NAYA

This document provides specifications for an aluminum conductor, PVC insulated cable with nominal cross-sectional areas ranging from 10 to 400 mm2. The cable is intended for use in building wiring installed in conduits in dry locations and can also be used as a grounding conductor. Electrical data including resistance, inductance, and current carrying capacity are provided for each nominal cross-sectional area.

Uploaded by

henry_gt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views1 page

NAYA

This document provides specifications for an aluminum conductor, PVC insulated cable with nominal cross-sectional areas ranging from 10 to 400 mm2. The cable is intended for use in building wiring installed in conduits in dry locations and can also be used as a grounding conductor. Electrical data including resistance, inductance, and current carrying capacity are provided for each nominal cross-sectional area.

Uploaded by

henry_gt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NAYA 10- -400

NAYA 10 400mm²
mm² 450/750
450/750 V V
Al / PVC
(Aluminium Conductor, PVC Insulated)
Adapted Specification : IEC 60227-1 : 2007 ; IEC 60228 : 2004

Construction Data
APPLICATION :
Nom. Overall Cable
For building wire installed in conduit in dry
Cross Diameter Weight location, sometimes can be used as grounding
Aluminium Conductor

Section conductor, inherently flame retardant in


Area approx. approx. compliance with IEC 60332-1.
mm� mm kg/km
Special Features on Request
10 6.2 54 • Oil Resistance PVC Insulation
16 7.3 77 • Flame Retardant Cat. A, B, C
• Heat Resistance
25 9.0 117 • Nylon Coated
35 10.1 153
50 12.2 210
70 13.7 271
95 16.0 374
120 17.7 452
150 19.7 559
185 22.0 696
Note :
240 25.1 903 Conductor Shaped
300 27.9 1,119 10 - 400 sqmm supplied in non compacted circular stranded (rm) conductor shape
400 31.3 1,410 Standard Packing
10 - 400 sqmm supplied in wooden drum @1000 m
Length Tolerance per drum ± 2%

Electrical Data
Conductor Insulation Inductance Current-Carrying Short
Nom. DC AC Insulation Capacity circuit current
at 30°C * at
Cross Resistance Resistance Resistance
1 sec
Sect. at 20°C at 70°C at 70°C in pipe in air

Max. Max. Min. Max. Max. Max.


(mm²) (Ω/km) (Ω/km) (M.Ω.km) (mH/km) (A) (A) (kA)

10 3.08 3.701 0.0065 0.274 35 57 0.76


16 1.91 2.295 0.0050 0.258 48 77 1.22
25 1.20 1.442 0.0050 0.257 65 101 1.90
35 0.868 1.043 0.0040 0.249 80 123 2.66
50 0.641 0.771 0.0045 0.248 103 154 3.80
70 0.443 0.533 0.0035 0.239 129 191 5.32
95 0.320 0.385 0.0035 0.239 162 226 7.22
120 0.253 0.305 0.0032 0.235 184 269 9.12
150 0.206 0.249 0.0032 0.235 - 305 11.40
185 0.164 0.199 0.0032 0.235 - 348 14.06
240 0.125 0.152 0.0032 0.233 - 410 18.24
300 0.100 0.123 0.0030 0.232 - 473 22.80
400 0.0778 0.097 0.0028 0.229 - 566 30.40
22133-01 Rev. 0.0 / 2009