TYCO Fire Protection Products Technical Support
March 23, 2017
Software Release
Product: 4100ES, 4010ES
Programmer: ESProgrammer_3.06.exe
Executive: ES_3.06.01.bin
Slaves included: 4010IDNETPLUS_3.12.11
(new files in bold) Amp_20203 (cards 566-205, -206, -208 use with > 28 speakers/circuit)
Amp_2.03.03 (cards 566-205, -206, -208 use with up to 28 speakers/circuit)
Amp2_3.02.05 (cards 566-521, -523, -524)
AudAna_20101
AudDig_10502 (card 566-033)
AudDig2_20102 (card 566-409)
BMUX_10102
BNIC_1.01.02
CPUBoot_2.02.03
EBOOT_1.01.03
EOS_1.01.02
EPS_1.05.03
ESS_1.05.03
FUI_1.05
FUIBoot_104
IDNET_3.12.11
IDNET1PLUS_3.12.11
idnet2_1.03.02
IDNETPLUS_3.12.11
lmc_3.01.02
MSS_3.12.11
MSSI_3.12.11
mxdloop_2.01.03
Phone_1.04.01
rps_3.12.11
SecurityZoneRelay_1.02
SPS_204 (for Rev E and earlier boards)
sps_3.12.11
TFXLoop_10103
tic_3.01.02
TIC2_1.01.01
TPS_1.05.05
XALIC_10105
XBC_10604
XPS_3.12.11
XSIG_101
Compatibility See SB11002 (in C:\4100ESINFO)
After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev3-06
Find the documentation in C:\4100ESinfo
To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_3.06.exe
1
ES Programmer 3.06
DBF Revision = 176
Functional Changes:
Release ES 8 Point IO Zone Relay card.
Add “Normally closed” EOLR value to 4007 Zone Relay Card
Fixed Defects:
592278 Creating a List and clicking on Cancel in the dialog where you can name your list closes every
dialogs.
698119 Display cards are not assigned to the correct controller
726570 Import of Small Panel Zone Relay card doesn't work
726575 Able to modify the MONA (2nd point) if <alt> N or [NEXT] button is used after setting a point to
MONA on 4007 Zone Relay Card
736135 Unable to edit Alt Custom Label on Zone Relay card after selecting a MONA point on 4007 Zone
Relay Card
736136 There is no warning pop up when trying to add a second DCAI on the IDNAC PS.
738397 2nd MONA point will appear as MONA or UNUSED depending on how you exit the Card Point
Editing Screen on 4007 Zone Relay Card
738410 Mode, Reference Address, Reference Label should not appear on Zone Relay Point Property
Page for 4007 Zone Relay Card
738411 You are able to modify IO2 point properties from the Point Tab when IO1 is MONA on 4007
Zone Relay Card. All properties should be read only.
738881 Import of Group Activation Lists is not correct
738903 Programmer allows you to Save a job using a name with a space in it.
740607 ERROR 41 during job builder - L185 incorrectly generated
740770 Add BMUX SCCs to where used report
748019 Mouse issues when editing a custom control comment.
748020 Add GSA LED System Option to HELP file
748156 Adding a second unit make crash the programmer when you expend it
755449 Compare Utility should report "No Changes" when comparing the Zones if there are no
differences between the two jobs.
757381 Warn user when Audio files may not download successfully because memory is too close to the
chip size.
757393 Issue importing MX points if done prior to viewing MX Card point editing tab
759117 25V Regulator should be placed in the bay taking 1st available PDI from Right to Left, not left to
right
759452 MX digital loop card power supply is not verified a second time if you drag the card in a second
bay
772793 SP-RABOX -Remote Annunciator Box should only appear for Small Panel and Auto Pulse jobs
772824 Programmer Installation should not attempt to turn off UAC programmatically
772827 Autofill does not write the correct custom label when a MONA point is configured.
772853 Alternate custom label becomes grayed out in the properties of the 4007 zone relay card
nd
772854 Autofill starting with a MONA point will cause the 2 MONA point’s device type to be UNUSED,
and it’s point type to appear as blank on 4007 Zone Relay Card
772855 The Alternate custom label is disabled in the Autofill dialog for 4007 Zone Relay card.
773366 Crash 23 occurring only with a specific job.
779886 External Points are not removed from unchecking "auto list gen externals" on the network tab
780002 QAlert points are generated both in L8 and L147
2
783497 Autofill operation on TFX Loop Card and MX Digital Loop Card causes programmer crash
784180 Deleting the Color User Interface causes the programmer to crash
784332 Programmer crashes when attempting to print labels for 4100-1275/1299 cards
785174 Editing and applying changes on the Card Properties page of Color User Interface causes the
Invert Push button state to reappear
Other Changes:
773476 Add high temp heat device support to legacy IDNet
784411 Add S527 Operation Checkbox on Color User Interface to support S527 Operation ULC Manual
Evac operation
699633 Error Message can be improved for trying to import using an XLG file.
748026 Add IDNet2 upgrade card to the grid view.
4100/4010ES Executive 3.06.01
Functional Changes (Version 3.06)
8 Point IO Card support
Smart Sprinkler 3000 Points support
Fixed Defects (Version 3.06)
726571 CSHOW command for a LedSwitch LED does not show the trouble state of the point.
726576 The CSHOW command does not show the trouble state of a digital pseudo if the point needs ac
740722 Invalid time date entry in historical alarm log when P212 is activated
759102 panel crashes with error 8: TIMER NOT OWNED BY CALLER
759514 DT SECURITY with PT SMALARM displays point status NORMAL when physical state is
shorted
759530 Legacy city alarm relay activates at startup
759549 Capture information is lost if panel crashes during AT6 capture
772568 From the FUI, cannot enable and disable MONA POINT (IO1/IO3/IO5) except the last one (IO7)
772569 From the front panel: not able to enable MONA POINT IO1. From the Service port: only can
disable MONA point IO7
772880 Crash dump file lost
772985 LEGACY: Lamp Test broken
774406 Event-time on LCD annunciator is incorrect
783458 Master Does not check the Speaker Relay Status Properly before turning off the Associated
NAC circuit
785167 During alarm, TSPAGE OFF operation on VNAC turns off that VNAC, which were on due to
alarm
Fixed Defects (Version 3.06.01)
788196 panel crash with error "Structure not dequeued"
788299 TS1,2 and 3 leds on the display module referenced to a custom VNAC do not follow the the
behavior of led programmed as L1,2,3
788422 The time date does not advance from 2/28/17 into 3/1/17, the date stays on 2/28 at the front
panel
788423 front panel show error when change the time date for leap year
788440 IDNet goes to IDNet Channel Failure with 3PII Devices (Beam Sensor)
788442 master crashes with MCF crash 3 - Address Error when SIG905 is referenced to TSPAGE
switch modes
3
Other Changes
None
Usage Notes
Revision 3.06.01 of the ESSupport tools should be used with this release.
Requires revision 2.02.02 or greater of CPU Bootloader.
Requires InfoAlarm revision 1.04 and InfoAlarm Bootloader revision 1.04.
Requires EPS revision 1.05.03 or later
Cpuboot_2.02.03.bin
Functional Changes
None
Fixed Defects
773509 Updated IOEthernet.c in CPUBOOT2 to configure the new PHY to operate the ethernet LED
indicators in the same fashion as the original PHY.
Other Changes
None
SecurityZoneRelay_1.02.bin
Functional Changes
N/A
Fixed Defects
N/A
Other Changes
Initial Release
4010IDNETPLUS_3.12.11
IDNET_3.12.11
IDNET1PLUS_3.12.11
IDNETPLUS_3.12.11
Functional Changes
668181 Short search cannot be completed.
4
Fixed Defects
783420 4009A latched OC trouble (power fail) cannot be cleared in hardware reset.
Other Changes
None
MSSI_3.12.11
sps_3.12.11
Functional Changes
None
Fixed Defects
677882 SQALERT device does not turn on horn/strobe in local mode.
783420 4009A latched OC trouble (power fail) cannot be cleared in hardware reset.
Other Changes
668181 Short search cannot be completed.
MSS_3.12.11
rps_3.12.11
XPS_3.12.11
Functional Changes
None
Fixed Defects
677882 SQALERT device does not turn on horn/strobe in local mode.
Other Changes
None
lmc_3.01.02
tic_3.01.02
Functional Changes
None
Fixed Defects
788127 Slaves could not go into local mode.
Other Changes
None
5
idnet2_1.03.02
Functional Changes
None
Fixed Defects
772756 An IAM that is placed at a configured address of MCOPS reports head missing trouble
instead of wrong device.
783419 4009A latched OC trouble (power fail) cannot be cleared in hardware reset.
785088 Beam sensor sensitivity updates are not downloaded to the Beam controller.
785301 A 4009A device may not be recovered if it is quickly power off/on.
Other Changes
None