The IEE tutorial workshop on
Earthing & Bonding techniques
for electrical installations.
Presentation by:
Geoff Cronshaw,
  Chief Engineer,
  Standards and Compliance,
  IEE.
IEE tutorial workshop
1. Overview of earthed and unearthed
   electrical systems.
2. Performance requirements of BS 7671.
3. Type of earthing systems, advantages,
   disadvantages, and applications of
   different systems, use of RCD’s.
1. Overview of earthed and
unearthed electrical systems
• It is necessary to determine the type of system, i.e.TN-S,
  TN-C-S, TT, etc, of which the proposed installation will
  form a part, before proceeding with the installation
  design.
• A distributor is required on request to provide a
  statement on the type of earthing (Reg 28 of the
  Electricity Safety, Quality and Continuity Regulations)
  and unless inappropriate for reasons of safety, the
  distributor is required to make available his supply
  neutral conductor or protective conductor for connection
  to the consumer’s earth terminal (Reg 24).
• For a low voltage supply given in accordance with the
  Electricity Safety, Quality and Continuity Regulations
  2002 the supply system will be TN-S, TN-C-S(PME)
  or TT, and most commonly for new supplies TN-C-S.
• TN-C and IT systems are both very uncommon in the
  UK, the former because it requires an exemption from
  the Electricity Safety, Quality and Continuity
  Regulations which invoke special installation
  arrangements and the latter because the source is not
  directly earthed and this is not permitted for a low
  voltage public supply in the UK (Reg 8).
• For TN-S, TN-C-S and TT systems the following
  explanations should aid a full understanding of the
  earthing arrangements and their scope of application.
  The nomenclature of these system types is as follows:
  T = Earth (from the French word Terre)
  N = Neutral
  S = Separate
  C = Combined
         TN-S system earthing
                            system
                        (origin of
                       installation)
          source of supply           installation
              L                                                     installation
                                                                    equipment
              N
              PE
                                                                     Exposed-
             T                           542-01-02                  conductive-
source                N-S                                              part
 earth
                  (separate neutral (N) and protective conductors
                  (PE) throughout the system)
                                                           circuit protective
                                                               conductors
                        TN-S                                                                LABEL - Safety Electrical
                                                                                           Connection. Do not remove
                         Electricity
                                                                                       metal water
           kWh           company
                                                                                          pipe
                          isolator
         S7 6E 165456
                                                                                                                        metal gas
                                                                                                                          pipe
        L N NL
                                        main switch
                    Main
                    earthing            LABEL - Safety Electrical
100 A                                  Connection. Do not remove
                    terminal
                                                                                                            gas meter
                                                                                   Water         Gas
                                                                                service pipe service pipe
TN-S system
A TN-S system has the neutral of the source of
  energy connected with earth at one point
  only, at or as near as is reasonably
  practicable to the source, and the consumer’s
  earthing terminal is typically connected to the
  metallic sheath or armour of the distributor’s
  service cable into the premises or to a
  separate protective conductor of, for instance,
  an overhead supply
    TN-C-S system earthing
                L
                PEN                      N
                              link       PE
                                       542-01-03
source                          additional
 earth                          source electrode
                    T
                        N-C             S
         (combined neutral and        (separate neutral (N) and
         protective conductor (PEN)   protective conductors (PE)
         in source of supply, with    within installation)
         PME applied)
                                                           circuit protective
                        TN-C-S
                                                               conductors
                                                                                        LABEL - Safety Electrical
                                                                                       Connection. Do not remove
                        Electricity
                        company                                                    metal water
          kWh
                         isolator                                                     pipe
        S7 6E 165456
                                                                                                                    metal gas
                                                                                                                      pipe
        L N NL
                                      main switch
                   Main
100 A
                   earthing
                                        LABEL - Safety Electrical
                   terminal
                                       Connection. Do not remove
                                                                                                        gas meter
                                                                               Water         Gas
                                                                            service pipe service pipe
TN-C-S system
A TN-C-S system has the supply neutral
  conductor of a distribution main connected
  with earth at source and at intervals along its
  run. This is usually referred to as protective
  multiple earthing (PME). With this
  arrangement the distributor’s neutral
  conductor is also used to return earth fault
  currents arising in the consumer’s installation
  safely to the source. To achieve this, the
  distributor will provide a consumer’s earthing
  terminal which is linked to the incoming
  neutral conductor.
TT system earthing
                   542-01-04
source
         T   T
 earth           consumer’s
                 earth
                                                                          circuit protective
                      TT                                                      conductors
                                                                                                    LABEL - Safety Electrical
                                                                                                   Connection. Do not remove
                                     Electricity                                                  metal water
                        kWh
                                     company                                                         pipe
 Electricity Supply                   isolator
(usually overhead)
                      S7 6E 165456                                                                                              metal gas
                                                                                                                                  pipe
                      L N NL
                                                        main switch
             100 A            Main
                              earthing
                              terminal
                                                                                                                   gas meter
                                                    LABEL - Safety Electrical
                                                   Connection. Do not remove
                                                                                             Water         Gas
                         Earth Rod                                                        service pipe service pipe
TT system
A TT system has the neutral of the source of
  energy connected as for TN-S, but no facility
  is provided by the distributor for the
  consumer’s earthing. With TT, the consumer
  must provide his or her own connection to
  earth, i.e. by installing a suitable earth
  electrode local to the installation.
2. Performance requirements
   of BS 7671
• A wide variety of types of earth electrode are recognised by BS
  7671. The most suitable type for a particular system will depend
  upon a number of factors, the single most important of these being
  the soil resistivity of the ground. If earth rods are to be driven it may
  be necessary to go down several metres before a good conductive
  layer is reached, especially where the water table is low. Rods can
  only be as effective as the contact they make with the surrounding
  material. Thus, they should be driven into virgin ground, not
  disturbed (backfilled) ground. Where it is necessary to drive two or
  more rods and connect them together to achieve a satisfactory result,
  the separation between rods should be at least equal to their
  combined driven depth to obtain maximum advantage from each rod.
• In some locations low soil resistivity is found to
 be concentrated in the topsoil layer, beneath
 which there may be rock or other impervious
 strata which prevents the deep driving of rods, or
 a deep layer of high resistivity. Only a test or
 known information about the ground can reveal
 this kind of information. In such circumstances,
 the installation of copper earth tapes, or pipes or
 plates, would be most likely to provide a
 satisfactory earth electrode..
•   Closely spaced buildings may sometimes make it
    difficult to find ground suitable for driving an earth
    electrode. Electrodes which employ suitable structural or
    other underground metalwork, or the metal reinforcement
    of concrete embedded in the ground may then be of
    particular advantage. Whatever form an earth electrode
    takes, the possibility of soil drying and freezing, and of
    corrosion, must be taken into account. Preferably, testing
    of an earth electrode should be carried out under the least
    favourable conditions, i.e. after prolonged dry weather.
    Further information on earthing principles and practice
    can be found in BS 7430 : 1998 ‘Code of Practice for
    Earthing’ (formerly CP 1013: 1965).
• Earthing conductors - The earthing conductor of
  an installation is part of the earth current path. It
  is therefore important that the conductor is
  adequately sized and, particularly where buried
  partly in the ground, of suitable material and
  adequately protected against corrosion and
  mechanical damage.
• The size of an earthing conductor is arrived at in
  basically the same way as for a circuit protective
  conductor, except that Table 54A of BS 7671
  must be applied to any buried earthing
  conductor. For a TN-C-S (PME) supply, the
  designer will additionally require it to be no
  smaller than the main bonding conductors.
•   Sizing of circuit protective conductors.
    There are several factors which may influence or
    determine the size required for a circuit protective
    conductor. A minimum cross-sectional area of 2.5 mm2
    copper is required for any separate circuit protective
    conductor, i.e. one which is not part of a cable or formed
    by a wiring enclosure or contained in such an enclosure.
    An example would be a bare or insulated copper
    conductor clipped to a surface, run on a cable tray or
    fixed to the outside of a wiring enclosure. Such a circuit
    protective conductor must also be suitably protected if it
    is liable to suffer mechanical damage or chemical
    deterioration or be damaged by electro-dynamic effects
    produced by passing earth fault current through it. If
    mechanical protection is not provided the minimum size
    is 4 mm2 copper or equivalent.
• BS 7671 provides two methods for sizing protective
  conductors including earthing conductors (see also Table
  54A). The easier method is to determine the protective
  conductor size from Table 54G, but this may produce a
  larger size than is strictly necessary, since it employs a
  simple relationship to the cross-sectional area of the
  phase conductor(s).
• The second method involves a formula calculation. The
  formula is commonly referred to as the ‘adiabatic
  equation’ and is the same as that used for short-circuit
  current calculations (see Regulation 434-03-03). It
  assumes that no heat is dissipated from the protective
  conductor during an earth fault and therefore errs on the
  safe side. Even so, application of the formula will in
  many instances result in a protective conductor having a
  smaller csa than that of the live conductors of the
  associated circuit. This is quite acceptable.
• Regulation 543-01-03 states :
543-01-03 The cross-sectional area, where calculated, shall
  be not less than the value determined by the following
  formula or shall be obtained by reference to BS 7454:
                                   I 2t
                          S=
    where:
                                   k
S   is the nominal cross-sectional area of the conductor in mm2.
I   is the value in amperes (rms. for a.c.) of fault current for a fault of negligible
    impedance, which can flow through the associated protective device, due
    account being taken of the current limiting effect of the circuit impedances
    and the limiting capability (I2 t) of that protective device. Account shall be
    taken of the effect, on the resistance of circuit conductors, of their
    temperature rise as a result of overcurrent - see Regulation 413-02-05.
t   is the operating time of the disconnecting device in seconds corresponding to
    the fault current I amperes.
k   is a factor taking account of the resistivity, temperature coefficient and heat
    capacity of the conductor material, and the appropriate initial and final
    temperatures.
3. Type of earthing systems,
advantages, disadvantages,
and applications of different
systems, use of RCD’s.
Protective multiple earthing (PME).
Such a supply system is described
in BS 7671 as TN-C-S.
• The Electricity Safety, Quality and Continuity
  Regulations 2002 permit the distributor to combine
  neutral and protective functions in a single conductor
  provided that, in addition to the neutral to earth
  connection at the supply transformer, there are one or
  more other connections with earth.
• This protective multiple earthing (PME) has been
  almost universally adopted by supply companies in the
  UK as an effective and reliable method of providing
  their customers with an earth connection. Such a supply
  system is described in BS 7671 as TN-C-S.
           PME earth terminal
                                                      L1
                                                      L2
                                                      L3
                                                      PEN
                                   PME earth
Source earth                       terminal    Additional
                    L    N   PE                earth
                             protective
                             conductor
               Customer’s installation
• However, under certain supply system fault conditions
  (external to the installation) a potential can develop
  between the conductive parts connected to the PME
  earth terminal and the general mass of earth.
• Supply system
  There are multiple earthing points on the supply
  network, and providing bonding within the building
  complies with BS 7671 it is unlikely that such a
  potential as described above would in itself constitute a
  hazard.
• Additional earth electrode for PME supplies.
• In the unlikely event of the PEN conductor of the
  supply becoming open circuit, touch voltages perhaps
  causing some discomfort may arise on exposed metal in
  customers installations downstream of the open circuit.
                • The effect can be mitigated by connection of a suitable
                  earth electrode to the main earth terminal of the
                  customers installation. The value of the resistance to-
                  earth necessary to limit the touch voltages to a given
                  value depends on the load and the network parameters:
                                                         Consumer’s
Line                 Re                                  installation
                                                    L
           Vs                                                           RL
                                      PEN           N
PEN                       Open-
                                                    PE
                          circuit
                          PEN
                                                          Vp
      RB                                       RA
Where:
Vs is the nominal supply (source) voltage
Vp is the touch voltage
Re is the external supply resistance
RL is the load resistance (Vs2 / wattage)
RA is the resistance of the additional earth
   electrode including parallel earth (e.g.
   water and gas pipes)
RB is the resistance to earth of the neutral
   point of the power supply.
• Special locations
  The Electricity Association provides guidance on PME
  in its Engineering Recommendation G12/3,
  ‘Requirements for the application of protective multiple
  earthing to low voltage networks’. The guidance given
  in this Section is based on Part 6 of G12/3.
• Remote supplies.
  A physically isolated building may be supplied via both
  a long LV distribution main and a long individual
  service. If these circumstances are coupled with an
  unbalanced load a potential difference will be evident
  between the PME terminal and true earth.
• This rise in neutral potential is transferred to metalwork
  connected to the PME terminal, and may be noticeable
  in such locations as shower areas, where simultaneous
  contact with true earth (a wet concrete floor) and the
  PME terminal (shower pipes) may be possible.
• G12/3 recommends that such floors should incorporate
  a metal grid connected to the supplementary bonding
  within the shower/bathing area. Certainly, if there is a
  grid in the floor it must be connected to the local
  supplementary bonding. An alternative approach would
  be not to use the PME earthing terminal and to afford
  protection by means of RCDs and an independent earth
  electrode, that is, treat as part of a TT system.
• Sports pavilions
  Where no shower area exists nor is likely to exist in a
  sports pavilion, PME may be offered provided the
  appropriate metalwork is bonded. Where a shower
  exists PME should only be applied where there is an
  earth grid in the floor of the shower area,
  supplementary bonded to accessible metal pipework,
  etc. An alternative would be to plumb the installation in
  plastic pipes.
• Swimming pools
  Swimming pools supplied with their own dedicated
  service should be protected with an RCD. All
  metalwork should be bonded and connected to an earth
  electrode. Where a swimming pool forms part of a
  residence, all metalwork and pipes supplying the pool
  should be connected to an earth electrode and
  segregated from the rest of the building. An RCD
  should then be used to protect the supplies to the pool
  area and the swimming pool installation treated as part
  of a TT system. Where segregation of pipes and
  metalwork around a pool is impracticable, e.g. in an
  indoor pool, the installation of a metal grid around the
  pool and the supplementary bonding of adjacent
  metalwork is recommended together with an RCD in
  addition to PME.Additional earth electrode for PME
  supplies.
• Agricultural and horticultural premises
  A PME terminal may be used in these premises
  provided main equipotential bonding has been carried
  out and the additional measures required by Section
  605 of BS 7671 have been provided, e.g. reduced
  disconnection times, supplementary bonding, RCD
  protection. The general principles to be adopted for
  separate buildings utilizing a PME terminal are as
  follows:
  (i) each separate building should have a designated
       main earthing terminal within the building
  (ii) any main equipotential bonding required in a
       separate building to external services, structural
       metalwork, etc, should be connected to the
       designated earth terminal. The cross-sectional area
       of the bonding conductor should be selected from
       Table 54H of BS 7671 using the electricity
       distributor’s supply neutral conductor as reference.
• Livestock/dairies
  Particular care must be taken in areas where livestock
  are housed as they are sensitive to small potential
  differences.
• Building and construction sites, quarries, etc
  It may be difficult to satisfy the electricity distributors
  bonding requirements because of the large number of
  parts of the building works that are extraneous-
  conductive-parts. In these circumstances a PME
  earthing terminal may not be provided. Regional
  electricity companies may be prepared to offer a TN-S
  supply to large sites requiring their own substation
  where the earthing terminal can be connected directly
  to the transformer neutral. For quarries, see also below.
• Caravan park and marinas
  Regulation 9(4) of the Electricity Safety, Quality and
  Continuity Regulations does not allow the combined
  neutral and protective conductor to be connected
  electrically to any metalwork in a caravan or boat. This
  prevents PME terminals being used for caravans or
  boat mooring supplies, although they may be used for
  fixed premises on the sites, such as the site owner’s
  living premises and any bars or shops, etc. Account is
  taken of this in Section 608 of BS 7671 with respect to
  caravans, and also will be for marinas when a section is
  included in the standard. The extension of PME to
  toilets and amenity blocks is not recommended as there
  is a high probability of people going barefoot and being
  in good contact with true earth through wet concrete
  floors.
                        Typical site distribution for a PME
                        supply, separation from PME earth at
                        main distribution board
TNC Supply (PME)                          Main Board             Distributor                  pitch supply     Pitch
                                                                                                             outlets
                                                               100 mA or greater
                                                                                   general purpose
                                                               RCD in insulated
     L        L                                                enclosure
                                                                                   30 mA RCD
     PEN      N
                                                         RCD                         RCD
              PE
                                             Installation earthing to
                                              be separated from the
                                                  PME earthing
                   Resistance areas of installation
                     and supply earthing to be
                             separated
                   Typical site distribution for a PME
                   supply, separation from PME earth at
                   pitch supply point
Isolator                                          Distributor    pitch supply point     Pitch
                            Main Board
TNC Supply (PME)                                                                      outlets
                                                Overcurrent
                                                device to
                                                disconnect
                                                O.4 s
                                                                30 mA RCD
L        L
PEN      N
                                                                 RCD
         PE
                    Cable protective conductor
                    (armour/sheath) separated from RCD
                    earth and caravan protective conductors
• Petrol filling stations
  The reference publication is “Guidance for the design,
  construction, modification and maintenance of petrol
  filling stations”, published by the APEA and the
  Institute of Petroleum, which recommends a TT supply
  for hazardous areas.
  A separate earth electrode and RCD or other alternative
  arrangement is required to ensure the segregation of
  petrol filling area earthing and that of the PME earth of
  the distribution network. A PME earth may be used for
  permanent buildings such as shops and
  restaurants.Additional earth electrode for PME
  supplies.
• Mines and quarries
  A supply taken to an underground shaft, or for use in
  the production side of a quarry, must have an earthing
  system which is segregated from any system bonded to
  the PME terminal.
• Supply terminating in a separate building
  Occasionally a service will terminate in a position
  remote from the building it supplies. The size of the
  PME bonding in the building supplied must be related
  to the size of the incoming supply cable, in accordance
  with Regulation 547-02-01 and Table 54H of BS 7671.
  If the size of the circuit protective conductor of the
  cable between the supply intake position and the
  building is less than that of the PME bonding
  conductor, a suitable additional conductor will have to
  be installed or the PME earth not used.
                 Supply terminating in a separate
                 building
                                                                         Main Equipotential
                                                                         Bonding to be related
      Remote supply                                Building              to the neutral of the
      termination                                  Supplied              main cable M
Supplier’s
   cutout                   Size of protective
                            conductor/armouring to
               Main earth   be related to the neutral
                                                                Earth
                terminal    of the main cable M
                                                              terminal
             Main supply
              cable M
                                  Sub main S
• PME and outside water taps
  Under an open-circuit supply neutral condition the
  potential of an outside water tap will rise above earth
  potential. A person coming into contact with the tap
  could receive an electric shock and the shock could be
  severe, if that person were barefooted. The probability
  of these two conditions occurring together is considered
  to be so small that the use of PME where a metal
  outside tap exists is not precluded. It is recommended,
  however, that a plastic insert be provided in the pipe to
  the outside water tap.
• High rise buildings
  For guidance on the application of PME to high rise
  buildings and building complexes, guidance should be
  sought from the electricity supply company and
  Engineering Recommendation G12/3.
• Highway power supplies
  Street electrical fixtures were exempted from the
  requirements of Regulation 7 of the former Electricity
  Supply Regulations 1988 as amended. The exemption
  allowed the minimum copper equivalent cross sectional
  area of the main equipotential bonding conductor to be
  reduced to 6 mm2 in specific circumstances. As the
  Electricity Safety, Quality and Continuity Regulations
  do not specify minimum sizes of main bonding
  conductors, it is to be presumed that it would be
  reasonable to allow the reduction in size for street
  lighting equipment in the same circumstances as
  before. Although BS 7671 at present has a minimum
  size of 10 mm2 for supply neutral conductors of 35
  mm2 csa or less, it would seem appropriate to reduce
  the minimum size to 6 mm2 for supply neutral
  conductors of 6 mm2 csa or less, see Regulation
  547-02. However, the departure from Part 5 would
  need to be recorded on the Electrical Installation
  certificate.
A TT system
• A TT system has the neutral of the source of energy
  connected as for TN-S, but no facility is provided by
  the distributor for the consumer’s earthing.
• With TT, the consumer must provide his or her own
  connection to earth, i.e. by installing a suitable earth
  electrode local to the installation. The circumstances in
  which a distributor will not provide a means of earthing
  for the consumer are usually where the distributor
  cannot guarantee the earth connection back to the
  source, e.g. a low voltage overhead supply, where there
  is the likelihood of the earth wire either becoming
  somehow disconnected or even stolen.
• A distributor also might not provide means of earthing
  for certain outdoor installations, e.g. a construction site
  temporary installation, leaving it to the consumer to
  make suitable and safe arrangements for which they are
  fully responsible. The electricity distributor is required
  to make available his supply neutral or protective
  conductor for connection to the consumer’s earth
  terminal, unless inappropriate for reasons of safety
  (Reg 24). Construction site, farm or swimming pool
  installations might be inappropriate unless additional
  precautions are taken, such as an additional earth
  electrode.
A TN-S system
• A TN-S system has the neutral of the source of energy
  connected with earth at one point only, at or as near as
  is reasonably practicable to the source, and the
  consumer’s earthing terminal is typically connected to
  the metallic sheath or armour of the distributor’s
  service cable into the premises or to a separate
  protective conductor of, for instance, an overhead
  supply.
• Large consumers may have one or more HV/LV
  transformers dedicated to their installation and installed
  adjacent to or within their premises. In such situations
  the usual form of system earthing is TN-S. It is not
  necessary for the star (neutral) point of the transformer
  LV secondary to be brought out at the transformer
  cable box in order to earth this point. The usual and
  most convenient means of earthing the source neutral is
  for the connection to earth to be made at the first
  accessible position in the LV system at which the
  neutral is terminated, i.e. LV feeder pillar or main LV
  switchboard.
Use of RCD’s
• Supplementary protection by residual current devices.
• With specific exceptions, supplementary protection by
  a residual current device must be provided in every
  circuit intended or reasonably expected to supply
  portable equipment for use outdoors.
• Residual current devices do not prevent shock currents
  flowing through the body, for a current must flow to
  earth for the residual current device to detect. However,
  provided the residual current device is sufficiently
  sensitive and functionally tested periodically it will
  operate sufficiently quickly to prevent injury.
• Automatic disconnection of supply
• BS 7671 prescribes automatic disconnection of the
  supply to any circuit, i.e. distribution circuit or final
  circuit, in which an earth fault may occur. This is
  irrespective of how successful the earthing and bonding
  provisions may be in keeping down the magnitude of
  voltages that may appear between exposed-conductive-
  parts and extraneous-conductive-parts conductive-parts
  during an earth fault, since, even if there is no shock
  risk, thermal damage may be caused to conductors or
  their surroundings if earth fault current is allowed to
  persist. Whatever the type of system, the operating
  characteristic of each device for automatic
  disconnection and the relevant impedance of the
  associated circuit should be properly co-ordinated to
  achieve the required disconnection time.
• For installations supplied at nominal voltages (Uo) in
  the range 121 - 277 V to earth the prescribed maximum
  disconnection times are generally 0.4 s or 5 s, but are
  0.2 s for some special locations.
• An RCD may be used to provide indirect shock
  protection in TN systems where the earth fault loop
  impedance (Zs) is insufficiently low to operate a fuse or
  circuit-breaker within the prescribed disconnection
  time. An RCD may also be required for installations or
  locations of increased shock risk, such as those in
  Part 6 of BS 7671. Where more than one RCD is used
  they and their circuits should be segregated, or if RCDs
  are used in series the upstream device needs to be time
  delayed or S type and the downstream a type for
  general use, both to BS EN 61008 or BS EN 61009 to
  achieve discrimination.
Mixed disconnection times
• The requirements for mixed disconnection times apply
  for any final circuits supplied from the same
  distribution board, distribution circuit or sub-main. This
  includes adjacent boards supplied from a common
  circuit or with a common bonding connection.
• Mixed disconnection times within an installation can
  give rise to a particular problem. Consider two final
  circuits of an installation as shown below:
        Final circuits having 'mixed' disconnection
        times (Regulation 413-02-13)
                                          distribution
                                          board
                                                                                          exposed-conductive-part
                                                                     circuit A
                                                                                                        load A
L                                                                                                       (indoors)
                                                                                fixed
                                                             circuit B          Load B
250 V
                                                                                                                    Uf
N
         main earthing                                                                                      protective
         terminal                                                          If                               conductor
                                                                                                            in cord
E
                             Rc
                                                         further equipotential
                     main equipotential
                                                         bonding conductor
                     bonding
                                                         (if necessary)
                     conductor
                                                                         extraneous-conductive-part
                     earth
• Other ways of avoiding or overcoming the problem
  could include:
  (i) design all circuits supplied from a common
       distribution board or distribution circuit to achieve
       disconnection within 0.4 s
  (ii) use RCD (RCCB or RCBO) protection. This would
       have to include, in the example illustrated, fixed
       equipment circuit B. Fitting an RCD to socket-
       outlet circuit A would not solve the possible
       problem, since the RCD would be unaffected by the
       appearance of the voltage Uf and any current this
       might send through the body of a person who
       makes simultaneous contact with the exposed-
       conductive-part of load A and the nearby
       extraneous-conductive-part.Additional earth
       electrode for PME supplies.
• Automatic disconnection in a TT system Other than in
  exceptional circumstances in which steel reinforcement
  of underground concrete or similar structure is
  available for use, in TT systems it is often difficult and
  costly to achieve a sufficiently low earth electrode
  resistance for overcurrent devices to be used for
  indirect shock protection.
We have covered a brief
overview of earthing.
Thank you for listening, and
have you any questions?