Electric amplifiers RE 30054/03.

12
Replaces: 01.09
1/6

Type VT-VRPA1-5...-1X/...-RTP

Component series 1X

Table of contents Features


Contents Page – Suitable for controlling proportional valves
Features 1 – Analog amplifiers in Europe format for installation
Ordering code, accessories 2 in 19" racks
Front plate 2 – Controlled output stage
Block diagram with pin assignment 3 – Position control with PID behavior
Technical data 4 – Fast energization and fast deletion for short actuating times
Setting information 5 – Enable input
Unit dimensions 5 – Adjustable ramp that can be switched off
Project planning / maintenance instructions / – Cable break detection for actual value cable
additional information 5 – Inputs and outputs short-circuit-proof
– Adjustment possibilities for zero point and sensitivity, ac-
celeration and braking ramp

Notice:
The photo shows an example configuration.
The delivered product differs from the figure.
2/6 Bosch Rexroth AG Hydraulics VT-VRPA1-5...-1X/...-RTP RE 30054/03.12

Ordering code, accessories

VT- V R P A 1 1X V0 RTP
Hydraulic component Option
For valves with electric feedback =R RTP = Adjustable ramp that
Valve type can be switched off
4/2 high-response valve with (potentiometer)
positive overlap =P Option
Control PV = Pressure valves
Analog =A QV = Throttle/flow control valve

Output stages Customer version


1 output stage =1 V0 = Catalog version
1X = Component series 10 to 19
(10 to 19: Unchanged technical data
and pin assignment)
Serial number for types
527 = 2.7 A solenoid
537 = 3.7 A solenoid

Preferred types

Type Material number For proportional valves


VT-VRPA1-527-10/V0/RTP 0811405100 DBETFX
VT-VRPA1-527-10/V0/PV-RTP 0811405101 DREB6X
VT-VRPA1-537-10/V0/PV-RTP 0811405102 DBEB10Z / DREB10Z / DBETBX
VT-VRPA1-527-10/V0/QV-RTP 0811405103 4WRP6EA / 3FREZ
VT-VRPA1-537-10/V0/QV-RTP 0811405104 4WRP10EA

Suitable card holder:


– Open card holder VT 3002-1-2X/32F
(see data sheet 29928).
Only for control cabinet installation!

Front plate

LED green Enable


ON

LED red UB < UB min. UB


Q,P P Ramp Ramp
Q= Q= LED yellow Ramp off
off QP
100% 100%
α
Sensitivity ΔT
(100...50 %) max. β
5 sec α β

UE UE Tmin = 0,05 s t
UE =10 V UE =10 V max. Tmax = 5 s
– zero
Q,P P +
valve
Zero point adjustment
(±10 %) Lvdt

UE UE LED yellow Cable break


UE =10 V UE =10 V
+15 V b16
+UB 24 V=
DC +UB
+10 V b18 Supply
b32 DC b28
+10 V/50 mA –15 V
b30
Enable
8.5 V=
z16 b2
100 k Safety logic
8,5…40 V= b4
max 40 V= L– 0V
On * Neutral point
z32 10 V UB Lvdt. b12 ST – 0 V
α β
RE 30054/03.12 VT-VRPA1-5...-1X/...-RTP

Zero point b14


0… 10 V z10 Sensitivity b24
Block diagram with pin assignment

UEI 100 k + α β DC
b26
0V z12 – AC
100 k
Command 0… 10 V Osz./Dem.
values 0… 10 V b10
UEII 10 k +UB
0… 10 V z8 b6
UEIII 10 k
b12 b8
8.5 V=
8,5…40 V= b20
100 k
1 2 3
max 40 V=
Ramp off
Size 6
b22
+10 V Size 10
0… 10 V z28
Test actual value 10 k
+UB
24 V
0V 24 V= U
z26
Error s
max 100 mA
Hydraulics Bosch Rexroth AG
3/6
4/6 Bosch Rexroth AG Hydraulics VT-VRPA1-5...-1X/...-RTP RE 30054/03.12

Technical data

Supply voltage Nominal 24 V =


UB at b16/b18 Battery voltage 21...40 V,
Rectified alternating voltage Ueff = 21...28 V
(one-phase, full-wave rectifier)
Smoothing capacitor, separately Recommendation: Capacitor module VT 11110 (see data sheet 30750)
at b16 – b2 (only necessary if the ripple of UB > 10 %
Valve solenoid max. A/W 2.7/25 (size 6) 3.7/50 (size 10)
Power consumption, max. W 35 60
Current consumption, max. A 1.5 2.5
Solenoid output Rectangular voltage, pulse-modulated
b6 – b8 Imax. = 2.7 A Imax. = 3.7 A
Command value UE III : 0...+10 V
UE III : 0 V
(z10)
(z12) }input
Difference

UE III : 0...+10 V
UE III : 0...+10 V
Signal source (command value) Potentiometer Ri = 1 kΩ
Supply with +10 V from b32 (10 mA) or external source
Actual value feedback Osci b26 Test point z28 1)
0811405100 10.2 Veff / 7.8 kHz 0...+10 V =
0811405101 10.2 Veff / 7.8 kHz 0...+10 V =
0811405102 10.8 Veff / 7.8 kHz 0...+10 V =
0811405103 10.2 Veff / 7.8 kHz 0...+10 V =
0811405104 10.8 Veff / 7.8 kHz 0...+10 V =
Enable output stage At z16, U = 8.5...40 V; e. g. 10 V from z 32
LED (green) on front plate lights up
Ramp OFF At b20; U = 8.5...40 V
Cable lengths between amplifier and Solenoid cable: < 20 m 1.5 mm2
valve 20...50 m 2.5 mm2
Position transducer: Max. 50 m with 100 pF/m
Supply and capacitor 1.5 mm2
LED displays green: Enable
yellow: Cable break actual value / ramp OFF
red: UB < UB min. (approx. 21 V)
Error message
– Cable break actual value z26: Switching output
– UB too low No error +24 V (max. 100 mA)
– ±15 V stabilization Error 0 V
Short-circuit-proof outputs Output stage to the solenoid, Signal to the positional transducer
Supply voltage for potentiometer
Special features Cable break protection for actual value cable,
Position control with PID behavior,
Pulsed output stage,
Fast energization and fast deletion for short actuating times,
Adjustable ramp that can be switched off
Adjustment via trimming potentiometer 1. Zero point 3. Acceleration ramp
2. Sensitivity 4. Braking ramp
Circuit board format mm (100 x 160 x approx. 35) / (W x L x H)
Europe format with front plate 7 TE
Plug-in connection Connector DIN 41612 – F32
Ambient temperature °C 0...+70
Storage temperature range °C –20...+70
Weight m 0.36 kg
Notice:
Power zero b 2 and control zero b 12 must be bridged. If the distance to the power supply unit is < 1 m, directly onto the DIN connector.
With larger distances, lead the control zero separately to the ground.
1) 0 V with I = 0 V (enable OFF), +10 V with I = max. (U = 10 V, potentiometer = c )
m m E W
RE 30054/03.12 VT-VRPA1-5...-1X/...-RTP Hydraulics Bosch Rexroth AG 5/6

Setting information

Information for the use of ramps In case of Ramp OFF or Cable break, any ramp started be-
Ramp ON: No signal at b20. fore will be canceled. Transition to the signal end value is ef-
fected by means of a step.
Ramp OFF: 8.5...40 V at b20 or connection between b22
and b20.

Unit dimensions (dimensions in mm)


35

Plug-in connector
DIN 41612 - F 32

100
24 V= Mains

160

Project planning / maintenance instructions / additional information


– The amplifier card may only be unplugged and plugged when de-energized.
– The distance to aerial lines, radios and radar systems must be sufficient (> 1 m).
– Do not lay solenoid and signal lines near power cables.
– For signal lines and solenoid conductors, we recommend using shielded cables.
The cable shield must be connected to the control cabinet extensively and as short as possible.
– The valve solenoid must not be connected to free-wheeling diodes or other protective circuits.
– The cable lengths and cross-sections specified on page 4 must be complied with.
6/6 Bosch Rexroth AG Hydraulics VT-VRPA1-5...-1X/...-RTP RE 30054/03.12

Notes

Bosch Rexroth AG © This document, as well as the data, specifications and other informa-
Hydraulics tion set forth in it, are the exclusive property of Bosch Rexroth AG. It
Zum Eisengießer 1 may not be reproduced or given to third parties without its consent.
97816 Lohr am Main, Germany The data specified above only serve to describe the product. No state-
Phone +49 (0) 93 52 / 18-0 ments concerning a certain condition or suitability for a certain applica-
documentation@boschrexroth.de tion can be derived from our information. The information given does not
www.boschrexroth.de release the user from the obligation of own judgment and verification. It
must be remembered that our products are subject to a natural process
of wear and aging
RE 30054/03.12 VT-VRPA1-5...-1X/...-RTP Hydraulics Bosch Rexroth AG 7/6

Notes

Bosch Rexroth AG © This document, as well as the data, specifications and other informa-
Hydraulics tion set forth in it, are the exclusive property of Bosch Rexroth AG. It
Zum Eisengießer 1 may not be reproduced or given to third parties without its consent.
97816 Lohr am Main, Germany The data specified above only serve to describe the product. No state-
Phone +49 (0) 93 52 / 18-0 ments concerning a certain condition or suitability for a certain applica-
documentation@boschrexroth.de tion can be derived from our information. The information given does not
www.boschrexroth.de release the user from the obligation of own judgment and verification. It
must be remembered that our products are subject to a natural process
of wear and aging
Bosch Rexroth AG Hydraulics VT-VRPA1-5...-1X/...-RTP RE 30054/03.12

Notes

Bosch Rexroth AG © This document, as well as the data, specifications and other informa-
Hydraulics tion set forth in it, are the exclusive property of Bosch Rexroth AG. It
Zum Eisengießer 1 may not be reproduced or given to third parties without its consent.
97816 Lohr am Main, Germany The data specified above only serve to describe the product. No state-
Phone +49 (0) 93 52 / 18-0 ments concerning a certain condition or suitability for a certain applica-
documentation@boschrexroth.de tion can be derived from our information. The information given does not
www.boschrexroth.de release the user from the obligation of own judgment and verification. It
must be remembered that our products are subject to a natural process
of wear and aging