LEGENDS AND SYMBOLS: LEGENDS AND SYMBOLS:
GLASS FRAME LED PINLIGHT, DAY LIGHT,
CONVENIENCE OUTLET
DROP LAMP
ACU OUTLET
15 WATTS LED RECESSED WALL LIGHT ACU
ACU ACU
S SINGLE SWITCH
RANGE OUTLET
R
2GS SINGLE SWITCH
550mm ABOVE FP 550mm ABOVE FP
PANEL BOARD
3GS SINGLE SWITCH
S3S SINGLE SWITCH 550mm ABOVE FP
PANELBOARD
550mm ABOVE FP
ACU
550mm ABOVE FP
1200mm ABOVE FP
R 550mm ABOVE FP
C10
01 LIGHTING LAYOUT PLAN 02 POWER LAYOUT PLAN
A 04 SCALE: 1:100 MTS A 04 SCALE: 1:100 MTS
REGISTERED ARCHITECT PROJECT TITLE SUBMITTED BY GRADE SHEET NO.:
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF REGISTERED ARCHITECT REGISTERED ARCHITECT A
SOUTHERN PHILIPPINES 4-6
GENERAL NOTES SPECIFICATIONS
1. ALL ELECTRICAL WORKS/INSTALLATION SHALL BE DONE IN ACCORDANCE WITH
THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINES
ELECTRICAL CODE, WITH THE RULES AND REGULATION OF THE
NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE
ENFORCEMENT OF THE ELECTRICAL LAW AND ORDINANCE, THE
RULES AND REGULATIONS OF THE LOCAL POWER COMPANY
CONCERNED, AND IN ACCORDANCE WITH THE APPROVED
MANUFACTURERS RECOMMENDATIONS.
2. ALTHOUGH NOT INDICATED IN THE PLAN, A UTILITY BOX SHALL BE PROVIDED
SCHEDULE OF LOADS AND DESIGN COMPUTATION FOR THE FOLLOWING EQUIPMENTS AND FIELD DEVICES, MAIN
CONTROL PANEL, (MCP) PIR MOTION INDICATOR, SMOKE
DETECTORS, ELECTRIC SIREN, STROBE LIGHT, ELECTRIC
FEEDER CIRCUIT DESCRIPTION LO CO OTHERS VOLTS LOAD AMP CIRCUIT SIZE OF WIRE & PIPE FIREARM BELL, DURESS/PANIC BUTTON AND KEY PAD UNIT.
NO. PROTECTION PLATE COVER SHALL BE PROVIDED FOR FUTURE EXPANSION
DEVICES.
1 LIGHTING 11 220 1100 2.73 15 AT 2.0 mm2 @ 21 pvc
3. WIRING METHOD SHALL BE AS FOLLOWS:
2 LIGHTING 11 220 1100 1.82 15 AT 1
b) POLYVINYL CHLORIDE PIPE (PVC) @ FOR AUXILIARY LAY OUT.
2.0 mm2 @ pvc
2
c) RIGID STEEL CONDUIT (RSC) @ FOR FEEDER LAY OUT.
3 LIGHTING 12 220 1200 2.27 15 AT 2.0 mm2 @ 21 pvc d) ELECTRICAL METALLIC TUBING (EMT @ FOR POWER AND LIGHTING LAY OUT
4 LIGHTING 10 220 1000 2.27 15 AT 2.0 mm2 @ 21 pvc 4. MINIMUM SIZE OF WIRES FOR POWER AND LIGHTING LAY OUT SHALL BE 3.5mm
CONVENIENCE 1 220 180 1.22 20 AT THHN AND 15mm0 (NOMINAL DIAMETER) RESPECTIVELY. WIRE
5 3.5 mm2 @ 21 pvc
INSULATION ARE GOOD FOR 600 VOLTS.
6 ACU 1 220 2500 11.36 30 AT 5. ALL ELECTRICAL MATERIALS TO BE USED SHALL BE NEW AND OF APPROVED
5.0 mm2 @ 21 pvc
TYPE FOR BOTH PURPOSE AND LOCATION INTENDED.
7 ACU 1 220 2500 11.36 30 AT 5.0 mm2 @ 21 pvc
8 ACU 1 220 2500 11.36 30 AT 5.0 mm2 @ 21 pvc
USE 2-38mm THW
9 ACU 1 220 2500 11.36 30 AT COPPER WIRE & 1-22mm
5.0 mm2 @ 21 pvc FROM SERVICE THW COPPER WIRE
1
10 RANGE 1 220 2500 11.36 30 AT 5.0 mm2 @ pvc
2 UTILITY PROVIDER FOR MAIN & NEUTRAL
M FEEDER RESPECTIVELY
11 SPARE 220
200 AT
12 SPARE 220 15 AT 15 AT
LIGHTNING OUTLET 1 15 AT 15 AT
2 LIGHTNING OUTLET
LIGHTNING OUTLET 3 20 AT 30 AT
4 LIGHTNING OUTLET
17080 67.11 CONVENIENCE OUTLET 5 6 ACU
30 AT 30 AT
ACU 7 30 AT 30 AT
8 ACU
ACU 9 10 RANGE
SPARE 11 12 SPARE
COMPUTATION OF LOADS:
LOAD AMP
I = 17080 / 220 = 77.63 x 1.25
= 97.04 AMPS
GROUNDING
SINGLE LINE DIAGRAM
A 0105 SCALE: 1:50 MTS
REGISTERED ARCHITECT PROJECT TITLE SUBMITTED BY GRADE SHEET NO.:
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF REGISTERED ARCHITECT REGISTERED ARCHITECT A
SOUTHERN PHILIPPINES 5-6
FROM SERVICE
UTILITY PROVIDER
LEGENDS AND SYMBOLS: M
CLOSE-CIRCUIT TELEVISION
ACU ACU
ACU AIR CONDITIONING UNIT
WF WIFI ROUTER
W D
TV TELEVISION
REF REFRIGERATOR
W D
W WASHER
D DRYER
TELEPHONE
WF TP
ACU
REF
TV
TP
ACU
01 ELECTRONIC LAYOUT PLAN
A 06 SCALE: 1:100 MTS GROUNDING
02 SINGLE LINE DIAGRAM
GENERAL NOTES AND SPECIFICATIONS
A 06 SCALE: 1:100 MTS
1. ALL ELECTRONIC WORKS/INSTALLATION SHALL BE DONE IN ACCORDANCE WITH
THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINES
ELECTRONIC CODE, WITH THE RULES AND REGULATION OF THE
NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE
ENFORCEMENT OF THE ELECTRONIC LAW AND ORDINANCE, THE
RULES AND REGULATIONS OF THE LOCAL POWER COMPANY
CONCERNED, AND IN ACCORDANCE WITH THE APPROVED
MANUFACTURERS RECOMMENDATIONS.
2. CONTRACTOR SHALL SECURE A PERMIT AND ALL FEES REQUIRED FOR THE WORKS AND FURNISH THE OWNER THE ELECTRONIC INSPECTION
3. ALTHOUGH NOT STATED IN THE PLAN, ALL CCTV MUST BE INSTALLED AT LEAST 2.5M HIGHER FROM THE FLOOR LINE.
4. ALL WIRING CONNECTIONS SHOULD BE CHECKED BY THE PROFESSIONALS
5. ALL ELECTRONIC MATERIALS TO BE USED SHALL BE NEW AND OF APPROVED TYPE FOR BOTH PURPOSE AND LOCATION INTENDED.
REGISTERED ARCHITECT PROJECT TITLE SUBMITTED BY GRADE SHEET NO.:
UNIVERSITY OF SCIENCE AND TECHNOLOGY OF REGISTERED ARCHITECT REGISTERED ARCHITECT A
SOUTHERN PHILIPPINES 6-6