3 0.140 0.940 2.425 2.665 2.810 3583 5332 5977 8895
19014-14-012 400 3 0.140 0.985 2.520 2.760 2.900 4065 6049 6551 9749
19014-12-012 500 2 0.140 1.065 2.685 2.925 3.065 4935 7344 7590 11295
19014-15-012 600 2 0.140 1.140 2.920 3.160 3.330 6001 8390 9143 13606
19014-16-012 750 2 0.140 1.235 3.125 3.365 3.535 7438 11069 10891 16208
19014-17-012 1000 1 0.140 1.385 3.455 3.695 3.865 9868 14685 13765 20485
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
19020-04-032 2 6 0.220 0.760 1.090 1.340 1.430 286 426 1028 1530
19020-05-032 1 4 0.220 0.790 1.120 1.370 1.460 391 582 1170 1740
19020-06-032 1/0 4 0.220 0.830 1.160 1.410 1.500 459 683 1270 1890
19020-07-032 2/0 4 0.220 0.860 1.200 1.450 1.540 546 813 1390 2060
19020-08-032 3/0 3 0.220 0.910 1.250 1.500 1.590 693 1031 1570 2340
19020-09-032 4/0 3 0.220 0.960 1.300 1.580 1.680 830 1235 1780 2650
19020-10-032 250 2 0.220 1.020 1.380 1.660 1.760 989 1472 2010 2990
19020-11-032 350 1 0.220 1.120 1.500 1.780 1.880 1228 1827 2490 3700
19020-12-032 500 1/0 0.220 1.240 1.650 1.940 2.040 1896 2821 3220 4790
19022-12-032 750 2/0 0.220 1.420 1.890 2.180 2.280 2766 4116 4390 6530
19022-25-032 1000 2/0 0.220 1.570 2.050 2.340 2.480 3552 5286 5550 8260
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000 Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test Metallic Shield: Helically applied 15% gapped copper tape
• ICEA T-29-520 (210,000 Ground (Bonding) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000
BTU/hr) Vertical Flame Test Armour: Aluminum Interlocked Armour (AIA)
*Refer to CE Code for details Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), red
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield
19022-01-032 2 6 0.220 0.760 2.020 2.310 2.430 793 1180 2665 3966
19022-02-032 1 6 0.220 0.790 2.100 2.370 2.490 964 1435 3089 4597
19022-03-032 1/0 6 0.220 0.830 2.170 2.460 2.580 1175 1749 3300 4900
19022-04-032 2/0 6 0.220 0.860 2.260 2.550 2.670 1438 2140 3650 5430
19022-05-032 3/0 4 0.220 0.910 2.360 2.650 2.770 1821 2710 4140 6160
19022-06-032 4/0 4 0.220 0.960 2.470 2.760 2.880 2248 3345 4680 6960
19022-07-032 250 4 0.220 1.020 2.590 2.880 3.000 2607 3880 5275 7850
19022-08-032 350 3 0.220 1.120 2.900 3.190 3.330 3597 5353 6842 10181
19022-11-032 500 3 0.220 1.240 3.160 3.450 3.590 5022 7474 8513 12668
19022-16-032 750 2 0.220 1.420 3.570 3.850 4.000 7452 11090 11507 17122
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
19023-02-012 1 4 0.320 0.990 1.365 1.605 1.715 385 573 1386 2063
19023-03-012 1/0 4 0.320 1.026 1.415 1.655 1.765 453 674 1568 2333
19023-04-012 2/0 4 0.320 1.066 1.455 1.695 1.805 538 801 1634 2432
19023-05-012 3/0 3 0.320 1.113 1.490 1.730 1.840 685 1019 1970 2932
19023-06-012 4/0 3 0.320 1.185 1.560 1.800 1.910 818 1217 2136 3179
19023-08-012 250 2 0.320 1.218 1.640 1.880 1.990 974 1449 2366 3521
19023-10-012 350 1 0.320 1.315 1.800 2.040 2.150 1343 1999 2966 4414
19023-12-012 500 1/0 0.320 1.454 1.940 2.180 2.290 1866 2777 3654 5438
19023-14-012 750 2/0 0.320 1.620 2.105 2.350 2.485 2642 3932 4677 6960
19023-15-012 1000 3/0 0.320 1.770 2.235 2.475 2.615 3491 5195 5665 8430
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000 Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test Metallic Shield: Helically applied 15% gapped copper tape
• ICEA T-29-520 (210,000 Ground (Bonding) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000
BTU/hr) Vertical Flame Test Armour: Aluminum Interlocked Armour (AIA)
*Refer to CE Code for details Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: Galvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield
19026-02-012 1 6 0.320 0.990 2.530 2.820 2.940 985 1466 3690 5490
19026-03-012 1/0 6 0.320 1.030 2.650 2.940 3.060 1193 1775 4110 6120
19026-06-012 2/0 6 0.320 1.070 2.740 3.030 3.150 1460 2173 4490 6680
19026-04-012 3/0 4 0.320 1.120 2.910 3.190 3.330 1842 2741 5270 7840
19026-05-012 4/0 4 0.320 1.170 3.020 3.310 3.440 2261 3365 5840 8700
19026-08-012 250 4 0.320 1.220 3.150 3.430 3.580 2629 3912 6440 9590
19026-11-012 350 3 0.320 1.370 3.440 3.730 3.880 3615 5380 7720 11490
19026-12-012 500 2 0.320 1.454 3.625 3.865 4.035 5096 7584 9943 14797
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
19031-02-012 1 4 0.345 1.035 1.385 1.625 1.735 387 576 2477 3686
19031-03-012 1/0 4 0.345 1.076 1.465 1.705 1.815 453 674 1565 2329
19031-04-012 2/0 4 0.345 1.116 1.505 1.745 1.855 538 801 1841 2740
19031-05-012 3/0 3 0.345 1.160 1.525 1.765 1.875 678 1009 1982 2950
19031-06-012 4/0 3 0.345 1.215 1.605 1.845 1.955 818 1217 2204 3280
19031-08-012 250 2 0.345 1.255 1.645 1.885 1.995 975 1451 2397 3567
19031-10-012 350 1 0.345 1.365 1.850 2.090 2.200 1343 1999 3058 4551
19031-12-012 500 1/0 0.345 1.506 1.990 2.230 2.340 1868 2780 3729 5549
19031-14-012 750 2/0 0.345 1.620 2.105 2.345 2.485 2723 4052 4758 7081
19031-15-012 1000 2/0 0.345 1.810 2.280 2.520 2.660 3491 5195 5740 8542
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000 Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test Metallic Shield: Helically applied 15% gapped copper tape
• ICEA T-29-520 (210,000 Ground (Bonding) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000
BTU/hr) Vertical Flame Test Armour: Aluminum Interlocked Armour (AIA)
*Refer to CE Code for details Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield
19027-01-012 1 6 0.345 1.040 2.680 2.970 3.100 988 1470 3980 5930
19027-02-012 1/0 6 0.345 1.080 2.760 3.050 3.180 1200 1786 4360 6490
19027-03-012 2/0 6 0.345 1.120 2.920 3.210 3.360 1466 2182 4950 7370
19027-04-012 3/0 4 0.345 1.170 3.020 3.310 3.460 1848 2750 5490 8160
19027-05-012 4/0 4 0.345 1.220 3.140 3.430 3.580 2264 3369 6090 9060
19027-06-012 250 4 0.345 1.270 3.260 3.550 3.700 2635 3921 6660 9910
19027-08-012 350 3 0.345 1.420 3.560 3.850 4.000 3621 5389 7960 11840
19027-10-012 500 2 0.345 1.506 3.740 3.900 4.150 2893 3980 8008 11917
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
19030-02-010 1/0 4 0.345 1.076 1.465 1.705 1.815 453 674 1565 2329
19030-03-010 2/0 4 0.345 1.116 1.505 1.745 1.885 538 801 1841 2740
19030-04-010 3/0 3 0.345 1.160 1.525 1.765 1.875 678 1009 1982 2950
19030-05-010 4/0 3 0.345 1.215 1.605 1.845 1.955 818 1217 2204 3280
19030-06-010 250 2 0.345 1.255 1.645 1.885 1.995 975 1451 2397 3567
19030-08-010 350 1 0.345 1.365 1.850 2.090 2.200 1343 1999 3058 4551
19030-10-010 500 1/0 0.345 1.506 1.990 2.230 2.340 1868 2780 3729 5549
19030-12-010 750 2/0 0.345 1.620 2.105 2.345 2.485 2723 4052 4758 7081
19030-15-010 1000 2/0 0.345 1.810 2.280 2.520 2.660 3491 5195 5740 8542
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
• CSA FT1 & FT4 Conductor: Bare copper Class B compact or compressed stranded
• CSA C22.2 No. 131 & 174 Conductor Shield: Extruded thermoset semi-conducting shield
• CSA C68.10 Insulation: Tree-Retardant Cross-Linked Polyethylene (TR-XLPE)
• IEEE 383 & 1202 (70,000 Insulation Shield: Extruded thermosetting semi-conducting shield
BTU/hr) Flame Test Metallic Shield: Helically applied 15% gapped copper tape
• ICEA T-29-520 (210,000 Ground (Bonding) Conductor: Stranded bare copper conductor
BTU/hr) Vertical Flame Test
Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
• ICEA T-30-520 (70,000
BTU/hr) Vertical Flame Test Armour: Aluminum Interlocked Armour (AIA)
*Refer to CE Code for details Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
Options: G
alvanized Steel Interlocked Armour (GSIA)
HL Other coloured outer jacket and constructions available upon request
Helically applied 20% overlapped copper tape shield
19028-02-010 1/0 6 0.345 1.080 2.760 3.050 3.180 1200 1786 4360 6488
19028-03-010 2/0 6 0.345 1.120 2.920 3.210 3.360 1466 2182 4950 7366
19028-04-010 3/0 4 0.345 1.170 3.020 3.310 3.460 1848 2750 5490 8170
19028-05-010 4/0 4 0.345 1.220 3.140 3.430 3.580 2264 3369 6090 9063
19028-06-010 250 4 0.345 1.270 3.260 3.550 3.700 2635 3921 6660 9911
19028-08-010 350 3 0.345 1.420 3.560 3.850 4.000 3621 5389 7960 11846
19028-11-010 500 3 0.345 1.510 3.740 3.980 4.250 2893 4305 10133 15083
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. * See pages 30 & 31 for corresponding connector.
Specifications are subject to change without prior notice.
MED IU M VOLTAGE
SH IEL D ED
CO N TR O L
TMC2 Connector
Standard: Aluminum connectors
Options: Also available in nickel plated brass and stainless steel connectors
Locknuts: Aluminum connectors up to 1” hub size - steel locknut included
Aluminum connectors above 1” hub size - sold separately
Nickel plated connectors - all sizes sold separately
Stainless steel connectors - all sizes sold separately
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance.
Specifications are subject to change without prior notice
TMC2X Connector
Standard: Aluminum connectors
Options: Also available in nickel plated brass and stainless steel connectors
Locknuts: All sizes sold separately
RapidEX Sealer Included with Connector
Note: A
ll dimensions are nominal and are subject to normal manufacturing tolerance. Note: On single conductor cables above 600 volts, please contact a Texcan Representative.
Specifications are subject to change without prior notice
EDITOR’S NOTE: Texcan has made every effort to ensure the accuracy of the information in this catalogue. Information contained herein neither constitutes endorsement of the
product nor does Texcan make any claims or guarantees as to the accuracy or the completeness of the information. All information is subject to change without notice and suggestions
made are not to be understood as recommendations to use any products in violation of any regulation or laws relating to any material or its intended use.
Length Conversions
From To Multiply By From To Multiply By
Kilometers Miles 0.06214 Miles Kilometers 1.6093
Meters Feet 3.2808 Yards Meters 0.9144
Meters Inches 39.3701 Feet Meters 0.3048
Meters Yards 1.0936 Feet Centimeters 30.48
Centimeters Inches 0.3937 Inches Meters 0.0254
Centimeters Feet 0.03281 Inches Centimeters 2.54
Millimeters Inches 0.03937 Inches Millimeters 25.4
Millimeters Mils 39.3701 Inches Mils 1000.0
Mils Inches 0.001 Mils Millimeters 0.0254
Mass Conversions
From To Multiply By From To Multiply By
Kilograms Pounds 2.205 Pounds Kilograms 0.4535
Kilograms Short Tons 0.0011 Short Tons Kilograms 907.1848
Grams Grains 15.4323 Grains Grams 0.0647
Grams Ounces 0.0352 Ounces Grams 28.3495
Temperature Conversions
From To Multiply By
Celsius Fahrenheit (ºC x 9/5 ) + 32
Fahrenheit Celsius (ºF - 32) x 5/9
Power Cables Over 600V, Unshielded,Unarmoured 3. With cable grip over non-leaded cable, the maximum
pulling tension should not exceed 1000 lbs or the
The minimum bending radius for all cables is six times the
maximum obtained using TM = 0.008 x n x CM.
overall cable diameter.
4. When more than three conductors are pulled
Power Cables Over 600V, Shielded together, the maximum pulling tension should be
The minimum bending radius for all cables is twelve times the reduced by 20%.
overall cable diameter. B. Maximum Permissible Pulling Length
LM = (TM) / (f x W)
Interlocked Armoured Cable, All Voltages where: LM = pulling length, feet (straight section)
For unshielded Teck cables, the minimum bending radius is TM = maximum tension, lbs
six times the armour outside diameter (as per rule 12-614). f = coefficient of friction (usually 0.5)
For shielded Teck cables, the minimum bending radius is twelve W = weight of cable, lbs/ft
times the diameter (as per Table 15 of the C.E.C.). C. Pulling Tension Requirements in Ducts / Raceway
(refer to rule 12-902 in CE Code)
*Please refer to the C.E.C. for additional information. 1. For straight sections:
TS = L x W x f
Note: B
ending radius refers to the inner surface of the cable at the where: TS = tension at pulling end of straight section, lbs
bend and not at the axis of the cable. L = length of straight section, ft
W = weight of cable, lbs/ft
f = coefficient of friction (usually 0.5)
• S pecial constructions built to customer • Our stocking, cutting and shipment expertise ensure
specifications when requested that your wire and cable requirements are satisfied and
project delays eliminated