MANUAL BAX 3945

External Bypass for UPS - Series:


JOVYTEC – P / POWERMASTER - S

UPS - Devision

Index Date Name Status


0 07.04.2009 A.Heller First Edition
1
2
3
4
5
6
7
8
9
10

JOVYATLAS GmbH
Groninger Straße 29 - 37
D-26789 Leer
Germany
Phone : ++49 491 - 6002 - 30
Fax : ++49 491 - 6002 - 10
E-mail : service@jovyatlas.de
Internet : http://www.jovyatlas.de
JOVYATLAS

NOTES!
Notes concerning this operating manual
Thank you for deciding to purchase this manual bypass for ups devices out of the series: JOVYTEC P and POWERMASTER S. They
represent reliable protection for the attached consumers.

Please read through this manual very carefully


This manual contains regulations covering safety, installation and operating methods which will help you guarantee to obtain the full
performance und operational readiness which the manual bypass can offer.

Put this manual in a place of safe keeping


It contains important regulations for safe use of these manual bypasses and for reaching manufacturer services if, for some reason,
correct operation of the manual bypass is in doubt.

Keep or reuse the packaging material


The packaging material for the manual bypass was designed with great care to protect its contents against damage during transport.
This material is also useful if you ever have to send the manual bypass back for checking. Damage which occurs during transport is not
covered by the warranty provisions.

Duty to instruct persons


This operating manual is to be read through carefully before assembly and first use of the manual bypass by persons who will be
working with or on the manual bypass.
This operating manual is an integral part of the manual bypass. The operator of this device is required to make this operating manual
available in an unlimited fashion to every group of persons commission it, maintain it or who do any other kind of work on this device.

Validity
This operating manual is in line with state-of-the-art of the manual bypass technology at its time of publishing. The contents are not part
of the contract but simply serve as a source of information.
JOVYATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating
manual without having to make an announcement to this effect. JOVYATLAS GmbH cannot be held responsible for any errors or
improper information in this operating manual since there is no duty upon the company to update this operating manual on an ongoing
basis.

Loss of warranty
Our deliveries and services rendered are subject to the General Delivery Conditions for Products of the Electrical Industry as well as
our General Sales Conditions. We reserve full rights to make any changes to this operating manual, in particular to technical data,
operation, dimensions and weights. We request that you make any claims concerning delivered goods within eight days after arrival of
the goods together with the packing slip. Complaints made later than this cannot be considered.
JOVYATLAS GmbH will annul all duties upon JOVYATLAS GmbH and its dealers such as promises to offer a warranty period, service
contracts etc. without warning if any spare parts other than original JOVYATLAS GmbH parts or parts bought from JOVYATLAS GmbH
are used for maintenance and repair purposes.

Handling
This operating manual for the manual bypass is constructed in such a way that all work required for commissioning, maintenance and
repair can be conducted by appropriate skilled personnel.

The Service Hotline


There is further information available under Chapter “Service information“ or questions about the manual bypass, about the operating
manual, service etc.

Copyright
Any passing on, duplication and/or transfer by means of electronic or mechanical means, also extracts thereof, of this operating manual,
requires express prior written permission from JOVYATLAS GmbH.
Copyright JOVYATLAS GmbH 2009. All rights reserved.

Manual BAX 3945 Page 2


JOVYATLAS
Table of Contents
Chapter Description Page

1. TECHNICAL DATA 4

1.1 Technical Data Manual Bypass JOVYTEC P 700 – P3000 4

1.2 Technical Data Manual Bypass POWERMASTER S 1002 –S 3002 19“ 5

1.3 Technical Data Manual Bypass POWERMASTER S 6000 19“ 6

2. DESCRIPTIONS 7

2.1 Manual Bypass JOVYTEC P 700 - 3000 7

2.2 Manual Bypass POWERMASTER S 1002 - 3002 8

2.3 Manual Bypass POWERMASTER S 6000 9

3. ELEKTRICAL CONNECTION 10

3.1 Circuit Diagram Manual Bypass 10

3.2 Switch Procedure 11

3.2.1 Activating the Manual Bypass 11

3.2.2 DEACTIVATING THE MANUAL BYPASS 12

4. CUSTOMER SERVICE 13

Manual BAX 3945 Page 3


JOVYATLAS
1. Technical Data

1.1 Technical Data Manual Bypass JOVYTEC P 700 – P3000

Manual Bypass JOVYTEC P 700- P3000


Power 700VA - 3000VA
Voltage 230V
Current max. 16A
Mains Frequency 50Hz or 60Hz
Phase 1-phase
External Fuse D01/16A
230V s
Voltage
standard
Output
Frequency 50Hz or 60Hz
Phase Single phase
0°C to 40°C
Temperature
Enviroment +15 … +25°C
Humidity 0% bis 95%, not condensing
Storage at … -20°C to 70°C
Width 198mm
Dimensions Depth 89mm
Height 135mm
Weight Manual Bypass ca. 2,9 kg
Manual Bypass
Delivery Hardware Manual BAX 3945
Connection Cables (Option)

Manual BAX 3945 Page 4


JOVYATLAS
1.2 Technical Data Manual Bypass POWERMASTER S 1002 –S 3002 19“

Manual Bypass POWERMASTER S1002- S3002


Power 1000VA - 3000VA
Voltage 230V
Current max. 16A
Mains Frequency 50Hz or 60Hz
Phase Single Phase
External Fuse D01/16A
Voltage 230V standard
Output Frequency 50Hz or 60Hz
Phase Single Phase
0°C to 40°C
Temperature
Enviroment +15 … +25°C
Humidity 0% to 95%,
Storage at … -20°C to 70°C
Width 483mm (19“)
Dimensions Depth 140mm
Height 133mm
Weight Manual Bypass app. 2,9 kg
Manual Bypass
Delivery Hardware Manual BAX 3945
Connection Cable (Option)

Manual BAX 3945 Page 5


JOVYATLAS
1.3 Technical Data Manual Bypass POWERMASTER S 6000 19“

Manual Bypass POWERMASTER S 6000


Power 6000VA
Voltage 230V
Current nom. 26A
Mains Frequency 50Hz or 60Hz
Phase Single Phase
External Fuse D02/35A
Voltage 230V Standard
Output Frequency 50Hz or 60Hz
Phase Single Phase
0°C to 40°C
Temperature
Enviroment +15 … +25°C
Humidity 0% bis 95%, not condensing
Storage at … -20°C to 70°C
Width 483mm (19“)
Dimensions Depth 140mm
Height 133mm
Weight Manual Bypass ca. 3,2 kg
Manual Bypass
Delivery Hardware Manual BAX 3945
Connection Wires (Option)

Manual BAX 3945 Page 6


JOVYATLAS
2. Descriptions

2.1 Manual Bypass JOVYTEC P 700 - 3000


The external manual bypass consists of an additional wall housing with a special changeover switch. This
change over switch offers the possibility to switch over without an interruption and reverse voltage on the ups
– system. It allows a direct main supply to the attached critical load. The wall housing is fitted with terminals
for connecting up the mains power supply, the consumers and the UPS unit. A built-in yellow indicator lamp
shows whether the manual bypass is active. The cable guide in the wall housing takes place from below
through the screwed cable glands installed for that purpose. The connection cables can be ordered as an
option.

ACTIVATING THE BYPASS: DEACTIVATING THE BYPASS:


At UPS - Device: At Manual Bypass:
SIGNAL LAMP TXXXXXXXXXXXXXXXXXXXXXXXXxXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX At UPS - Device:
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
At Manual Bypass: XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXX At Manual Bypass:
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
SELECTOR SWITCH XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXX
2 XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
At UPS - Device:
XXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
1 3 XXXXXXXXXXXXXXXXXXXXXXXXXXxX XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXx
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX

3
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXX
1. - MANUAL BYPASS OFF XXXXXXXXXXXXXXXXXXXXXXXXXXXXX.

2. - MAINS VOLTAGE ON
3. - MANUAL BYPASS ON communications

MAINS INPUT LOAD UPS-INPUT UPS-OUTPUT

Manual bypass

Dimensions of the manual


Width Height Depth Weight
bypass

JOVYTEC P max. 189 mm max. 135 mm max. 89 mm ca. 2.9 kg


(incl. hinges) (incl. PG screw connections) (incl. switch)

The manual bypass is suitable for wall mounting!

The manual bypass allows the UPS unit to be completely disconnected from the mains power supply
network. Neither the input mains nor the consumers have any connection to the UPS. Maintenance work and
service work can now be conducted on the unit itself.

P L E A S E N OT E!
If the UPS needs to be unclipped and replaced by another device then open ends
of cables must be insulated for accident prevention purposes.
For a battery change ensure that the UPS unit was set to manual bypass via the
display panel.

Manual BAX 3945 Page 7


JOVYATLAS
2.2 Manual Bypass POWERMASTER S 1002 - 3002
The external manual bypass consists of an additional 19” plate with a special changeover switch. This
change over switch offers the possibility to switch over without an interruption and reverse voltage on the ups
– system. It allows a direct main supply to the attached critical load. The housing is fitted with terminals for
connecting up the mains power supply, the consumers and the UPS unit. A built-in yellow indicator lamp
shows whether the manual bypass is active. The connection cables must be secured by pull reliefs, which
are already installed. The connection cables can be ordered as an option.

Dimensions of the manual


Width Height Depth Weight
bypass

POWERMASTER S max. 483 mm max. 133 mm max. 160 mm ca. 2.9 kg


(incl. switch)

The manual bypass is suitable for wall mounting!

The manual bypass allows the UPS unit to be completely disconnected from the mains power supply
network. Neither the input mains nor the consumers have any connection to the UPS. Maintenance work and
service work can now be conducted on the unit itself.

P L E A S E N OT E!
If the UPS needs to be unclipped and replaced by another device then open ends
of cables must be insulated for accident prevention purposes.
For a battery change ensure that the UPS unit was set to manual bypass via the
display panel.

Manual BAX 3945 Page 8


JOVYATLAS
2.3 Manual Bypass POWERMASTER S 6000
The external manual bypass consists of an additional 19” plate with a special changeover switch. This
change over switch offers the possibility to switch over without an interruption and reverse voltage on the ups
– system. It allows a direct main supply to the attached critical load. The housing is fitted with terminals for
connecting up the mains power supply, the consumers and the UPS unit. A built-in yellow indicator lamp
shows whether the manual bypass is active. The connection cables must be secured by pull reliefs, which
are already installed. The connection cables can be ordered as an option.

Dimensions of the manual


Width Height Depth Weight
bypass

POWERMASTER S max. 483 mm max. 133 mm max. 160 mm ca. 3.2 kg


(incl. switch)

The manual bypass is suitable for wall mounting!

The manual bypass allows the UPS unit to be completely disconnected from the mains power supply
network. Neither the input mains nor the consumers have any connection to the UPS. Maintenance work and
service work can now be conducted on the unit itself.

P L E A S E N OT E!
If the UPS needs to be unclipped and replaced by another device then open ends
of cables must be insulated for accident prevention purposes.
For a battery change ensure that the UPS unit was set to manual bypass via the
display panel.

Manual BAX 3945 Page 9


JOVYATLAS
3. Elektrical Connection

3.1 Circuit Diagram Manual Bypass

H1
YE
X2

2 4
7 6

S1
8 5
1 3

L1

N X1
PE

1 2 3 4 5 6 7 8 9 10 11 12

L1 N PE L1 N PE L1 N PE L1 N PE

Netzeinspeisung Verbraucher USV Eingang USV Ausgang

Mains Input Load UPS Input UPS Output

1x230V/50Hz 1x230V/50Hz

Manual BAX 3945 Page 10


JOVYATLAS

3.2 Switch Procedure

3.2.1 Activating the Manual Bypass

Switching the Manual Bypass from UPS – Operation to Bypass Operation


Adjustments at the UPS - Device
Switch Positions Switch Manual Signal Lamp UPS – Display UPS – LED UPS – LED
and Indications Bypass Manual Bypass ON – LINE BYPASS
Normal Position 1 OFF LINE MODE ON OFF
Push Button FUNC
First Parameter
at the UPS for 2 1 OFF ON OFF
O/P Volt Set
Seconds
Push Button FUNC
several times until MANUAL
1 OFF ON OFF
BYPASS appears BYPASS
in Display
Push Button ENTER
to select 1 OFF Bypass OFF ON OFF
MANUAL BYPASS
Change Display
Announcement
Bypass OFF
by pushing the
1 OFF Bypass ON ON OFF
FUNC Button to
BYPASS ON.
Confirm by pushing
the ENTER Button.
Display Message MANUAL
1 OFF OFF ON
MANUAL BYPASS BYPASS
Adjustments at the Manual Bypass, when the UPS – Device has been switched to Bypass
Switch Manual
Bypass Switch direct
from Position 1
(MANUAL BYPASS MANUAL
3 ON OFF ON
OFF) to BYPASS
Position 3
(MANUAL BYPASS
ON)
Remark: The UPS – Device is now completely disconnected from Mains an must be switched off. For
exchanging or maintaining, the ups can be disconnected from the supplying line or be opened.

Manual BAX 3945 Page 11


JOVYATLAS
3.2.2 Deactivating the Manual Bypass

Switching the Manual Bypass from Bypass Operation to UPS Operation

Adjustments at the Manual Bypass

Switch Positions Switch Manual Signal Lamp UPS –Display UPS – LED UPS – LED
and Indications Bypass Manual Bypass ON – LINE BYPASS
Manual Bypass Switch
on Position 3: 3 ON OFF OFF OFF
MANUAL BYPASS ON
Switch Manual Bypass from
Position 3: MANUAL BYPASS
2 ON OFF OFF OFF
ON to Position 2: MAINS
VOLTAGE ON

Remark: The Display will light and also the Fans will start to work!!!

Adjustments at the UPS - Device

Switch ON the UPS by


pushing the ON/OFF Button
2 ON Ready on OFF OFF
until the beeping sound
stops.
The UPS initialize, wait until
MANUAL
MANUAL BYPASS will 2 ON OFF ON
BYPASS
appear in the Display.

Adjustments at the Manual Bypass

Switch the Manual Bypass Switch


from Position 2:
MAINS VOLTAGE ON MANUAL
1 OFF OFF ON
to BYPASS
Position 1: MANUAL BYPASS
OFF

Adjustments at the UPS - Device

Push the FUNC – Button First Parameter


1 OFF OFF ON
for 2 Seconds O/P Volt Set
Push Button FUNC
several times until MANUAL
1 OFF OFF ON
BYPASS appears BYPASS
in Display
Push Button ENTER
MANUAL
to select 1 OFF OFF ON
BYPASS
MANUAL BYPASS
Change Display Announcement
Bypass ON
by pushing the FUNC Button to MANUAL
1 OFF OFF OFF
BYPASS OFF. BYPASS
Confirm by pushing
the ENTER Button
The Message MANUAL BYPASS at
the display will
disappear after initializing
the UPS and the Message 1 OFF LINE MODE ON OFF
LINE MODE will occur
in Display. This can last 30
Seconds.

The UPS is now completely set into operation again!!

Manual BAX 3945 Page 12


JOVYATLAS
4. Customer Service
The manual bypass is completely maintenance free.

NOTE:

i When ordering spare parts always the designation (position/component) and unit number
shall be stated.

Our customer service department will be pleased to send you a complete spare part list for your manual bypass
upon request.
Please contact the following address in this case or if you should have any questions or suggestions:

JOVYATLAS GmbH
Groninger Strasse 29-37
26789 Leer
Germany

P.O. Box 1580


26765 Leer
Germany
Phone : + 49 - 491 - 6002 - 30
Fax : + 49 - 491 - 6002 - 10
Internet : http://www.jovyatlas.de
E-Mail : service@jovyatlas.de

ATTENTION:
We draw your attention to the fact that spare parts not supplied by us are not tested or
approved. Installation of such spare parts can therefore have a detrimental effect on the
operation and passive safety of the unit. We do not accept any liability for any resulting damage.

Manual BAX 3945 Page 13