Heat Exchanger Performance Report

The technical recommendation form details a proposed chemical cleaning of two coolers, VH 823 and VH 824, at a VCM plant. Temperature data shows poor heat transfer through the coolers compared to design specifications, likely due to dirt and deposits. The recommendation is to chemically clean the heat exchangers to improve performance. Required approvals, tools, and tests are also listed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
75 views3 pages

Heat Exchanger Performance Report

The technical recommendation form details a proposed chemical cleaning of two coolers, VH 823 and VH 824, at a VCM plant. Temperature data shows poor heat transfer through the coolers compared to design specifications, likely due to dirt and deposits. The recommendation is to chemically clean the heat exchangers to improve performance. Required approvals, tools, and tests are also listed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

TECHNICAL RECOMMENDATION FORM

Date: No: TR/________ /________


PLANT
CAP EDC / VCM PVC JETTY

EQUIPMENT
TAG NO. EQUIPMENT DESCRIPTION

PROCESS DATA
LIQUID TEMPERATURE (C) PRESSURE (BARG) MATERIAL

CASE / PROBLEM

ANALYSIS / INSPECTION

RECOMMENDATION

TOOL REQUIRED
1 2 3 4
5 6 7 8
TEST / NDT REQUIRED
PRESSURE TEST PENETRANT TEST ALIGNMENT VIBRATION

RECOMMENDED BY APPROVED BY RECEIVED BY

TECH. MANAGER BUSSINESS TEAM MGR SHE MANAGER


FINAL COMPLETION & HAND OVER
EXECUTED BY INSPECTED BY APPROVED BY
Date: Date: Date: Date:

TECH. MANAGER BUSSINESS TEAM MGR SHE MANAGER


Note:

Note, No diisi: TR/nomor urut hari ini sesuai nomor registrasi buku/tgl-bulan-tahun
TECHNICAL RECOMMENDATION FORM
Date: 10/09/2019 No: TR/________ /________
PLANT VCM
EQUIPMENT NAME Cooler
TAG NO VH 823 and VH 824 Other Specification:
SERVICE HCl -
TEMPERATURE -
PRESSURE -
CAPACITY -
MATERIAL -
CASE / PROBLEM
Heat transfer on VH 823 and VH 824 does not work well. Because it does not give temperature difference between T inlet and T
outlet shows the poor heat transfer in the heat exchanger.

ANALYSIS / INSPECTION
Base on temperature inlet and outlet shows that the difference in temperature value is lower than the design that indicates that
there is a decline in performance of the heat exchanger. The Data is presented as follows:

RECOMMENDATION
The decrease performance of the heat exchanger caused by dirty / deposited so that heat exchanger needs to be done chemical
cleaning.

1 2 3 4
5 6 7 8
TEST / NDT REQUIRED
PRESSURE TEST PENETRANT TEST ALIGNMENT VIBRATION

RECOMMENDED BY APPROVED BY RECEIVED BY

TECH. MANAGER PLANT MANAGER MAINT. MANAGER


Note:

FINAL COMPLETION & HAND OVER


EXECUTED BY INSPECTED BY APPROVED BY
Date: Date: Date: Date:

TECH. MANAGER BUSSINESS TEAM MGR SHE MANAGER


Note, No diisi: TR/nomor urut hari ini sesuai nomor registrasi buku/tgl-bulan-tahun
Distribution: 1. Maintenance 2. Technical 3. Bussiness Team Manager 4. SHE
Sheet4

Surveyor (c) Technical (d) Spv (e) Selisih (c-d) Selisih (c-e) Selisih (d-e)
Initial 1720.5500 1706.4600 1706.4560 14.0900 14.0940 0.0040
ST 101A Final 181.1760 163.8100 163.8330 17.3660 17.3430 -0.0230
Quantity 1539.3740 1542.6500 1542.6230 -3.2760 -3.2490 0.0270
Initial 1629.3970 1616.2640 1617.7590 13.1330 11.6380 -1.4950
ST 101B Final 199.9500 184.8500 184.7480 15.1000 15.2020 0.1020
Quantity 1429.4470 1431.4140 1433.0110 -1.9670 -3.5640 -1.5970
Total Cargo (a) 2968.8210 2974.0640 2975.6340 -5.2430 -6.8130 -1.5700
Kapal (b) 3002.5820 3002.5820 3002.5820 0.0000 0.0000 0.0000
Selisih (b-a) 33.7610 28.5180 26.9480 5.2430 6.8130 1.5700