Electrical & Automation
Wärtsilä JOVYCUBE
PRODUCT LE AFLET
The modular UPS systems of the type Wärtsilä JOVYCUBE are based on a 20 kVA UPS
module and offer a flexible solution for power supply from 20 kVA up to 640 kVA. The UPS
modules convince by efficient power control, dynamic transition without failover times as
well as with a high efficiency of 96%. They dispose of an extensive battery management with
dynamic load control. The UPS systems Wärtsilä JOVYCUBE can work single-phased as
well as three-phased.
ONLINE UPS SYSTEM                                                  each other. Due to the large AC input voltage range the
As online systems (double converter, continuous trans-             UPS system Wärtsilä JOVYCUBE is especially suitable for
ducers technology) Wärtsilä JOVYCUBE UPS systems                   instable power grids.
protect against system interferences and failures of any           The systems work with smooth load transfer – gradually
kind in a secure and economic way.                                 step-by-step transfer of load from the DC to the AC sour-
                                                                   ce is carried out. This so-called dynamic load transfer,
HIGH EFFICIENCY AND FLEXIBILIT Y BY MEANS                          in which the loads are switched partially or completely
OF TO MODULES                                                      between AC and DC sources, is able to capture peak
For the realisation of different types of power supply             loads from the battery and helps to reduce energy costs.
solutions three types of control cabinets JOVYCUBE 60,             Furthermore the permanent energy-saving mode ensures
JOVYCUBE 160 and JOVYCUBE 200 are available, which                 optimal efficiency together with low energy costs.
can each accommodate a high number of 20 kVA mo-                   The Wärtsilä JOVYCUBE UPS systems combine a modular
dules. Via parallel connection further and higher perfor-          inverter of 20 kVA with a battery charger. The modules
mance ranges can be achieved.                                      can be exchanged under operating conditions without
Wärtsilä JOVYCUBE UPS systems can work single-                     observing specific operation procedures (Hot-Swap). A
phased as well as three-phased. (3:3 / 3:1 / 1:1 / 1:3). The       permanent power-saving mode provides for an optimal
AC input and AC output frequency are independent from              efficiency.
                 Autonomy Times [min]                                                Power UPS System
                                                            20       40      60      80     100     120     140     160     180     200
        Battery Cabinet                   Termination      [kVA]    [kVA]   [kVA]   [kVA]   [kVA]   [kVA]   [kVA]   [kVA]   [kVA]   [kVA]
     BC26-1/32     32 Batteries à 26 Ah    BC2055101       14,5       6
     BC26-2/64     64 Batteries à 26 Ah    BC2055102        38      14,5     8       6
     BC26-3/96     96 Batteries à 26 Ah    BC2055103        66       26     14,5     10      7       6       5
   BC26-4/128     128 Batteries à 26 Ah    BC2055104       101       38      23     14,5     11      8       7       5
      BC44-1/32    32Batteries à 44 Ah     BC2055401        28       10      6
     BC44-2/64    64 Batteries à 44 Ah     BC2055402        83       28      15      10
     BC44-3/96    96 Batteries à 44 Ah     BC2055403       136       53      28      19      12      10      8       7
   BC44-4/128 128 Batteries à 44 Ah        BC2055404       187       83      45      28      21     14,5     11      10
     BC70-1/32     32 Batteries à 70 Ah    BC2055601        62       24      11      8
     BC70-2/64     64 Batteries à 70 Ah    BC2055602       161       62      35      24      16      11      10      8
     BC70-3/96     96 Batteries à 70 Ah    BC2055603       274       113     62      44      29      24      18      14      11      10
   BC70-4/128     128 Batteries à 70 Ah    BC2055604       414       161    100      62      48      35      28      24      20      15
12 / 2016
                                                                                               WÄRTSILÄ JOV YCUBE
TECHNICAL DATA
                               JOVYCUBE 60 JOVYCUBE 160 JOVYCUBE 200
   Power                          20 - 60 kVA          20-160 kVA              20-200 kVA
                                                                                                       MODUL AR ONLINE UPS
   Output power                 20 kVA / 20 kW       20 kVA / 20 kW           20 kVA / 20 kW           VFI /Double Converter Techno-
   per module
                                                                                                       logy, Maximum safety for con-
   Number of mountable                1-3                  1-8                    1 - 10               nected consumers / loads
   modules
   Dimensions cabinet           600x1900x800         600x1900x800             600x1900x800             HIGH EFFICIENCY SAVES
   W x H x D [mm]                                                                                      ENERGY COSTS
   Dimensions module             483x133x600          483x133x600             483x133x600              Ma ximum output ef fective
   W x H x D [mm]                                                                                      power (K VA = K W )
   Weight module [kg]                24 kg                 24 kg                  24 kg
                                                                                                       EFFICIENT POWER
INPUT
                                                                                                       CONTROL
   Nominal voltage               3x380 V/220 V+N, 3x400 V/230 V+N, 3x415 V/240 V+N                     by intelligent and integrated
   Tolerances of input                    198 VAC up to 264 VAC at >70% load                           control
   voltage
                                            150 VAC up to 264 VAC at <70% load
                                                                                                       HIGHEST FLEXIBILITY
                                  3x343 VAC/198 V+N up to 3x457 VAC+N at >70% load                     by 20 kVA module
                                  3x260 VAC/150V+N up to 3x457 VAC+N at <70% load
   Frequency                                         47 Hz up to 63 Hz                                 FORECASTS FOR BATTERY
   Power factor                                 ≥0,99 (25% up to 100% load)                            CAPACITY AND SPARE TIME
OUTPUT
                                                                                                       HOT-SWAPPING
   Nominal voltage                     220 VAC or 230 VAC or 240 VAC (adjustable)                      Exchange of modules during
                                     3x380 VAC+N or 3x400VAC+N or 3x415 VAC+N                          running operation
   Stability of output                                 static:   ≤ ±2%
   voltage                      dynamic (load step 0% --> 100% and 100% --> 0%): ±3%
   THDI                                             at linear load <±2%,
                                        at non linear load <±4% (EN62040-3-2001)
   Frequency                                             50 or 60 Hz
   Tolerance of the output              freerunning (AC input not existing): ±0,1%.
   frequency                            synchronised with AC-input 47 up to 63 Hz
                                              Freerunning out of this range.
   Unbalanced load                                    100 % per phase
                                                                                               Fig.1 Wärtsilä JOV YCUBE with battery cabinet
   capacity
   Overload capacity                        130% for 15 sec, 110% permanent
                               (at nominal voltage, in dependency to ambient temperature)
   Short circuit possibility             4 x In with existing AC-input within 20 ms
   Crest Factor                                              2.7:1
   Efficiency                                AC-AC: 96% / 96% / 95% / 93 %
   100%/75%/50%/25%                          DC-AC: 97% / 97% / 95% / 93 %
BATTERY SYSTEM
   VRLA-Battery, battery voltage: ±192 VDC in total (384 VDC), number of battery cells:
   192, with reduced power range operation with 180 cells is possible
COMMUNICATION
   Communication / information takes place via UPS interfaces for parametrisation and
   system informations, 6 digital inputs and 7 relais outputs