TAC MicroNet 2000
                                                                                                                   TM
                                                   The TAC MicroNet Sensor
                                                   TAC MicroNet Sensors are a family of digital room temperature sensors used with the
                                                   TAC MicroNet 2000™ Controllers. Available in three models, TAC MicroNet Sensors are
                                                   microprocessor-based and include industry standard thermistors for accurate room sens-
                                                   ing and plug-in communication jacks for the TAC MicroNet Controller Interface.
• Contemporary, low-profile packaging.            Using the digital wall sensor, the operator can monitor the performance of the product,
                                                   edit operational values, and even reprogram the controller, if provided with the proper
• Digital zone temperature indication (select-
                                                   password level. Up to two sensors can be connected to a TAC MicroNet 2000 Control-
   able 0.1° or 1° display in Fahrenheit or
                                                   ler providing more sophisticated information such as BTU calculations for the controlled
   Celsius).
                                                   zone.
• Accurate temperature sensors provide inter-
   changeability without recalibration.            TAC MicroNet Sensors are suitable for direct-wall, 2 x 4 electrical box, 1/4 DIN electrical
• Self compensating temperature conversions       box, or surface box mounting.
   remove the need to calibrate over time.
                                                   The TAC MicroNet 2000 family of controllers interconnects with all Building Automation
• Pushbutton override capabilities allow tenant
                                                   Systems manufactured by TAC, providing full integration with the other systems within
   to switch to timed occupied mode for after
                                                   the facility. Communications is optimized throughout the system to provide immediate
   hours operation.
                                                   feedback for the facility operator. The digital wall sensor is durable, and offers easy moni-
• Accepts virtually any wiring type including     toring and a wide variety of interface capabilities for the user. Through the wall sensor’s
   unshielded pairs without termination resis-     communication jack, the TAC MicroNet Controller Interface software may be utilized to
   tors.                                           set up and monitor TAC MicroNet Controllers.
• Displays selected system values such as
   setpoints, outdoor air temperature, operating   A TAC MicroNet Sensor connected to a TAC MicroNet 2000 Controller is considered a
   mode, and actual air flow.                      stand-alone digital temperature control component. The TAC MicroNet Sensor mea-
                                                   sures room conditions and relays the information to the controller via the U-Link™. The
• Provides the ability to change operational
                                                   Controller Interface Module plugs into the communication jack on the sensor to provide
   mode with proper access level.
                                                   a user interface to the controller via the TAC MicroNet Controller Interface.
• Configurable intuitive display screens that
   are permanently retained, even if the TAC         Table-1	         Model Chart.
   MicroNet Sensor is replaced.
                                                      Model              Description                  Keypad                     Display
                                                       MN-S       Sensor only                No                          No
                                                                                                                         Override occupied
                                                                  Sensor with
                                                      MN-SO                                  One-button                  Status
                                                                  override
                                                                                                                         Indication only
                                                                                                                         Digital Liquid Crystal
                                                     MN-SDK       Deluxe                     Four-button
                                                                                                                         Display
    SOFTWARE SPECIFICATIONS
    Access Levels (MN-SDK only)
      Three access levels for monitoring, operating, and editing functions with automatic
      time-out feature.
    Digital Display (MN-SDK only)
      Custom field configurable sensor displays.
      Auto-ranging of displayed values.
      Occupant command capabilities.
      Adjustable minimum/maximum limit setpoint values.
      Controller driven, automatically configured, customized display/command values (see
      Table-2).
      Table-2 Typical MN-SDK Display/Change Values.
                   Value                           Display                 Change
     Time Format (12 or 24 hour)                    Yes                      Yes
     Zone Temperature                               Yes                      No
     Outdoor Air Temperature                        Yes                      No
     Percent Room Humidity                          Yes                      Yes
     Heating Setpoint                               Yes                      Yes
     Cooling Setpoint                               Yes                      Yes
     Mode (Heating/Cooling/Occ/Un-                  Yes                      No
     occ)
     Time/Day of Week Schedule                      Yes                      No
    Communications
    TAC MicroNet U-Link
      Provides power and communication interface to the TAC MicroNet Sensor. 200 ft
      (61 m) between controller and controlled devices or peripherals. 400 ft (122 m) total
      distance including all wire segments.
    Plug-in Communication Jack
      Provides receptacle for TAC MicroNet Controller Interface Module (MN-CIM) for
      user access to the TAC MicroNet 2000 Controller via the TAC MicroNet Controller
      Interface software.
    Accessories
      AT-1104	                 Cast aluminum guard
      AT-1155	                 Plastic guard
      AT-1163	                 Wire guard
      MNA-STAT-2	              Designer inserts for MN-S model (qty. 25)
      MNA-STAT-3	              Designer inserts for MN-SO model (qty. 25)
2
SPECIFICATIONS
MF2 SERIES
Hardware Specifications                       Wiring Terminals
Dimensions                                    Screw terminals.
  4-13/16 in. H x 3-1/4 in. W x 15/16 in. D     #18 to 24 AWG.
  (122 mm x 83 mm x 24 mm).
                                              Inputs
Enclosure                                     Display Range
  Conforms to NEMA-1 Requirements.              Setpoints/input span varies with the
                                                controller application.
Surge Immunity Compliance
  IEC 801.5 and ANSI C62.41 (IEEE-587,        Temperature
  Category A & B).                              –320 to 320 °F (–195 to 160 °C).
Transient Compliance                          Humidity
  IEC 801.4.                                   0 to 100% RH.
Electrostatic Discharge Compliance            Flow
  IEC 801.2.                                    0 to 9,990 CFM. (Larger values can be
                                                monitored and accessed via the TAC
Agenc y Approvals                               MicroNet Controller interface.)
UL-916
  File #E71385 Category PAZX.                 Command Options
                                                Varies with the controller application.
CSA
  File #LR 3728.                              System Mode
                                                Heat/Cool/Off/Auto or other configu-
FCC                                             rations.
  Class A.
                                              Fan Mode
Ambient Limits                                  On/Off.
Operating Temperature
 32 to 122 °F (0 to 50 °C).                   System
                                                On/Off.
Shipping and Storage Temperature
  –40 to 160 °F (–40 to 71 °C).               Override
                                               Occupied/Unoccupied.
Humidity
 5 to 95% RH, non-condensing.
                         TAC MicroNet VAV MN-CIM
                         Series Controller TAC MicroNet Controller
                                           Interface Module
                         U-Link
                                                    RS-232
                   TAC MicroNet
                        Sensor                       TAC MicroNet Controller
                                                       Interface (Software)
                         Figure-1 TAC MicroNet 2000 Architecture.
                                                                                          3
Copyright © 2006, TAC                                            TAC
All brand names, trademarks and registered trademarks are        1354 Clifford Avenue
the property of their respective owners. Information contained   PO Box 2940
within this document is subject to change without notice.        Loves Park, IL 61132-2940
All rights reserved.
                                                                 www.tac.com
F-25834-2